Motor Current: Flying Start

SED2 VFD Electronic Bypass Option Operating Instructions

Parameter

Description

 

 

Action

Setting/

 

 

Default

 

 

 

 

 

 

 

 

 

 

 

P1202

Motor Current: Flying Start

1.

Press

to enter the SED2

Minimum = 10

 

 

Default = 100

 

Defines search current used for

 

parameter mode and to display

Maximum =

 

flying start. Value is in % based

 

r0000.

 

200

 

on the rated motor current

 

 

 

 

 

(P0305).

2.

Press

to advance to

 

 

 

 

 

 

 

parameter P1202.

 

 

 

3.

Press

to access the

 

 

 

 

parameter values level.

 

 

 

4.

Press

to advance to

 

 

 

 

desired value.

 

 

 

5.

Press

to confirm and save

 

 

 

 

the setting.

 

 

 

 

 

 

 

NOTE:

Reducing the search current may improve performance for flying start if the inertia of the system is not very high.

P1203

Search Rate: Flying Start

1.

Press

to enter the SED2

Minimum = 10

 

 

Default = 100

 

Sets factor by which the output

 

parameter mode and to display

Maximum =

 

 

r0000.

 

 

frequency changes during flying

 

 

200

 

start to synchronize with the

 

 

 

 

 

turning motor. This value,

2.

Press

to advance to

 

 

entered in % relative to the

 

 

 

parameter P1203.

 

 

default time factor, defines the

 

 

 

 

 

 

 

 

initial gradient and influences the

 

 

 

 

 

time taken to search for the

3.

Press

to access the

 

 

motor frequency.

 

 

 

parameter values level.

 

 

 

 

 

 

The search time is the time taken

 

 

 

 

 

to search through all frequencies

4.

Press

to advance to

 

 

between

 

desired value.

 

 

f_max + 2 × f_slip to 0 Hz.

 

 

 

 

 

 

5.

Press

to confirm and save

 

 

 

 

the setting.

 

 

 

 

 

 

 

NOTES:

1. P1203 = 100% is defined as giving a rate of 2% of f_slip, nom/ms.

2. P1203 = 200% would result in a rate of frequency change of 1% of f_slip, nom/ms.

3. A higher value produces a flatter gradient, and thus a longer search time. A lower value has the opposite effect.

32

Siemens Building Technologies, Inc.

Page 40
Image 40
Siemens 125-3208 operating instructions Motor Current Flying Start, r0000, Search Rate Flying Start