Emerson MAN -0016-00, UVC120 manual Manual Check Procedure

Page 30

The visual integrity test and the count test are performed at the same time.

1.Place the controller in the bypass mode (all outputs inhibited) by keeping the MENU/SET switch activated until ‘Chc’ ‘Err’ or ‘bPS’ are shown on the digital displays. Release the switch and activate it again until ‘bPS’ is shown on the right side of the display, then activate the SELECT/RESET switch. The right digital display will show ‘Chn’ and the left side of the digital display will show ‘bPS’.

2.Activate the MENU/SET switch again to toggle through the available channels. W hen the desired channel is shown on the left side of the display, activate the SELECT/RESET switch.

3.W hile in the bypass mode, the right side of the display will show the counts per second produced by the background UV in the detector’s range of vision. Activating the SELECT/RESET switch will perform the manual vi test, a significant increase in the count displayed should be observed. (Counts should be greater than 150 and less than 400. If the counts read are not with in this range the lens and reflector need cleaning or the vi adjustment allen screw the sensor on module needs to be repositioned (only available on tube modules with aluminum shroud.)

4.To exit the bypass mode, activate the MENU/SET switch repeatedly until ‘test’ is shown on the left side of the display. Now activate the SELECT/RESET switch.

NOTE

The Automatic vi system continuously monitors the operation of the detector but does not monitor external relays or equipment that may be operated from the relay outputs. It is important that the system be manually checked using the MANUAL check procedure on a regular basis. The whole system (including external equipment) should be checked periodically using a UV Test Lamp to simulate a fire.

MANUAL CHECK PROCEDURE

The whole system should be checked periodically with a UV test lamp to make sure that the detectors are not obstructed, that the area ‘seen’ by the detector has not changed and that there is no fault in the vi circuit.

1.Place the channel to be tested in bypass mode as described in the ‘MAIN MENU’ section of this manual.

2.Direct the UV test light into a detector viewing window. The counts per second displayed on the right display should increase to an alarm level.

3.Turn off the UV source.

4.Repeat the test for all detectors in the system.

5.After all detectors have been checked, return the system to the normal operating mode.

6.Restore power to output loads or remove any mechanical blocking devices.

- 24 -

Image 30
Contents Ultraviolet Fire Detection System Page Page Page Table of Contents Unit V Maintenance Unit I General Information Detector Specifications Dimensions Basic Operation Controller Controller Faceplate Description Outputs Relay OutputsCurrent Outputs External Reset Automatic Diagnostics and Fault IdentificationProgramming Options System Application Unit II UV Fire DetectionDetector Petroleum Products HandlingDetector Sensitivity Spectral Sensitivity Range Gaseous Fuel HandlingOther Processes Cone of Vision System SensitivityUnit III System Installation Installation General Wiring RequirementsController Wiring Page W iring for U1F-UV with Non-Isolated Current Output W iring for U1F-UV with Isolated Current Output W iring for U2F-UV with Non-Isolated Output W iring Diagram for U2F-UV with Isolated Current Output W iring for U4F-UV with Non-Isolated Current Output W iring for U4F-UV with Isolated Current Output DIP Switch Settings Position and Density of DetectorsMounting the Detector U1F, U2F and U4F Controller Sensitivity AdjustmentChannel Selection U2F and U4FRelay Outputs LATCHING/NON-LATCHING Relay Outputs ENERGIZED/DE-ENERGIZEDExample Page Time Delay for Area Alarms Relay SettingsStartup Procedure Checkout ProcedureUnit IV System Operation Manual Check Procedure Alternate Test Procedure Normal Operation Fire ResponseCurrent Output Situation Main Menu Error Check Mode Err Chc Special Function MenuCurrent Calibration Mode CuC Troubleshooting Unit V MaintenanceRoutine Maintenance Device Repair and ReturnPage Appendices B lis h ed in Accordance with E1A Standard Appendix B Procedure For Activating Reed Switches Appendix C Record Of Dip Switch Settings Appendix D Common Ultra-Violet Absorbing Gases Appendix E Wire Resistance In Ohms AWG #20 AWG #18 AWG #16 AWG #14 AWG #12 AWG #10 AWG #8

0016-00, UVC120, MAN -0016-00 specifications

The Emerson MAN-0016-00, UVC120, 0016-00 is a state-of-the-art device designed to meet the demands of modern industrial and commercial applications. This advanced model showcases Emerson’s commitment to innovation, providing users with reliable performance and cutting-edge technology.

One of the key features of the Emerson MAN-0016-00 is its superior control capabilities. Equipped with sophisticated algorithms, this device ensures precise and adaptable control over various processes, improving efficiency and productivity in operations. Users benefit from enhanced responsiveness to changing conditions, allowing for quick adjustments that lead to optimized performance.

Another noteworthy technology integrated into the UVC120 is its advanced user interface. The device boasts a highly intuitive control panel that facilitates easy navigation and management of settings. This user-friendly design minimizes the learning curve for operators, ensuring that they can quickly familiarize themselves with its functions. The display provides clear, real-time feedback, enabling users to monitor system performance effortlessly.

The Emerson MAN-0016-00 is also characterized by its robust construction. Designed to endure harsh environmental conditions, this model is built with durable materials that enhance its longevity and reliability. It is resistant to various industrial contaminants, ensuring consistent operation even in challenging settings.

Energy efficiency is a hallmark of the UVC120 model. By employing innovative power management technologies, it significantly reduces energy consumption without compromising performance. This emphasis on sustainability not only lowers operational costs for users but also aligns with global efforts to minimize environmental impact.

Moreover, the Emerson MAN-0016-00 incorporates advanced safety features that prioritize user protection. These include integrated alarms and emergency shut-off mechanisms that respond to detected anomalies, enhancing overall workplace safety. The design also adheres to international safety standards, ensuring compliance and peace of mind for users.

In conclusion, the Emerson MAN-0016-00, UVC120, 0016-00 stands out as an exemplary model in the field of industrial technology. Its combination of precision control, user-friendly interface, robust construction, energy efficiency, and safety features make it an ideal choice for various applications. As industries continue to evolve, devices like this play a crucial role in enhancing performance, safety, and sustainability across the board.