SERVICE CLEARANCE
MODELS: PT036 - PT120
D
C
A
B
MODELS: PT180 - PT360
D
E
C
A
B
NOTE: Only two condenser fans for models PT180 - PT240.
NOTE: All dimensions are in cm.
MODEL |
|
| DIMENSIONS |
| ||
NUMBER |
| A | B |
| C | D |
PT036 | 85 | 105 |
| 85 | 150 | |
PT048 | 85 | 105 |
| 85 | 150 | |
PT060 | 85 | 105 |
| 85 | 150 | |
PT075 | 90 | 105 |
| 90 | 200 | |
PT090 | 90 | 105 |
| 90 | 200 | |
PT100 | 90 | 105 |
| 90 | 200 | |
PT120 | 90 | 105 |
| 90 | 200 |
A:Clearance dimension from condenser coil
B: Clearance dimension from compressor, control box, blower, evaporator coil & filter
C:Clearance dimension from condenser coil & filter
D:Clearance dimension over the condenser fan
MODEL |
|
| DIMENSIONS |
|
| |
NUMBER | A | B |
| C | D | E |
PT180 | 120 | 120 |
| 115 | 250 | 90 |
PT215 | 120 | 120 |
| 115 | 250 | 90 |
PT240 | 120 | 120 |
| 115 | 250 | 90 |
PT300 | 120 | 120 |
| 115 | 250 | 90 |
|
|
|
|
|
|
|
PT360 | 120 | 120 |
| 115 | 250 | 90 |
A : Clearance dimension from condenser coil
B : Clearance dimension from compressor, control box & evaporator coil
C : Clearance dimension from condenser coil & blower
D : Clearance dimension over the condenser fan
E : Clearance dimension from filter access panel
RIGGING INSTRUCTIONS
ATTENTION TO RIGGERS
•Insert 2" nominal pipe through holes in the base rail as shown in the figure below for slings.
•Holes in base rail are centered around the unit center of gravity.
•Use wooden pallet or spreader bar when rigging, to prevent the slings from damaging the unit.
•Rollers may be used to move the unit on the roof or ground.
CAUTION: All panels should be in place when rigging.
MODELS: PT036 - PT360
LIFT | LIFT |
| SPREADER BAR |
| PROPER CLEARANCE TO BE |
| PROVIDED. |
COMPRESSOR |
|
END |
|
| Note: |
NOMINAL PIPE THRU UNIT FOR SLINGS TO AVOID BASE DAMAGE. | 1 .PIPE DIA 1 1/2" FOR PT036 TO PT075 MODELS |
2. PIPE DIA 2" FOR PT090 TO PT360 MODELS |
5