Cooline PT360, PT036 manual Standard Options 1. UVM Option

Page 28

TYPICAL SCHEMATIC WIRING DIAGRAM

MODELS : PT180 - PT240 (Dual compressor units)

STANDARD OPTIONS 1. UVM OPTION

TO HVTB

TO HVTB

2. SMOKE DETECTOR OPTION

3. VOLT FREE CONTACT OPTIONS

A. UNIT ON & OFF INDICATION OPTION

COMP. WITH CIRCUIT BREAKER OPTION

HVTB

LUG

LOW AMBIENT OPTION

C. BM ON,OFF & TRIP INDICATION OPTION

FAN MOTOR CONTROL CONNECTION

(APPLICABLE FOR FM WITH T.O.P)

A) STANDARD CONNECTION

B) WITH LOW AMBIENT OPTION

 

LEGEND

AR

AUXILIARY RELAY

AFS

AIRFLOW SWITCH

ATB

AUXILIARY TERMINAL BLOCK

BM

BLOWER MOTOR

BMC

BLOWER MOTOR CONTACTOR

CC

COMPRESSOR CONTACTOR

CCA

AUXILIARY CONTACT

CB

CIRCUIT BREAKER

C. HTR

CRANKCASE HEATER

COMP

COMPRESSOR

ECB

ELECTRONIC CONTROL BOARD

FCS

FAN CYCLING SWITCH

F

FUSE

FL

FUSE LINK

FM

FAN MOTOR (CONDENSER)

FMC

FAN MOTOR CONTACTOR

FR

FAULT RELAY

HC

HEATER CONTACTOR

HPS

HIGH PRESSURE SWITCH

HVTB

HIGH VOLTAGE TERMINAL BLOCK

HTR

HEATER

JP

JUMPER

L1

LINE 1

L2

LINE 2

L3

LINE 3

LPS

LOW PRESSURE SWITCH

LUG

LUG GROUND

NTB

NEUTRAL TERMINAL BLOCK

O/L

OVER LOAD

OHT

OVER HEAT THERMOSTAT

PDS

PUMP DOWN SOLENOID

SSPS

SOLID STATE PROTECTIVE SYSTEM

SD

SMOKE DETECTOR

TRANS

TRANSFORMER

T'STAT

THERMOSTAT

UVM

UNDER VOLTAGE MONITOR

_ _ _

FIELD WIRING

 

+DISCONNECT TAB - 1/4"

SPLICE-CLOSED END

TERMINAL BLOCK OR TERMINATION POINT

NOTES

1.POWER SUPPLY, 380/415V-3PH-50Hz.

2.ANY WIRE REPLACEMENT SHOULD BE OF 900C OR ITS EQUIVALENT. USE COPPER CONDUCTOR WIRES ONLY.

3.IF PDS & HEATERS ARE FACTORY INSTALLED, PLEASE READ BROKEN LINES AS CONTINUOUS LINES.

4.POWER MUST BE SUPPLIED TO CRANKCASE HEATER FOR MINIMUM OF 12 HOURS PRIOR TO SYSTEM START UP. IF POWER IS OFF 6 HOURS OR MORE, CRANKCASE HEATER MUST BE ON FOR 12 HOURS BEFORE OPER- ATING THE SYSTEM.

FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RE- SULT IN COMPRESSOR DAMAGE.

5.FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER TO BE PROVIDED BY CONSUMER WITH RATING AS RECOMMENDED BY COOLINE.

6.COMPRESSORS ARE PROVIDED WITH INTERNAL OVERLOAD.

7.IF COMPRESSOR IS SUPPLIED WITH SSPS, CONNECT AS SHOWN. PLEASE ALLOW 2-3 MINUTES FOR SSPS SWITCH TO CLOSE, BEFORE STARTING THE UNIT.

8.IF ANY CHANGE IN DIP SWITCH SETTING IS REQUIRED, TURN OFF POWER FIRST & SET REQUIRED SETTING.

27

Image 28
Contents Installation Operation Maintenance Manual Contents IndexModels PT036 PT060 Direct Drive Motor Model DecodingModels PT075 PT360 Belt Driven Motor Warranty Safety IssuesGeneral General StatementGeneral Installation InstructionsLocation of Unit Models PT036 PT120 Models PT180 PT360 Rigging InstructionsModels PT036 PT360 Unit Weight & Weight Distribution Condensate Drain ConnectionDuct Connection Electric HeatersUnit Dimensions PT036 PT075PT090 PT120 PT180 TOP View Side View Front ViewPT215 PT240 PT300 PT360 Cable Size Operation InstructionsSTART-UP Inspection & Check List Electrical Data Models PT036 PT060Models PT075 & PT090 Models PT100 & PT120Models PT240 & PT300 Models PT180 & PT215Model PT360 AUTO/MANUAL Reset of the Alarm Signals Electronic ThermostatCrankcase Heater Pump Down ControlMaintenance Instructions Cleaning of Coils & FiltersTypical High and LOW Voltage Field Wiring Connections Belt Tension Testing ProcedureBelts Belt Tension Checker Measure the Belt Deflection ForcePreventive Maintenance Schedule Maintenance TOOLS/EQUIPMENT RequiredFrequency of MAINTENANCE, Months E MTrouble Shooting Chart Symptom Causes Check & Corrective MeasureUnit works continuously, no sufficient Low suction pressure Typical Schematic Wiring Diagram Models PT036 PT075 Single compressor unitsAuxiliary Relay Models PT090 PT120 Dual compressor units Connection Applicable for Volt Free Contact Options Models PT180 PT240 Dual compressor units Standard Options 1. UVM Option Models PT300 PT360 Dual compressor units Terminal Block or Termination Point Parts List Model NumberPT240L PT300L PT360L Optional Items