Emerson MAN -0016-00, UVC120 manual Position and Density of Detectors, Mounting the Detector

Page 24

POSITION AND DENSITY OF DETECTORS

The detector has a nominal 120º cone of vision. In an application such as a loading rack with a ceiling height of 25 feet (7.5 meters) where it is desired to have complete detector coverage at floor level and a detector is mounted 2 feet (0.6 meter) from the ceiling and pointed straight down, the distance from the detector to the designated level would be 23 feet (7 meters) and because of its 120º cone of vision the detector would cover a circular area 80 feet (24 meters) in diameter at floor level. A sketch of the area to be covered will indicate the number of detectors required to monitor the area. Detectors should be placed as close as practical to the expected fire hazard.

NOTE

Do not mount UV detectors close to the ceiling of enclosed buildings if smoke might accumulate before the break-out of flame. It is preferable to mount the detectors on walls a few feet (or about 1 meter) below the ceiling where they may respond before being obscured by smoke. Consider shortening time delay settings when smoke is expected to accumulate during a fire. If dense smoke is likely to accumulate prior to flame (as in an electrical fire), supplement UV detectors with other protection.

MOUNTING THE DETECTOR

Locate detectors to ensure an unobstructed view of the area to be monitored and where accessible for cleaning the detector window and vi reflecting surface. Take care so dirt will not accumulate and obscure the detector viewing window. Detectors mounted outdoors should be pointed downward to prevent the cone of vision from scanning the horizon where long duration lightning flashes or far-off arc welding may activate the detector. To minimize dirt accumulation around the vi surfaces, mount the detectors so that the internal vi tube is on top. The silver external reflector should be placed directly over the vi tube. Refer to Figures 2a and 2b for the detector and swivel mounting assembly dimensions. Refer to Figure 10 for a diagram of the assembled detector and swivel assembly.

Figure 10 - Detector with Swivel Mount Assembly

DIP SWITCH SETTINGS

NOTE

To make DIP switch changes take effect, cycle controller power off then on.

The DIP switches on the controller circuit board must be properly programmed before applying power to the system. There are three banks of 8 position DIP switches which are OFF or ON to select area and detector combinations, controller sensitivity, fire voting logic, output latching and

- 18 -

Image 24
Contents Ultraviolet Fire Detection System Page Page Page Table of Contents Unit V Maintenance Unit I General Information Detector Specifications Dimensions Basic Operation Controller Controller Faceplate Description Outputs Relay OutputsCurrent Outputs External Reset Automatic Diagnostics and Fault IdentificationProgramming Options Unit II UV Fire Detection DetectorSystem Application Petroleum Products HandlingDetector Sensitivity Spectral Sensitivity Range Gaseous Fuel HandlingOther Processes Cone of Vision System SensitivityUnit III System Installation Installation General Wiring RequirementsController Wiring Page W iring for U1F-UV with Non-Isolated Current Output W iring for U1F-UV with Isolated Current Output W iring for U2F-UV with Non-Isolated Output W iring Diagram for U2F-UV with Isolated Current Output W iring for U4F-UV with Non-Isolated Current Output W iring for U4F-UV with Isolated Current Output DIP Switch Settings Position and Density of DetectorsMounting the Detector Controller Sensitivity Adjustment Channel SelectionU1F, U2F and U4F U2F and U4FRelay Outputs LATCHING/NON-LATCHING Relay Outputs ENERGIZED/DE-ENERGIZEDExample Page Time Delay for Area Alarms Relay SettingsStartup Procedure Checkout ProcedureUnit IV System Operation Manual Check Procedure Alternate Test Procedure Normal Operation Fire ResponseCurrent Output Situation Main Menu Error Check Mode Err Chc Special Function MenuCurrent Calibration Mode CuC Unit V Maintenance Routine MaintenanceTroubleshooting Device Repair and ReturnPage Appendices B lis h ed in Accordance with E1A Standard Appendix B Procedure For Activating Reed Switches Appendix C Record Of Dip Switch Settings Appendix D Common Ultra-Violet Absorbing Gases Appendix E Wire Resistance In Ohms AWG #20 AWG #18 AWG #16 AWG #14 AWG #12 AWG #10 AWG #8

0016-00, UVC120, MAN -0016-00 specifications

The Emerson MAN-0016-00, UVC120, 0016-00 is a state-of-the-art device designed to meet the demands of modern industrial and commercial applications. This advanced model showcases Emerson’s commitment to innovation, providing users with reliable performance and cutting-edge technology.

One of the key features of the Emerson MAN-0016-00 is its superior control capabilities. Equipped with sophisticated algorithms, this device ensures precise and adaptable control over various processes, improving efficiency and productivity in operations. Users benefit from enhanced responsiveness to changing conditions, allowing for quick adjustments that lead to optimized performance.

Another noteworthy technology integrated into the UVC120 is its advanced user interface. The device boasts a highly intuitive control panel that facilitates easy navigation and management of settings. This user-friendly design minimizes the learning curve for operators, ensuring that they can quickly familiarize themselves with its functions. The display provides clear, real-time feedback, enabling users to monitor system performance effortlessly.

The Emerson MAN-0016-00 is also characterized by its robust construction. Designed to endure harsh environmental conditions, this model is built with durable materials that enhance its longevity and reliability. It is resistant to various industrial contaminants, ensuring consistent operation even in challenging settings.

Energy efficiency is a hallmark of the UVC120 model. By employing innovative power management technologies, it significantly reduces energy consumption without compromising performance. This emphasis on sustainability not only lowers operational costs for users but also aligns with global efforts to minimize environmental impact.

Moreover, the Emerson MAN-0016-00 incorporates advanced safety features that prioritize user protection. These include integrated alarms and emergency shut-off mechanisms that respond to detected anomalies, enhancing overall workplace safety. The design also adheres to international safety standards, ensuring compliance and peace of mind for users.

In conclusion, the Emerson MAN-0016-00, UVC120, 0016-00 stands out as an exemplary model in the field of industrial technology. Its combination of precision control, user-friendly interface, robust construction, energy efficiency, and safety features make it an ideal choice for various applications. As industries continue to evolve, devices like this play a crucial role in enhancing performance, safety, and sustainability across the board.