SED2 VFD Electronic Bypass Option Operating Instructions

Parameter

Description

 

 

Action

Setting/

 

 

Default

 

 

 

 

 

 

 

 

 

 

 

P1121

Ramp-down time

1.

Press

to advance to

Site Setting

 

 

 

 

0s to 650s

 

parameter P1121.

Default = 30

 

 

 

 

 

 

2.

Press

to access the

Typical fan =

 

 

 

parameter values level.

120s

 

 

3.

Press

to advance it desired

Typical pump =

 

 

30s

 

 

 

value.

 

 

 

 

4.

Press

to confirm and save

 

 

 

 

the setting.

 

 

 

 

 

 

 

NOTES:

1. Setting the ramp-up time too short can cause the SED2 to trip (F0001 over current, F0002 over voltage, or F0003 under voltage.

2. If using an external frequency setpoint with set ramp rates (such as from a PLC), achieve optimum SED2 performance by setting ramp times (P1120 and P1121) slightly shorter than those of the PLC.

P3900

End Quick Commissioning

1.

Press

to advance to

Setting = 1

 

 

 

 

0 = End without motor calculation

 

parameter P3900.

Default = 0

 

 

 

 

 

or factory reset.

 

 

 

 

 

1 = End with motor calculation

2.

Press

to access the

 

 

 

parameter values level.

 

 

and factory reset (recommended

 

 

 

 

 

on SED2 without bypass option).

3.

Press

to advance to 1.

 

 

2 = End with motor calculation

 

 

 

 

 

 

 

and with I/O reset.

4.

Press

to confirm the

 

 

 

 

 

3 = End with motor calculation

 

setting.

 

 

 

but without I/O reset

 

 

 

 

 

(recommended with SED2 with

 

 

 

 

 

bypass option).

 

 

 

 

 

 

 

 

 

 

NOTES:

1. P0010 must always be set back to 0 before operating the motor.

2. If P3900 is greater than 0 on completion of commissioning, P0010 is automatically set back to 0.

3. If P0700 either indeed was changed during this process, programming of P0704 = 3 is required.

30