Table 6. SED2 Specifications (Continued).

Drive Specifications

Description

Auxiliary supply 24V

Glavanically separated, unregulated auxiliary supply (18V to 32V) 100 mA

Overload capacity

110% for 60 seconds

Control method

Linear, parabolic and programmable V/f; and flux current control low-power

 

mode

PWM frequency

4k Hz to 16k Hz (adjustable in 2k Hz increments)

Fixed frequencies

15 programmable

Skip frequency bands

4 programmable

 

 

Setpoint resolution

0.01 Hz digital, 0.01 Hz serial, 10 bit analog

Digital inputs

6: fully programmable and scalable isolated digital inputs, switchable

(sink/source)

 

Analog inputs

2: 0 to 10 Vdc, 0/4 to 20 mA, can also be configured as digital inputs or

 

Ni 1000 input

Relay outputs

2: configurable 30 Vdc/5A (resistive), 250 Vac 2A (inductive)

 

 

Analog outputs

2: programmable (0/4 to 20 mA)

 

 

Serial interface

RS-485 Transmission rate: Up to 38.4k Baud

 

Protocols: Siemens, P1 and Johnson, N2;

Protection level

IP20: NEMA Type 1 with protective shield and gland plate installed

 

IP54: NEMA Type 12 (400V and 500V series only)

 

Temperature ranges

Operating: 14°F to 104°F (–10°C to 40°C)

Storage: –40°F to 158°F (–40°C to 70°C)

 

Humidity

95% rh, non-condensing

Operational altitudes

Up to 3280 ft (1000m) above sea level without de-rating

 

 

Protection features

Under-voltage, Over-voltage, Overload, Ground fault, Short circuit, Stall

 

prevention, Locked motor, Motor overtemperature l2t PTC, Over-temperature,

 

Parameter PIN protection

Standards

UL, cUL

NOTE: SED2 Compliance with EN61000-3-12:

From September 1st, 2005 all electrical apparatus covered by the EMC directive will have to comply with EN61000-3-12 “Limits for harmonic currents produced by equipment connected to public low voltage systems with input currents > 16A and =< 75 A per phase”.

Siemens variable speed drives of the product range SED2 (Micromaster 436) fulfil the requirements of the EN 61000-3-12 (without the need for external line reactors) regarding the THD values of Table 3 under the pre condition of Rsce > 190. The required PWHD values will not be achieved. Due to this fact it is recommended to apply for connection approval at the local electricity board.

The local electricity board will evaluate among many other data the content of the 5th harmonic current and the Line Power Factor "Lambda”, which is the ratio of active power and apparent power.

Siemens frequency inverters are optimized in design and operation characteristics regarding energy efficiency and less interference with line supplies.