Controls/Burners

Refer to the BOILER OPERATION and CHECKING and ADJUSTMENT sections in this manual.

1.Check the thermostat for proper operation.

2.If the boiler has been equipped with a low water cut-off device, L.W.C.O, ensure that it operates properly. A float type L.W.C.O. should be flushed out.

3.The relief valve should vent water when the test lever is lifted. It should not weep or discharge water at normal system pressure. Never try to clean or repair the relief valve! If the valve fails replace it!

4.The aquastat high limit controls the maximum water temperature in the boiler. It is adjustable from 140°F, 60°C, to 220°F, 104°C. If the water temperature reaches the set temperature before the demand for heat has been met, the aquastat high limit should shut the burners off. The outlet water temperature should never exceed 220°F, 104°C. If the aquastat high limit fails to function properly replace it.

5.Visually check the burner flames. See FIG. NO. 18.

INSTRUCTIONS TO THE INSTALLER

The installer must give this copy of the INSTALLATION AND OPERATING INSTRUCTIONS to the boiler owner and make sure that the owner or operator has a basic understanding of the following:

1.The lighting instructions, the type of ignition system installed and how it operates.

2.What the labels on the boiler say.

3.How to start up and shut off the boiler.

4.How to turn the gas and electrical power on or off.

5.What to do if the boiler ignition system locks out.

6.Where to check the system temperature and pressure and what they should be.

7.The importance of reading, understanding and following these instructions.

The installer must make sure that the owner knows to shut the boiler off and call for service if the following conditions occur:

1.Yellow lazy flames or flames outside the boiler jacket.

2.Gas smell or other strange odors.

3.Discoloration of the boiler or surrounding materials due to overheating.

4.Water leaking from the heating system piping or relief valve.

5.Flue products leaking from the vent system into the living space. Dampness or condensation in the building is a good indicator of this condition.

6.The boiler’s flame roll-out safety system is actuated.

7.Control malfunction or sporadic operation.

Image 21
Contents GV100W GV100W Boiler Installation & Operating Instructions Boiler Location Boiler Ratings & CapacitiesCombustible Floor Option Boiler Dimensions Combustion AIR Fresh Air ⁄4 Wire Metal Wooden Duct SizeCommon Vent Systems Combustion Air Duct SizingChimney Inspection & Sizing Chimney VentingVertical Venting Horizontal Venting Heating System PipingNo B Pump Away Bypass System BypassPumped Blend Piping For Use With Cooling UnitsReverse Acting Aquastats Circulators GAS Supply PipingThermostat Installation Electrical WiringEquivalent Pipe Length Chart CO DetectorsFIG. no Fenwal/Honeywell Hot Surface Ignition FIG. no Multi-Zone Diagram Operating Instructions For Your Safety Read Before OperatingTo Turn OFF GAS to Appliance Property damage, personal injury or loss of lifePour Votre Sécurité Lisez Avant DE Mettre EN Marche Boiler SET-UP Boiler OperationDirect Ignition Systems Checking & Adjustment Burner Installation Boiler MaintenanceHeat Exchanger Cleaning Burner RemovalInstructions to the Installer Name of Part GV100 Series Repair PartsHSI Fenwall Ignition System Ref # Name of PartNorth ELM Street WESTFIELD, MA 01085 TEL 562-9631 FAX 413

GVIOM-5R specifications

The Smith Cast Iron Boilers GVIOM-5R is a high-efficiency, versatile heating solution designed for both residential and commercial applications. This model is particularly renowned for its robust construction, impressive performance, and energy-saving features. With a focus on durability, the GVIOM-5R is built from high-quality cast iron, which not only ensures longevity but also excellent thermal mass for effective heat retention.

One of the main features of the GVIOM-5R is its fire-tube design, which enhances heat transfer and allows for higher efficiency rates compared to traditional boiler designs. The fire-tube configuration ensures that flue gases travel through a series of tubes submerged in water, maximizing heat exchange and minimizing heat loss. This design contributes to an efficiency rating that often exceeds 85%, helping users to reduce their energy costs while maintaining comfort.

The boiler is equipped with advanced control technology, allowing for precise temperature management. This feature is critical for optimizing performance and ensuring consistent heating throughout the property. Additionally, an integrated diagnostic system enables users to monitor boiler operations and troubleshoot potential issues before they escalate, ensuring reliable performance and reducing downtime.

Another characteristic that sets the GVIOM-5R apart is its flexibility in fuel options. The boiler can operate on various fuels, including natural gas, propane, or oil, making it an adaptable choice for different heating needs. This multi-fuel capability not only provides versatility but also allows property owners to choose the most economical and efficient fuel source based on their specific circumstances.

Maintenance is also simplified with the GVIOM-5R, thanks to its accessible design that allows for easy servicing and parts replacement. The robust construction minimizes the need for frequent repairs, which enhances overall reliability and customer satisfaction.

In summary, the Smith Cast Iron Boilers GVIOM-5R combines durability, efficiency, and versatility. Its innovative fire-tube design, advanced control systems, multi-fuel capabilities, and ease of maintenance make it an outstanding choice for those seeking a reliable heating solution. Whether for a home or a commercial building, the GVIOM-5R stands out as a top-tier option that delivers consistent performance and long-term value.