Network Settings

SNMP Communications Menu

Use the SNMP Communications Menu to enable authentication traps and view or change communi- ties and trap communities, events and parameters. For details on viewing support information, see 9.2 - Events and Parameters.

Table 12 SNMP communications menu

Parameter

Description & Telnet Menus

Authentication Traps

Enables authentication traps to receive security alerts when the Web card detects

a request with an invalid community string.

 

 

Enables the RFC-1628 (UPS specific information) MIB on the Web card for

RFC-1628 (UPS) MIB

querying of information in that MIB. This can be enabled or disabled independently

 

of the Liebert Global Products MIB.

Traps

This option enables the RFC-1628 traps to be sent when an alarm event occurs on

the device. The parent option must be enabled for this to also be enabled.

 

 

Enables the Liebert Global Products MIB (Enterprise Specific) for querying of

Liebert Global Products MIB

information in that MIB. This option can be enabled or disabled independently of

 

the RFC-1628 MIB.

Condition Traps

Enables event condition traps to be sent per the LGP MIB. The parent option must

be enabled for this to also be enabled.

 

System Notify Trap Enabled

Enables system traps to be sent per the LGP MIB. The parent option must be also

enabled for this to be enabled.

 

Heartbeat Trap Interval

Specifies how often a heartbeat trap will be sent to show that the device is online

and functioning normally.

 

Display/Modify Communities

View devices that have permission to access the Web card, identified by IP address or hostname, read/ write permission and community string. Up to 20 devices may be configured for access.

 

 

 

 

Communities - Example

 

 

 

 

 

 

 

-------------------------

 

 

 

 

 

 

 

1:

 

10.0.0.5

 

 

write

 

public1

 

 

 

 

2:

 

 

10.0.0.6

 

 

write

 

public1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Entry

 

IP

Access

Community

Codes for

 

 

#

 

address

(read/write)

 

string

 

<a>dd

 

<d>elete

<e>dit

 

 

 

 

editing

 

Complex lines allowed. e.g. <a 198.1.1.1 write public> ?>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Each device is identified by:

Entry Number - use the entry number (1-20) to edit or delete an entry

IP address or Hostname - the address of the device with access (MultiLink server, Nform server, Network Management System)

Access (read/write) - read allows users to view but not change data; write allows full permission for configuration, control and viewing

Community string - the community string used by the IP host for this Entry Number (case-sensitive, up to 32 characters)

To make changes:

Add a device (see example at right to enter all parameters in one line):

Example

• Enter a to add an entry, then press Enter.

a 10.0.0.5 write public1

• Enter the IP address or hostname of the device to be added, then press

(then press Enter)

Enter.

 

Enter 1 for read or 2 for write access for this device, then press Enter.

Enter the community string, then press Enter.

17

Page 21
Image 21
Emerson IS-WEB485ADPT installation manual Snmp Communications Menu, Display/Modify Communities, Snmp communications menu