Siemens 125-3208 operating instructions Pulse Frequency, r0000

Models: 125-3208

1 64
Download 64 pages 51.63 Kb
Page 45
Image 45
Pulse Frequency

Startup Procedures

Pulse Frequency

Parameter

Description

 

 

Action

Setting/

 

 

Default

 

 

 

 

 

 

 

 

 

 

 

P1800

Pulse Frequency

1.

Press

to enter the SED2

Minimum = 4

 

 

 

 

Sets pulse frequency (kHz) of

 

parameter mode and to display

Default =

 

power switches in SED2. The

 

r0000.

 

Varies by

 

frequency can be changed in

 

 

 

model

 

increments of 2 kHz.

2.

Press

to advance to

(hp/voltage

 

 

dependent)

 

 

 

parameter P1800.

 

Pulse frequencies > 4 kHz

 

 

 

 

 

 

Maximum = 16

 

selected on 380V to 480V units

 

 

 

 

 

 

 

 

 

reduce the maximum continuous

3.

Press

to access the

 

 

motor current.

 

parameter values level.

 

 

 

4.

Press

to advance to

 

 

 

 

desired value.

 

 

 

5.

Press

to confirm and save

 

 

 

 

the setting.

 

 

 

 

 

 

 

NOTES:

1. Minimum pulse frequency depends on P1082 (maximum frequency) and P0310 (rated motor frequency).

2. At 4 kHz, full output current is obtained up to 50 degrees C (CT mode); over 50 degrees C, full output may be obtained at 8 kHz.

3. If silent operation is not absolutely necessary, lower pulse frequencies may be selected to reduce SED2 losses and radio-frequency emissions.

4. Under certain circumstances, the SED2 may reduce the switching frequency to provide protection against over-temperature.

Siemens Building Technologies, Inc.

37

Page 45
Image 45
Siemens 125-3208 operating instructions Pulse Frequency, r0000