Configuration Overview

3.4 Open the Telnet Interface

To access configuration using Telnet:

1.Open a Telnet connection on a computer with an Ethernet connection to the Liebert unit. To do this:

Open a command prompt window—click the Start button, then Run.

Enter cmd and click OK.

In the command prompt window that opens, enter telnet

followed by a space and the IP address or hostname of the Web card—for example:

telnet 192.168.0.125

2.When the message at right appears in the command prompt window, press the Enter key.

3.Enter the Administrator username and password (both are case- sensitive):

a.Login (username—default is Liebert)

b.Password (default is Liebert)

NOTE

C:>telnet 192.168.0.125

RTCS v2.96.00 Telnet server

Service Port Manager Active <Esc> Ends Session

Login: Liebert

Password: ********

For security, change the default username and password (see 5.7 - Change Username / Password).

4.In the Main Menu, enter the number that corresponds to your choice. Refer to 3.1 - Guide to Configuration for details on each function.

5.After making changes, return to the Main Menu and choose Exit and Save to reboot the Web card and put your changes into effect (see 3.6 - Saving Changes and Reinitializing the Web Card).

Main Menu

----------

1:System Information

2:IP Network Settings

3:Messaging

4:Factory Settings

5:Firmware Updates

q:Quit and abort changes

x:Exit and save

Please select a key ?>