Cooline manual Rigging Instructions, Models PT036 PT120 Models PT180 PT360, Models PT036 PT360

Page 6

SERVICE CLEARANCE

MODELS: PT036 - PT120

D

C

A

B

MODELS: PT180 - PT360

D

E

C

A

B

NOTE: Only two condenser fans for models PT180 - PT240.

NOTE: All dimensions are in cm.

MODEL

 

 

DIMENSIONS

 

NUMBER

 

A

B

 

C

D

PT036

85

105

 

85

150

PT048

85

105

 

85

150

PT060

85

105

 

85

150

PT075

90

105

 

90

200

PT090

90

105

 

90

200

PT100

90

105

 

90

200

PT120

90

105

 

90

200

A:Clearance dimension from condenser coil

B: Clearance dimension from compressor, control box, blower, evaporator coil & filter

C:Clearance dimension from condenser coil & filter

D:Clearance dimension over the condenser fan

MODEL

 

 

DIMENSIONS

 

 

NUMBER

A

B

 

C

D

E

PT180

120

120

 

115

250

90

PT215

120

120

 

115

250

90

PT240

120

120

 

115

250

90

PT300

120

120

 

115

250

90

 

 

 

 

 

 

 

PT360

120

120

 

115

250

90

A : Clearance dimension from condenser coil

B : Clearance dimension from compressor, control box & evaporator coil

C : Clearance dimension from condenser coil & blower

D : Clearance dimension over the condenser fan

E : Clearance dimension from filter access panel

RIGGING INSTRUCTIONS

ATTENTION TO RIGGERS

Insert 2" nominal pipe through holes in the base rail as shown in the figure below for slings.

Holes in base rail are centered around the unit center of gravity.

Use wooden pallet or spreader bar when rigging, to prevent the slings from damaging the unit.

Rollers may be used to move the unit on the roof or ground.

CAUTION: All panels should be in place when rigging.

MODELS: PT036 - PT360

LIFT

LIFT

 

SPREADER BAR

 

PROPER CLEARANCE TO BE

 

PROVIDED.

COMPRESSOR

 

END

 

 

Note:

NOMINAL PIPE THRU UNIT FOR SLINGS TO AVOID BASE DAMAGE.

1 .PIPE DIA 1 1/2" FOR PT036 TO PT075 MODELS

2. PIPE DIA 2" FOR PT090 TO PT360 MODELS

5

Image 6
Contents Installation Operation Maintenance Manual Contents Index Model Decoding Models PT036 PT060 Direct Drive Motor Models PT075 PT360 Belt Driven Motor General WarrantySafety Issues General StatementInstallation Instructions GeneralLocation of Unit Rigging Instructions Models PT036 PT120 Models PT180 PT360Models PT036 PT360 Duct Connection Unit Weight & Weight DistributionCondensate Drain Connection Electric HeatersUnit Dimensions PT036 PT075PT090 PT120 PT180 TOP View Side View Front ViewPT215 PT240 PT300 PT360 Operation Instructions Cable SizeSTART-UP Inspection & Check List Models PT075 & PT090 Electrical DataModels PT036 PT060 Models PT100 & PT120Models PT180 & PT215 Models PT240 & PT300Model PT360 AUTO/MANUAL Reset of the Alarm Signals Electronic ThermostatCrankcase Heater Pump Down ControlMaintenance Instructions Cleaning of Coils & FiltersBelts Typical High and LOW Voltage Field Wiring ConnectionsBelt Tension Testing Procedure Belt Tension Checker Measure the Belt Deflection ForceFrequency of MAINTENANCE, Months Preventive Maintenance ScheduleMaintenance TOOLS/EQUIPMENT Required E MTrouble Shooting Chart Symptom Causes Check & Corrective MeasureUnit works continuously, no sufficient Low suction pressure Typical Schematic Wiring Diagram Models PT036 PT075 Single compressor unitsAuxiliary Relay Models PT090 PT120 Dual compressor units Connection Applicable for Volt Free Contact Options Models PT180 PT240 Dual compressor units Standard Options 1. UVM Option Models PT300 PT360 Dual compressor units Terminal Block or Termination Point PT240L PT300L PT360L Parts ListModel Number Optional Items