Smith Cast Iron Boilers GVIOM-5R manual Vertical Venting

Page 8

Page 8

GV100W BOILER

INSTALLATION & OPERATING INSTRUCTIONS

Vent Connections to Chimneys

Use Type B1 or single wall metal vent pipe from the boiler to the chimney. If used, a 4 in to 5 in, 102 mm to 127 mm increaser must be fastened directly to the boiler vent collar with sheet metal screws no longer than 1/2 in, 13 mm. Use the shortest, straightest vent system possible for the particular application. The vent system should be sloped up toward the chimney 1/4 in/ft, 2 cm/m. Ensure that the flue pipe is properly supported and each connection securely fastened with at least 3 corrosion resistant sheet metal screws. The termination of the vent pipe must be flush with the inside of the chimney flue.

Always provide a minimum clearance of 6 in, 152 mm, between single wall metal vent pipe and any combustible materials. Type B1 vent may be used, clearance between it and any combustible material must be as listed.

WARNING: Failure to maintain minimum clearances between vent connectors and combustible materials can result in a fire causing extensive property damage, severe personal injury or death!

FIG NO. 4 Chimney Venting

CHIMNEY

Single Wall Metal Vent

GV100W boilers may be vented vertically using single wall metal vent pipe sized per Table 1. Galvanized sheet metal pipe must have a minimum wall thickness of 26 gauge. In Canada, pipe constructed of .025 in, 0.63 mm, thick aluminum or .018 inch thick stainless steel may be required.

The use of thimbles, firestops and other protective devices when penetrating combustible or noncombustible construction must be in accordance with all applicable national and local codes.

WARNING: Single wall vent pipe must NEVER pass through interior walls or through floors or ceilings! Failure to comply with this warning could result in a fire causing extensive property damage, severe personal injury or death!

An unused chimney flue can be used as a raceway for single wall metal pipe, see FIG. NO. 4A.

WARNING: Never run vent pipe through a chimney flue that has another appliance attached to it! Never connect another appliance to a pressurized vent system, it must serve only one appliance. Failure to comply with this warning can result in excessive levels of carbon monoxide causing severe personal injury or death!

LINER

THIMBLE

VENT SYSTEM

BOILER

CLEANOUT

A listed vent terminal designed for the type of pipe being used must complete the vertical run where it exits the chimney. If the chimney is on an outside wall or in an unheated space the optional condensate tee and trap pictured in FIG. NO. 4A may be required. The trap is made by ty-rapping a loop in the 3/8" clear plastic tubing attached to the tee and filling it with water.

Do not operate the boiler without this trap!

FIG. NO 4A Vertical Venting Through a Chimney

CHIMNEY

VERTICAL VENTING

B Vent

The boiler may be vented vertically using the proper size Type B1 vent pipe. Do not use the boiler as a load bearing element. The vent system must be fully supported by the building structure. Use an approved vent terminal at the vent outlet which must extend at least 3 ft, 1 m, above the highest point where it passes through the roof. In addition, the vent pipe must be at least 2 ft, 0.6 m higher than any portion of the building within a horizontal distance of 10 ft, 3 m.

THIMBLE

CONDENSATE

DRAIN ASS'Y

VENT

SYSTEM

BOILER

Image 8
Contents GV100W GV100W Boiler Installation & Operating Instructions Boiler Ratings & Capacities Boiler LocationCombustible Floor Option Boiler Dimensions Fresh Air ⁄4 Wire Metal Wooden Duct Size Combustion AIRCommon Vent Systems Combustion Air Duct SizingChimney Venting Chimney Inspection & SizingVertical Venting No B Horizontal VentingHeating System Piping System Bypass Pump Away BypassReverse Acting Aquastats Pumped BlendPiping For Use With Cooling Units GAS Supply Piping CirculatorsElectrical Wiring Thermostat InstallationEquivalent Pipe Length Chart CO DetectorsFIG. no Fenwal/Honeywell Hot Surface Ignition FIG. no Multi-Zone Diagram For Your Safety Read Before Operating Operating InstructionsTo Turn OFF GAS to Appliance Property damage, personal injury or loss of lifePour Votre Sécurité Lisez Avant DE Mettre EN Marche Direct Ignition Systems Boiler SET-UPBoiler Operation Checking & Adjustment Boiler Maintenance Burner InstallationHeat Exchanger Cleaning Burner RemovalInstructions to the Installer GV100 Series Repair Parts Name of PartRef # Name of Part HSI Fenwall Ignition SystemNorth ELM Street WESTFIELD, MA 01085 TEL 562-9631 FAX 413

GVIOM-5R specifications

The Smith Cast Iron Boilers GVIOM-5R is a high-efficiency, versatile heating solution designed for both residential and commercial applications. This model is particularly renowned for its robust construction, impressive performance, and energy-saving features. With a focus on durability, the GVIOM-5R is built from high-quality cast iron, which not only ensures longevity but also excellent thermal mass for effective heat retention.

One of the main features of the GVIOM-5R is its fire-tube design, which enhances heat transfer and allows for higher efficiency rates compared to traditional boiler designs. The fire-tube configuration ensures that flue gases travel through a series of tubes submerged in water, maximizing heat exchange and minimizing heat loss. This design contributes to an efficiency rating that often exceeds 85%, helping users to reduce their energy costs while maintaining comfort.

The boiler is equipped with advanced control technology, allowing for precise temperature management. This feature is critical for optimizing performance and ensuring consistent heating throughout the property. Additionally, an integrated diagnostic system enables users to monitor boiler operations and troubleshoot potential issues before they escalate, ensuring reliable performance and reducing downtime.

Another characteristic that sets the GVIOM-5R apart is its flexibility in fuel options. The boiler can operate on various fuels, including natural gas, propane, or oil, making it an adaptable choice for different heating needs. This multi-fuel capability not only provides versatility but also allows property owners to choose the most economical and efficient fuel source based on their specific circumstances.

Maintenance is also simplified with the GVIOM-5R, thanks to its accessible design that allows for easy servicing and parts replacement. The robust construction minimizes the need for frequent repairs, which enhances overall reliability and customer satisfaction.

In summary, the Smith Cast Iron Boilers GVIOM-5R combines durability, efficiency, and versatility. Its innovative fire-tube design, advanced control systems, multi-fuel capabilities, and ease of maintenance make it an outstanding choice for those seeking a reliable heating solution. Whether for a home or a commercial building, the GVIOM-5R stands out as a top-tier option that delivers consistent performance and long-term value.