Reset to Factory Defaults

SED2 VFD Electronic Bypass Option Operating Instructions

Reset to Factory Defaults

Parameter

Description

 

 

Action

Setting/

 

 

Default

 

 

 

 

 

 

 

 

 

 

 

P0010

Reset to Factory Default

1.

Press

to enter the SED2

P0010:

P0970

 

Setting = 30

 

 

parameter mode and to display

 

Resets SED2 parameters to the

 

Default = 0

 

factory defaults.

 

r0000.

 

 

 

 

 

 

P0970:

 

 

 

 

 

 

 

2.

Press

to advance to

Setting = 1

 

 

Default = 0

 

 

 

parameter P0010.

 

 

 

 

 

 

3.

Press

to access the

 

 

 

 

parameter values level.

 

 

 

4.

Press

to advance to 30.

 

 

 

5.

Press

to confirm and save

 

 

 

 

the setting.

 

 

 

6.

Press

to go to parameter

 

 

 

 

P0970.

 

 

 

 

7.

Press

to access the

 

 

 

 

parameter values level.

 

 

 

8.

Press

to advance to 1.

 

 

 

9.

Press

to confirm and save

 

 

 

 

the setting.

 

 

 

 

 

 

 

NOTES:

1. First set P0010 = 30.

2. Stop SED2 (that is, disable all pulses) before you reset parameters to factory default values.

3. The following parameters retain their values after a factory reset:

P0918 (address of CB, communications board or module)

P2010 (USS baud rate)

P2011 (USS address)

4. The reset process takes about 10 seconds.