Smith Cast Iron Boilers JW527, JWF507, JW727 Vacuum Relief Valves, Closed System/Thermal Expansion

Page 13

DO NOT use any pumps, valves, or fittings that are not com- patible with potable water.

DO NOT use valves that may cause excessive restriction to water flow. Use full flow ball or gate valves only.

DO NOT use any lead based solder in potable water lines. Use appropriate tin-antimony or other equivalent material. DO NOT tamper with the aquastat, burner or temperature and pressure relief valve. Tampering voids all warranties. Only qualified service technicians should service these com- ponents.

DO NOT use with piping that has been treated with chro- mates, boiler seal, or other chemicals.

DO NOT add any chemicals to the system piping which will contaminate the potable water supply.

Closed System/Thermal Expansion

Periodic discharge of the temperature and pressure relief valve may be due to thermal expansion in a closed water supply system. The water utility supply meter may contain a check valve, backflow preventer or water pressure-reducing valve. This will create a closed water system. During the heating cycle of the water heater, the water expands caus- ing pressure inside the water heater to increase. This may cause the temperature and pressure relief valve to dis- charge small quantities of hot water. To prevent this, it is rec- ommended that a diaphragm-type expansion tank (suitable for potable water) be installed on the cold water supply line. The expansion tank must have a minimum capacity of 5.6 litres (1.5 US gallons) for every 190 litres (50 US gallons) of stored water and be rated at the working pressure of the water heater. Contact the local water supplier or plumbing inspector for information on other methods to control this sit- uation.

Important: Do not plug or remove the temperature and pressure relief valve.

Temperature and Pressure (T&P) Relief Valve

Water Supply Systems”, ANSI Z21.22/CSA 4.4”. The function of the temperature and pressure relief valve is to discharge water in large quantities in the event of excessive temperature or pressure developing in the water heater. The valve’s relief pressure must not exceed the working pres- sure of the water heater as stated on the data plate.

Important: Only a new temperature and pressure relief valve should be used with your water heater. Do not use an old or existing valve as it may be damaged or not adequate for the working pressure of the new water heater. Do not place any valve between the relief valve and the tank.

The Temperature and Pressure Relief Valve:

Must not be in contact with any electrical part.

Must be connected to an adequate discharge line.

Must not be rated higher than the working pressure shown on the data plate of the water heater.

The Discharge Line/Driptube:

Must not be smaller than the pipe size of the relief valve or have any reducing coupling installed in the discharge line.

Must not be capped, blocked, plugged or contain any valve between the relief valve and the end of the dis- charge line.

Must terminate a maximum of 300mm (12 in.) (Canada) or 150mm (6 in.) (U.S.A.) above the floor.

Must be capable of withstanding 121°C (250°F) without distortion.

Must be installed to allow complete drainage of both the valve and discharge line.

NOTE: Rear and Combination flue units must be fitted with a T&P Relief Valve WATTS type 40XL-5 or equivalent.

Failure to install and maintain a new, properly listed temperature and pressure relief valve will release the manufacturer from any claims which may result from excessive temperature or water pressure.

WARNING

Explosion Hazard

If the temperature and pressure relief valve is dripping or leaking, have a licensed plumber repair it.

Do not plug valve.

Do not remove valve.

Failure to follow these instructions can result in death or an explosion.

For protection against excessive pressures and tempera- tures, a temperature and pressure relief valve must be installed in the opening marked “T&P RELIEF VALVE”. This valve must be design certified by a nationally recognized testing laboratory that maintains periodic inspection of the production of listed equipment or materials as meeting the requirements of the “Standard For Relief Valves For Hot

Vacuum Relief Valves

A vacuum relief valve, installed in the cold water supply line above the top of the water heater, shall protect the water heater against siphoning (loss of water due to loss of supply pressure). Where heating equipment has a bottom supply, the cold water supply piping shall be carried above the top of the heater before being routed to the supply connection and have a vacuum relief valve installed in it at a level above the top of the storage tank. The vacuum relief valve shall be in compliance with the latest edition of “Standard For Relief

Valves For Hot Water Supply Systems, ANSI Z21.22/CSA 4.4”.

– 13 –

Image 13
Contents What to do if YOU Smell OIL For Your SafetyImmediately call your oil supplier Table of Contents For Installations in Canada II SafetyIntroduction Consumer ResponsibilitiesSafety Warning Flammable Vapours For Installations in the United StatesSafety Warning Scalding Relief Valve Requirements T&PLocation Requirements Oil Supply Clearances and AccessibilityEarthquake Zones JWF307V Installation Dimensions Center Flue Models Air Requirements Where the water heater is locatedAir Supply Ducted Furnace Room And/or roomVent and Exhaust Connections Power Venting Blocked Vent Safety SwitchWater Supply Plumbing Connections Center Flue Filling the Water HeaterVacuum Relief Valves Temperature and Pressure Relief ValveClosed System/Thermal Expansion Discharge Line/DriptubeElectrical Supply Installation Of The Aquastat Temperature Control48245 Water Temperature Regulation Installation ChecklistIV Operation Water Heater Sounds Anode MaintenanceSmoke/Odour Anode Rod/Water OdourMaintenance Re-Starting The Heater After Shut- Down Shut Down For Extended PeriodsVI Combo Heating Combo Heating Baseboard InstallationVII OIL Burner Listing Beckett AFG GSW-J5006 WHO is Covered Limited WarrantyHOW the Original Owner can Make a Warranty Claim

JW327, JW517, JWF307V, JWF657, JWF507 specifications

Smith Cast Iron Boilers have established a strong reputation in the heating industry for their durable, efficient, and reliable products. Among their notable models are the JWF507, JW717, JWF657, JW327, and JW517. Each of these models incorporates advanced technologies and unique features tailored to meet various heating demands.

The JWF507 is renowned for its exceptional thermal efficiency. This boiler utilizes a water-to-water heat exchanger, providing efficient heat transfer, which significantly reduces fuel consumption. Its robust cast iron construction ensures longevity, even in harsh conditions, while an oversized heat exchanger design enhances performance and reliability.

The JW717 model stands out with its ability to handle large-scale heating needs. This boiler features a multi-pass design that maximizes heat transfer and minimizes the chance of overheating. Additionally, it is equipped with an advanced control system that allows for precise temperature adjustments, ensuring optimal comfort in residential and commercial settings.

The JWF657 introduces a unique burner design, which improves combustion efficiency and reduces emissions. This model also features a built-in pump which enhances the system's circulation, helping to maintain consistent and comfortable heating throughout the space. With its energy-efficient attributes, the JWF657 is a top choice for environmentally-conscious consumers.

Next in line, the JW327 model is designed for versatility and adaptability. This boiler can easily be integrated into various heating systems, making it suitable for both retrofit and new construction projects. Its compact size allows for easy installation in tight spaces, while its high-efficiency rating contributes to lower energy bills.

Lastly, the JW517 model is known for its reliability and user-friendly design. This boiler is equipped with an intuitive control panel, making operation simple and straightforward. Its rugged cast iron construction is designed to withstand rigorous use, providing peace of mind for users who seek a dependable heating solution.

In summary, Smith Cast Iron Boilers offer a diverse portfolio with models like the JWF507, JW717, JWF657, JW327, and JW517, each boasting unique features and technologies. From high thermal efficiency and advanced combustion systems to user-friendly designs and rugged durability, these boilers are crafted to deliver optimal performance in various heating applications. Whether for residential or commercial use, these models exemplify the superior quality and innovation that Smith Cast Iron Boilers is known for.