Cooline PT036, PT360 manual Crankcase Heater, Pump Down Control

Page 17

7.LEAD/LAG OPERATION: Whenever a compressor needs to be on, the controller will turn on the compressor with the shorter accumulated run time provided its 3 minutes minimum off time has lapsed. Otherwise the other compressor will on first. Similarly, the compressor with the longer accumulated run time will be the first one to be cut off. This is to load the compressors evenly over long run period. Balance loading is enabled when compressor #1 lead option is disabled.

8.AUTO MODE: In Auto mode, operating mode will be selected automatically between Heat and Cool mode, depend- ing on the Room Temperature and Set Temperature.

9.ERROR CODE:

Error code is displayed on the LCD panel. When system on and error code is shown, the ON/OFF LED on the LCD panel will blink. When system off, error code is still display for thermistor error but the ON/OFF LED will be off.

E06 Compressor 1 high pressure trip (or contact open)

E07 Compressor 2 high pressure trip (or contact open), (not applicable for single compressor units) E10 Compressor 1 low pressure trip

E11 Compressor 2 low pressure trip, (not applicable for single compressor units)

CRANKCASE HEATER

The crankcase heater is provided to hold the compressor oil reservoir at higher temperature than the coldest part in the system.

Power must be supplied to crankcase heater for a minimum of 12-hours prior to system start-up. If power is off for 6-hours or more, crankcase heater must be energized for 12-hours before operating the system. Otherwise compressor damage may result.

PUMP DOWN CONTROL

If the unit is provided with pumpdown system, then a solenoid type valve is installed in the liquid line ahead of expansion valve to prevent flow of refrigerant into the evaporator during off cycle. The controller is wired to solenoid valve which energize in cooling and opening the valve. Whenever the thermostat temperature is satisfied, the solenoid will close followed compressor off after pumping the refrigerant from low side of the system until the low pressure switch open the control circuit.

16

Image 17
Contents Installation Operation Maintenance Manual Index ContentsModels PT075 PT360 Belt Driven Motor Model DecodingModels PT036 PT060 Direct Drive Motor Safety Issues WarrantyGeneral General StatementLocation of Unit Installation InstructionsGeneral Models PT036 PT360 Rigging InstructionsModels PT036 PT120 Models PT180 PT360 Condensate Drain Connection Unit Weight & Weight DistributionDuct Connection Electric HeatersPT036 PT075 Unit DimensionsPT090 PT120 TOP View Side View Front View PT180PT215 PT240 PT300 PT360 START-UP Inspection & Check List Operation InstructionsCable Size Models PT036 PT060 Electrical DataModels PT075 & PT090 Models PT100 & PT120Model PT360 Models PT180 & PT215Models PT240 & PT300 Electronic Thermostat AUTO/MANUAL Reset of the Alarm SignalsPump Down Control Crankcase HeaterCleaning of Coils & Filters Maintenance InstructionsBelt Tension Testing Procedure Typical High and LOW Voltage Field Wiring ConnectionsBelts Belt Tension Checker Measure the Belt Deflection ForceMaintenance TOOLS/EQUIPMENT Required Preventive Maintenance ScheduleFrequency of MAINTENANCE, Months E MSymptom Causes Check & Corrective Measure Trouble Shooting ChartUnit works continuously, no sufficient Low suction pressure Models PT036 PT075 Single compressor units Typical Schematic Wiring DiagramAuxiliary Relay Models PT090 PT120 Dual compressor units Connection Applicable for Volt Free Contact Options Models PT180 PT240 Dual compressor units Standard Options 1. UVM Option Models PT300 PT360 Dual compressor units Terminal Block or Termination Point Model Number Parts ListPT240L PT300L PT360L Optional Items