Emerson IS-WEB485ADPT installation manual Specify Web Server Settings, Web server settings

Models: IS-WEB485ADPT

1 60
Download 60 pages 45.63 Kb
Page 23
Image 23

Network Settings

5.4Web Server

Use the Web Server Menu to configure access to the card through the Web interface. Consult your network adminis- trator if needed.

5.4.1Specify Web Server Settings

Web Server Menu

 

 

----------------

 

 

1: Web Server Mode

HTTP (Not Secure)

2: HTTP Transport Port

80

 

3: Password Protect Site

'disabled'

4: Configuration/Control

'enabled'

5: Refresh Rate

30

seconds

<ESC>: Cancel menu level Please select a key ?>

Terminal Emulation (Serial or TCP/IP Connection) / Telnet

To change any parameters:

1.Choose IP Network Settings from the Main Menu, then Web Server.

2.Select an option to change, then use the following guide to make changes.

Table 13 Web server settings

Parameter

Description & Valid Settings

 

 

 

Select the operation mode of the Web server.

Web Server

Disabled - Web server is disabled

Mode

HTTP - Standard Web port, not encrypted

 

HTTPS - Standard secure Web port, all communication is encrypted

 

Web Server listening port number.

HTTP

• For HTTP mode (non-encrypted communications), the default port is 80.

• For HTTPS mode (encrypted communications), the default port is 443.

Transport

For HTTPS, you must also install a security certificate for Internet Explorer. Refer to the appro-

Port

priate section for your version of Internet Explorer:

 

5.4.2 - Install Security Certificates - Internet Explorer 6 or earlier

 

5.4.3 - Install Security Certificates - Internet Explorer 7 or later

Password

When enabled, the entire site is password-protected. (If disabled, all pages are accessible

Protect Site

without a password except configure and control functions.)

Configuration/

Enable or disable the use of a Web browser to perform configuration and control operations.

Note: This feature affects configuration and control operations from the Web interface only. If

Control

disabled, these functions may still be available using other system interfaces.

 

 

 

 

The interval in seconds (10 to 600 seconds) between automatic updates of dynamic Web

Refresh

pages—parametric data and device status in the right panel.

RECOMMENDATION: Consider whether frequent updates will slow down the system. If many

Interval

users will access the device simultaneously, select a larger value to best serve all users.

 

 

Recommended values range from 20 to 60 seconds.

 

 

Web Interface

To access Web Server settings through the Web interface:

Click on the Configure tab, then Web in the left panel and finally Edit in the right panel. After making changes, click Save.

Configure tab

Web

Edit

 

19

Page 23
Image 23
Emerson IS-WEB485ADPT installation manual Specify Web Server Settings, Web server settings