Siemens 125-3208 Selection of Command Source, Start Command, Selection of Frequency, Setpoint

Models: 125-3208

1 64
Download 64 pages 51.63 Kb
Page 35
Image 35
Selection of Frequency

Startup Procedures

Parameter

 

Description

 

 

Action

Setting/

 

 

 

Default

 

 

 

 

 

 

 

 

 

 

 

 

P0700[1]**

Selection of Command Source

1.

Press

to advance to index

Setting = 1

 

(Start Command)

 

 

 

 

 

[1], IN001, HAND.

Default = 1

 

Selects the command source as

 

 

 

 

 

 

 

 

 

follows:

2.

Press

to confirm index

 

 

 

 

 

 

0

= Factory default setting

 

selection.

 

 

 

 

 

 

 

 

1

= BOP (keypad)

3.

Press

to advance to 1.

 

 

2

= Terminal digital input

4.

Press

to confirm and save

 

 

 

 

 

 

4

= USS on BOP link (AOP)

 

the setting.

 

 

 

 

 

 

 

5

= USS on COM link

5.

Press

again to return to the

 

 

6

= CB (Communications board

 

parameter selection level.

 

 

 

 

 

 

 

or module) on COM link (P1/N2)

 

 

 

 

 

 

 

 

 

 

 

NOTE:

Changing this parameter resets (to default) all settings on the selected item. For example, changing from 1 to 2 resets all digital inputs to default settings.

P1000[0]**

Selection of Frequency

1.

Press

to advance to

Setting = 2

 

Setpoint

 

 

 

 

 

parameter P1000.

Default = 2

 

(Speed Command Source)

 

 

 

 

 

 

 

 

 

Selects the frequency setpoint

2.

Press

to access the

 

 

 

parameter indexes.

 

 

source as follows:

 

 

 

 

 

1

= Motor potentiometer

3.

Press

to advance to index

 

 

setpoint/BOP (keypad)

 

[0], IN000, AUTO.

 

 

2

= Analog input

4

Press

to confirm index

 

 

 

 

 

 

3

= Fixed frequency setpoint

 

selection.

 

 

 

 

 

 

 

 

4

= USS on BOP Link/AOP

5.

Press

to advance to 2.

 

 

5

= USS on COM link

6.

Press

to confirm and save

 

 

 

 

 

 

6

= CB (Communications board

 

the setting.

 

 

or module) on COM link (P1/N2)

 

 

 

 

 

 

 

 

 

 

 

** Parameters have two index settings: IN000 = Auto and IN001 = Hand.

Siemens Building Technologies, Inc.

27

Page 35
Image 35