Preparing to Update Liebert IntelliSlot Firmware

A.2.3 Open the Telnet Interface

To connect to the card using Telnet:

1. Open a Telnet connection on a computer with an Ethernet connection to the Liebert unit.

To do this:

Open a command prompt window—click the Start button, then Run.

Enter cmd and click OK.

In the command prompt window that opens, enter telnet fol- lowed by a space and the IP address of the Web card—for exam- ple:

telnet 192.168.0.125

2.When the message at right appears in the command prompt window, press the Enter key.

3.Enter the Administrator username and password (both are case- sensitive):

a.Login (username—default is Liebert)

b.Password (default is Liebert)

C:>telnet 192.168.0.125

RTCS v2.96.00 Telnet server

Service Port Manager Active <Esc> Ends Session

Login: Liebert

Password: ********

A.2.4 Open the Web Interface

To connect to the card using the Web interface:

1.Open a Web browser such as Internet Explorer.

2.Enter the IP address of the Web card in the address bar—e.g., 192.168.0.125.

3.Click on a tab at the top of the window.

Configure and

Support Tabs

A.3 PREPARING TO UPDATE LIEBERT INTELLISLOT FIRMWARE A.3.1 Requirements to Update the Liebert IntelliSlot Card’s Firmware

Make sure you have the following before starting the update:

Firmware upgrade downloaded from Liebert’s Web site (see A.3.3 - Download the Firmware Upgrade File to the Computer)

A computer running Internet Explorer 5.5 or newer

A Liebert IntelliSlot card

A connection to the Liebert IntelliSlot card

Null modem cable—serial upgrade method

Ethernet connection—TFTP or HTTP upgrade method

An Internet connection

A3