Instruction Manual
7.0 ALARM CONFIGURATION
Model 20X or 200X Configured w ith Alarm Relay Output
Configuration Jum pers
Buzzer Active | Relay | Operation |
|
| ||
Y es | No | Normally |
| Normally | ||
Not Energized |
| Energized | ||||
|
|
| ||||
Default |
| Default |
|
| ||
Install Jumper | Remove Jumper | Install Jumper |
| Install Jumper | ||
JP6 | JP6 | JP2 pins |
| JP2 pins | ||
| (Best for 20X) |
|
|
|
|
|
|
|
|
|
|
| |
|
| W iring Terminations |
| |||
Power Supply |
|
| Output Terminals |
| ||
|
| |||||
+ DCV | 0 DC | NC |
| Common |
| NO |
Common |
|
|
|
|
| |
Model 20X or 200X Configured for Interface to Model 2102 Alarm Panel | ||||||
|
| Configuration Jum pers |
| |||
Buzzer Active | Relay | Operation |
| Interface Selection | ||
Yes | No | Normally |
| Normally |
| Model 2102 |
Not Energized |
| Energized |
| |||
|
|
|
|
| ||
Default |
| Default |
|
|
|
|
Install Jumper | Remove Jumper | N/A |
| N/A |
| Install Jumpers |
JP6 | JP6 |
|
|
|
| JP3 pins |
| (Best for 20X) |
|
|
|
| JP2 pins |
|
|
|
|
|
| |
|
| W iring Terminations |
| |||
Power Supply |
|
| Output Terminals |
| ||
|
| |||||
+ DCV | 0 DC | Safe |
| Alarm |
|
|
To Model 2102 | To Model 2102 | To Model 2102 |
| To Model 2102 |
| Not Used |
Terminal J5 | Terminal J5 | Terminal J5 |
| Terminal J5 |
| |
or | or | or |
|
|
| |
|
|
|
|
|
|
|
Table 6.2
Jumper Configuration and W iring Terminations
Relay Operation
Normally Not Energized
| |||
No Power | Connected | Open | |
Sensor Fail |
| Oscillating |
|
Safe | Connected | Open | |
Alarm | Open | Connected | |
| Normally Energized - Fail Safe |
| |
| |||
No Power | Connected | Open | |
Sensor Fail |
| Oscillating |
|
Safe | Open | Connected | |
Alarm | Connected | Open |
Table 6.3
Relay Operating States