Siemens 125-3208 operating instructions Operation for Europe/N, America, Rated Motor Voltage

Models: 125-3208

1 64
Download 64 pages 51.63 Kb
Page 31
Image 31
Operation for Europe/N.

Startup Procedures

Parameter

Description

 

 

Action

Setting/

 

 

Default

 

 

 

 

 

 

 

 

 

 

 

P0100

Operation for Europe/N.

1.

Press

to advance to

Setting = 1

 

America

 

 

0 = 50 Hz, kW (Europe)

 

parameter P0100.

Default = 0 or

 

 

 

 

1

 

factory default

2

Press

to access the

(Default is

 

1 = 60 Hz, hp

 

parameter values level.

 

 

 

 

determined by

 

(North America)

3.

Press

to advance to 1.

the setting of

 

 

the motor

 

2 = 60 Hz, kW

 

 

 

frequency and

 

(North America)

4.

Press

to confirm and save

unit of

 

 

measurement

 

 

 

the P0100 = 1 setting.

 

The setting of Motor Frequency

 

DIP switches.)

 

 

 

 

 

and Unit of Measurement DIP

 

 

 

 

 

switch 2 overrides P0100

 

 

 

 

 

settings 0 and 1.

 

 

 

 

 

 

 

 

 

 

NOTES:

1. Stop the SED2 (that is, disable all pulses) before changing this parameter.

2. Changing P0100 resets all rated motor parameters as well as other parameters that depend on the rated motor parameters (such as P0340, Calculation of motor Parameters).

P0304*

Rated Motor Voltage

1.

Press

to advance to

Setting =

 

 

Motor

 

10V to 2000V.

 

parameter P0304.

nameplate

 

Rated motor voltage (V) from

2.

Press

to access the

Default =

 

motor nameplate.

 

parameter values level.

Varies by

 

 

 

 

 

model

 

 

3.

Press

to advance to

 

 

 

 

nominal voltage.

 

 

 

4.

Press

to confirm and save

 

 

 

 

the setting.

 

 

 

 

 

 

 

 

* Motor related

parameters.

 

 

 

 

Siemens Building Technologies, Inc.

23

Page 31
Image 31
Siemens 125-3208 operating instructions Operation for Europe/N, America, Rated Motor Voltage