Emerson UVC120, MAN -0016-00 manual Appendix E Wire Resistance In Ohms

Page 43

Appendix E Wire Resistance In Ohms

DISTANCE (FEET)

AWG #20

AWG #18

AWG #16

AWG #14

AWG #12

AWG #10

AWG #8

100

1.02

0.64

0.40

0.25

0.16

0.1

0.06

200

2.03

1.28

0.80

0.51

0.32

0.2

0.13

300

3.05

1.92

1.2

0.76

0.48

0.3

0.19

400

4.06

2.55

1.61

1.01

0.64

0.4

0.25

500

5.08

3.2

2.01

1.26

0.79

0.5

0.31

600

6.09

3.83

2.41

1.52

0.95

0.6

0.38

700

7.11

4.47

2.81

1.77

1.11

0.7

0.44

800

8.12

5.11

3.21

2.02

1.27

0.8

0.5

900

9.14

5.75

3.61

2.27

1.43

0.9

0.57

1000

10.2

6.39

4.02

2.53

1.59

1.09

0.63

1250

12.7

7.99

5.03

3.16

1.99

1.25

0.79

1500

15.2

9.58

6.02

3.79

2.38

1.5

0.94

1750

17.8

11.2

7.03

4.42

2.78

1.75

1.1

2000

20.3

12.8

8.03

5.05

3.18

2

1.26

2250

22.8

14.4

9.03

5.68

3.57

2.25

1.41

2500

25.4

16

10

6.31

3.97

2.5

1.57

3000

30.5

19.2

12

7.58

4.76

3

1.88

3500

35.5

22.4

14.1

8.84

5.56

3.5

2.21

4000

40.6

25.5

16.1

10

6.35

4

2.51

4500

45.7

28.7

18.1

11.4

7.15

4.5

2.82

5000

50.1

32

20.1

12.6

7.94

5

3.14

5500

55.8

35.1

22.1

13.91

8.73

5.5

3.46

6000

61

38.3

24.1

15.2

9.53

6

3.77

6500

66

41.5

26.1

16.4

10.3

6.5

4.08

7000

71.1

44.7

28.1

17.7

11.1

7

4.4

7500

76.1

47.9

30.1

19

12

7.49

4.71

8000

81.2

51.1

23.1

20.2

12.7

7.99

5.03

9000

91.4

57.5

36.1

22.7

14.3

8.99

5.65

10 000

102

63.9

40.2

25.3

15.9

9.99

6.28

NOTE: RESISTANCE SHOWN IS ONE WAY. THIS FIGURE SHOULD BE DOUBLED

WHEN DETERMINING CLOSED LOOP RESISTANCE.

-37-

Image 43
Contents Ultraviolet Fire Detection System Page Page Page Table of Contents Unit V Maintenance Unit I General Information Detector Specifications Dimensions Basic Operation Controller Controller Faceplate Description Relay Outputs OutputsCurrent Outputs Automatic Diagnostics and Fault Identification External ResetProgramming Options Petroleum Products Handling Unit II UV Fire DetectionDetector System ApplicationGaseous Fuel Handling Detector Sensitivity Spectral Sensitivity RangeOther Processes System Sensitivity Cone of VisionInstallation General Wiring Requirements Unit III System InstallationController Wiring Page W iring for U1F-UV with Non-Isolated Current Output W iring for U1F-UV with Isolated Current Output W iring for U2F-UV with Non-Isolated Output W iring Diagram for U2F-UV with Isolated Current Output W iring for U4F-UV with Non-Isolated Current Output W iring for U4F-UV with Isolated Current Output Position and Density of Detectors DIP Switch SettingsMounting the Detector U2F and U4F Controller Sensitivity AdjustmentChannel Selection U1F, U2F and U4FRelay Outputs ENERGIZED/DE-ENERGIZED Relay Outputs LATCHING/NON-LATCHINGExample Page Relay Settings Time Delay for Area AlarmsCheckout Procedure Startup ProcedureUnit IV System Operation Manual Check Procedure Normal Operation Fire Response Alternate Test ProcedureCurrent Output Situation Main Menu Special Function Menu Error Check Mode Err ChcCurrent Calibration Mode CuC Device Repair and Return Unit V MaintenanceRoutine Maintenance TroubleshootingPage Appendices B lis h ed in Accordance with E1A Standard Appendix B Procedure For Activating Reed Switches Appendix C Record Of Dip Switch Settings Appendix D Common Ultra-Violet Absorbing Gases AWG #20 AWG #18 AWG #16 AWG #14 AWG #12 AWG #10 AWG #8 Appendix E Wire Resistance In Ohms

0016-00, UVC120, MAN -0016-00 specifications

The Emerson MAN-0016-00, UVC120, 0016-00 is a state-of-the-art device designed to meet the demands of modern industrial and commercial applications. This advanced model showcases Emerson’s commitment to innovation, providing users with reliable performance and cutting-edge technology.

One of the key features of the Emerson MAN-0016-00 is its superior control capabilities. Equipped with sophisticated algorithms, this device ensures precise and adaptable control over various processes, improving efficiency and productivity in operations. Users benefit from enhanced responsiveness to changing conditions, allowing for quick adjustments that lead to optimized performance.

Another noteworthy technology integrated into the UVC120 is its advanced user interface. The device boasts a highly intuitive control panel that facilitates easy navigation and management of settings. This user-friendly design minimizes the learning curve for operators, ensuring that they can quickly familiarize themselves with its functions. The display provides clear, real-time feedback, enabling users to monitor system performance effortlessly.

The Emerson MAN-0016-00 is also characterized by its robust construction. Designed to endure harsh environmental conditions, this model is built with durable materials that enhance its longevity and reliability. It is resistant to various industrial contaminants, ensuring consistent operation even in challenging settings.

Energy efficiency is a hallmark of the UVC120 model. By employing innovative power management technologies, it significantly reduces energy consumption without compromising performance. This emphasis on sustainability not only lowers operational costs for users but also aligns with global efforts to minimize environmental impact.

Moreover, the Emerson MAN-0016-00 incorporates advanced safety features that prioritize user protection. These include integrated alarms and emergency shut-off mechanisms that respond to detected anomalies, enhancing overall workplace safety. The design also adheres to international safety standards, ensuring compliance and peace of mind for users.

In conclusion, the Emerson MAN-0016-00, UVC120, 0016-00 stands out as an exemplary model in the field of industrial technology. Its combination of precision control, user-friendly interface, robust construction, energy efficiency, and safety features make it an ideal choice for various applications. As industries continue to evolve, devices like this play a crucial role in enhancing performance, safety, and sustainability across the board.