Siemens 125-3208 operating instructions Output relay on the Controller board

Models: 125-3208

1 64
Download 64 pages 51.63 Kb
Page 16
Image 16
Output relay on the Controller board.

SED2 VFD Electronic Bypass Option Operating Instructions

VFD0108R1

Pushbutton/Indicator

Description

 

When the Interlock DIP switch is enabled, the Interlock Start Logic Enable

 

indicator is on steady. Any call to start the motor in either VFD or bypass

 

modes will not start the motor; instead it will close the Programmable

 

Output relay on the Controller board.

 

The Programmable Output can be used to actuate another device. When

INTERLOCKSTARTLOGIC Enable Commanded Proofed

this occurs, the Interlock Start Logic Commanded indicator also lights,

 

and the Interlock Start Logic Proofed indicator flashes.

 

A contact closure from this other device is wired to the Interlock Start on

 

the Controller board which then starts the motor and turns the Interlock

 

Start Logic Proofed indicator on steady. This feature is also called

 

damper end switch relay logic.

 

 

8

Siemens Building Technologies, Inc.

Page 16
Image 16
Siemens 125-3208 operating instructions Output relay on the Controller board