Environmental Conditions

Install the Electronic Bypass Option in a heated, indoor controlled environment that is free of moisture and conductive contaminants such as condensation and dust. The air entering the unit for ventilation/cooling must be clean and free from corrosive gases.

The ambient temperature must be between 14°F and 104°F (-10°C to 40°C) and the relative humidity must be 0% to 95% noncondensing. Do not mount unit in direct sunlight.

Mechanical Installation

Inspection

1.As you unpack the Electronic Bypass Option, check for shipping damage. In the event of damage, contact the transport company.

2.Locate the Electronic Bypass Option nameplate and confirm that the unit is configured to the installation requirements.

3.Verify the delivery is complete. If not, contact the supplier.

Dimensions and Weights

Figure 5 shows overall and mounting dimensions for the Electronic Bypass Option. Figures 6 through 8 show conduit locations.

Approximate weights are as follows.

 

 

 

 

 

 

 

Bypass

Weight lb (kg)

 

Frame Size

 

 

 

 

A

45

(20)

 

B

55

(25)

 

C

75

(34)

 

D

150 (68)

 

E

180 (82)

 

F

470

(213)

NOTE: Exact weight will be affected by actual horsepower/voltage and selected power options.