CONDENSATE DRAIN CONNECTION
•
•
•
Use standard PVC pipe with NPT connection for the condensate drain. Provide a 'P' trap immediately at the condensate drain connection. Piping has to be sloped away from the unit.
Remember to remove the drain hole plug before operating the unit. Avoid bends & elbows.
DUCT CONNECTION
The units can be connected to the ducting in horizontal configuration. Connect ducting using flexible duct connection. The duct should be properly designed and the drive package should match the required CFM & corresponding external static pressure.
ATTENTION: Avoid abrupt changes in size and/or direction of duct to ensure proper unit performance.
ELECTRIC HEATERS
Electric heater kit is installed in the unit at the supply air opening space.
UNIT WEIGHT & WEIGHT DISTRIBUTION
MODEL |
|
| WEIGHTS (Kg.) |
|
| |
|
|
|
|
|
| |
NUMBER | J | K | M | L | P | Q |
| ||||||
PT036 | 67 | 36 | 51 | 34 | - | - |
|
|
|
|
|
|
|
PT048 | 72 | 41 | 57 | 39 | - | - |
|
|
|
|
|
|
|
PT060 | 76 | 45 | 62 | 42 | - | - |
PT075 | 86 | 52 | 70 | 45 | - | - |
|
|
|
|
|
|
|
PT090 | 116 | 92 | 95 | 73 | - | - |
|
|
|
|
|
|
|
PT100 | 134 | 91 | 98 | 73 | - | - |
PT120 | 135 | 91 | 98 | 73 | - | - |
|
|
|
|
|
|
|
PT180 | 155 | 99 | 152 | 85 | 108 | 105 |
|
|
|
|
|
|
|
PT215 | 182 | 89 | 94 | 101 | 177 | 103 |
PT240 | 186 | 94 | 98 | 105 | 181 | 107 |
|
|
|
|
|
|
|
PT300 | 226 | 130 | 202 | 148 | 221 | 158 |
|
|
|
|
|
|
|
PT360 | 256 | 145 | 216 | 151 | 249 | 175 |
|
|
|
|
|
|
|
J |
| P |
CONDENSER SECTION
M |
| Q |
= =
SUPPLY AIR/
RETURN AIR
K
L
6