Emerson UVC120, MAN -0016-00 manual Time Delay for Area Alarms, Relay Settings

Page 28

TIME DELAY FOR AREA ALARMS

NOTE

Time delay affects the Area alarms only; the instant alarm operates as soon as a flame is detected.

The time delay for the Area alarms is set using SW 5.3 to SW 5.7. If all of the switches are placed in the ‘OFF’ position the time delay will be 0.5 seconds (minimum setting).

<SW 5.3-7: OFF: 0.5 sec. time delay

<SW 5.3: ON: 0.5 sec. time delay

<SW 5.4: ON: 1 sec. time delay

<SW 5.5: ON: 2 sec. time delay

<SW 5.6: ON: 4 sec. time delay

<SW 5.7: ON: 8 sec. time delay

If switch 5.8 is "OFF" then in Bypass mode:

-the current output is 4 m A

-the Fault Relay state rem ains unchanged (if it was energized, it rem ains energized; if it was de-energized, it remains de-energized)

If switch 5.8 is "ON" then in Bypass mode:

-the current output is 3 m A

-the Fault Relay is de-energized

The total time delay is the added value of the switches turned ON. Switches can be turned ON in any combination for a time delay from 0.5 to 15.5 seconds in half second increments. These switches are factory set to a 3.0 second time delay as shown in the example below.

Example:

SW 5.3

OFF

time delay

 

SW 5.4

ON

= 2.5 sec.

 

SW 5.5 ON

 

 

SW 5.6

OFF

 

 

SW 5.7

OFF

 

NOTE

SW 3.5 through SW 3.8 are not used.

RELAY SETTINGS

There are four relays on the controller circuit board that can be configured for normally OFF or normally ON operation by moving the jumpers which are located below the relays. See Figure 11c for the location of the relays on the circuit board and Figure 11d for the settings.

- 22 -

Image 28
Contents Ultraviolet Fire Detection System Page Page Page Table of Contents Unit V Maintenance Unit I General Information Detector Specifications Dimensions Basic Operation Controller Controller Faceplate Description Relay Outputs OutputsCurrent Outputs Automatic Diagnostics and Fault Identification External ResetProgramming Options Unit II UV Fire Detection DetectorSystem Application Petroleum Products HandlingGaseous Fuel Handling Detector Sensitivity Spectral Sensitivity RangeOther Processes Cone of Vision System SensitivityInstallation General Wiring Requirements Unit III System InstallationController Wiring Page W iring for U1F-UV with Non-Isolated Current Output W iring for U1F-UV with Isolated Current Output W iring for U2F-UV with Non-Isolated Output W iring Diagram for U2F-UV with Isolated Current Output W iring for U4F-UV with Non-Isolated Current Output W iring for U4F-UV with Isolated Current Output Position and Density of Detectors DIP Switch SettingsMounting the Detector Controller Sensitivity Adjustment Channel SelectionU1F, U2F and U4F U2F and U4FRelay Outputs ENERGIZED/DE-ENERGIZED Relay Outputs LATCHING/NON-LATCHINGExample Page Time Delay for Area Alarms Relay SettingsCheckout Procedure Startup ProcedureUnit IV System Operation Manual Check Procedure Alternate Test Procedure Normal Operation Fire ResponseCurrent Output Situation Main Menu Error Check Mode Err Chc Special Function MenuCurrent Calibration Mode CuC Unit V Maintenance Routine MaintenanceTroubleshooting Device Repair and ReturnPage Appendices B lis h ed in Accordance with E1A Standard Appendix B Procedure For Activating Reed Switches Appendix C Record Of Dip Switch Settings Appendix D Common Ultra-Violet Absorbing Gases Appendix E Wire Resistance In Ohms AWG #20 AWG #18 AWG #16 AWG #14 AWG #12 AWG #10 AWG #8

0016-00, UVC120, MAN -0016-00 specifications

The Emerson MAN-0016-00, UVC120, 0016-00 is a state-of-the-art device designed to meet the demands of modern industrial and commercial applications. This advanced model showcases Emerson’s commitment to innovation, providing users with reliable performance and cutting-edge technology.

One of the key features of the Emerson MAN-0016-00 is its superior control capabilities. Equipped with sophisticated algorithms, this device ensures precise and adaptable control over various processes, improving efficiency and productivity in operations. Users benefit from enhanced responsiveness to changing conditions, allowing for quick adjustments that lead to optimized performance.

Another noteworthy technology integrated into the UVC120 is its advanced user interface. The device boasts a highly intuitive control panel that facilitates easy navigation and management of settings. This user-friendly design minimizes the learning curve for operators, ensuring that they can quickly familiarize themselves with its functions. The display provides clear, real-time feedback, enabling users to monitor system performance effortlessly.

The Emerson MAN-0016-00 is also characterized by its robust construction. Designed to endure harsh environmental conditions, this model is built with durable materials that enhance its longevity and reliability. It is resistant to various industrial contaminants, ensuring consistent operation even in challenging settings.

Energy efficiency is a hallmark of the UVC120 model. By employing innovative power management technologies, it significantly reduces energy consumption without compromising performance. This emphasis on sustainability not only lowers operational costs for users but also aligns with global efforts to minimize environmental impact.

Moreover, the Emerson MAN-0016-00 incorporates advanced safety features that prioritize user protection. These include integrated alarms and emergency shut-off mechanisms that respond to detected anomalies, enhancing overall workplace safety. The design also adheres to international safety standards, ensuring compliance and peace of mind for users.

In conclusion, the Emerson MAN-0016-00, UVC120, 0016-00 stands out as an exemplary model in the field of industrial technology. Its combination of precision control, user-friendly interface, robust construction, energy efficiency, and safety features make it an ideal choice for various applications. As industries continue to evolve, devices like this play a crucial role in enhancing performance, safety, and sustainability across the board.