Munchkin MUNCHKIN HIGH EFFICIENCY HEATER with the "925" Controller manual Part 3. GAS Connection

Page 12

GAS CONNECTION

PART 3. GAS CONNECTION

WARNING

Failure to follow all precautions could result in fire, explosion or death!

A. GAS CONNECTION

The gas supply shall have a maximum inlet pressure of less than 14" water column (350 mm), ½ pound pressure (3.5 kPa), and a minimum of 3.5" water column. The entire piping system, gas meter and regulator must be sized properly to prevent pressure drop greater than 0.5" as stated in the National Fuel Gas Code. This information is listed on the rating plate. It is very important that you are connected to the type of gas as noted on the rating plate. "LP" for liquefied petroleum, propane gas or, "Nat"

natural or city gas. All gas connections must be approved by the local gas supplier, or utility in addition to the governing authority, prior to turning the gas supply on. The nipple provided is ½" and it is mandatory that a ¾" to ½" reducing coupling (provided) is used, threaded into the branch of a ¾" tee, and a drip leg fabricated, as per the National Fuel Gas code. You must ensure that the entire gas line to the connection at the Munchkin is no smaller than ¾". Once all the inspections have been performed, the piping must be leak tested. If the leak test requirement is a higher test pressure than the maximum inlet pressure, you must isolate the Munchkin from the gas line. In order to do this, you must shut the gas off using factory and field-installed gas cocks (following the lighting instructions in Part 6 Section B.) This will prevent high pressure. Failure to do so may damage the gas valve. In the event the gas valve is exposed to a pressure greater than ½ PSI, 14" water column, the gas valve must be replaced. Never use an open flame (match, lighter, etc.) to check gas connections.

B.GAS PIPING

1.Run the gas supply line in accordance with all applicable codes.

2.Locate and install manual shutoff valves in accordance with state and local requirements.

C.GAS TABLE

Refer to Table (1) to size the supply piping to minimize pressure drop between meter or regulator and unit.

Maximum Capacity of Pipe in Cubic Feet of Gas per Hour for Gas Pressures of 0.5 psi or Less and a Pressure Drop of 0.3 Inch water Column

(TABLE 1)

 

 

 

(Based on a 0.60 Specific Gravity Gas)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Iron Pipe

Internal

 

 

 

 

Length of Pipe (Feet)

 

 

 

 

 

 

 

 

 

Size

Diameter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(inches)

(inches) 10

20

30

40

50

60

70

80

90

100

125

150

175

200.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3/4

.824

278

190

152

130

115

105

96

90

84

79

72

64

59

55}

BTU'S

1

1.049

520

350

285

245

215

195

180

170

160

150

130

120

110

100}

PER

1 1/4

1.380

1,050

730

590

500

440

400

370

350

320

305

275

250

225

210}

HOUR

1 1/2

1.610

1,600

1,100

890

760

670

610

560

530

490

460

410

380

350

320}

X 1,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

Image 12
Contents Munchkin High Efficiency Heater With the 925 ControllerUsing this Manual Special Attention BoxesTable of Contents Munchkin Ratings and Dimensions Part 1. General InformationHOW IT Operates Recommended Service Clearances Dimensions 80M 140M/199M PRE-INSTALLATION Requirement GeneralPart 2. Electrical Pressure Relief ValveElectrical Connection Electrical Connection Wiring Directly to Central Heating Circulator Part 3. GAS Connection GAS ConnectionGAS Piping GAS TableDungs GAS Valve Part 4. Venting Approved Venting MaterialsVenting the Munchkin Direct vent terminal clearance Minimum clearance, C Longer Vent Runs Vented ApplianceHeater Removal from a Common Vent System Condensate RemovalDiagrams for Sidewall Venting Venting Diagrams for Vertical Venting Part 5. Piping Hydronic Piping with Circulators or Zone ValvesCirculator Sizing Munchkin T50M Munchkin T80M/80M Munchkin 140M Munchkin 199MFill and Purge Heating System Piping Symbol Legend Piping IllustrationsOFF Zone valves Piping Zone valves Make-up water Piping Space heating zone circuit Zone Circulators Make-up water PB1 PB2 PB1 PB2 Part 6. START-UP Procedures Sequence of OperationItems to be Checked Before Lighting the Munchkin Lighting Instructions Operating InstructionsAdjusting the Temperature on the Munchkin Display Status MenuTest Mode To Turn OFF GAS to AppliancePart 7. Troubleshooting Munchkin Error Code925 Control Board Error Codes Resistance Tables Part 8. Maintenance Maintenance ProceduresCondensate Cleaning Instructions Before Each Heating SeasonMaintenance Control Wiring Layout Munchkin ControllerMaintenance Maintenance Page Page Munchkin R1

MUNCHKIN HIGH EFFICIENCY HEATER with the "925" Controller specifications

The Munchkin High Efficiency Heater, equipped with the advanced "925" Controller, represents a significant advancement in heating technology for both residential and commercial applications. Known for its reliability and exceptional performance, this heater is designed to provide efficient heating while minimizing energy costs and environmental impact.

The Munchkin High Efficiency Heater operates on a condensing technology that extracts heat from exhaust gases. This process allows for higher efficiency rates, often exceeding 95%. By recovering heat that would otherwise be lost, the heater maximizes energy utilization, making it an eco-friendly choice for homeowners and businesses alike.

One of the standout features of the Munchkin 925 Controller is its user-friendly interface, which allows for effortless operation and monitoring of the heating system. The controller comes with advanced diagnostic capabilities that provide real-time feedback on system performance. Users can easily adjust settings, program schedules, and monitor energy consumption, ensuring optimal comfort and efficiency.

Furthermore, the Munchkin High Efficiency Heater is equipped with a variety of features that enhance its performance and user experience. The unit is designed with a durable heat exchanger made from stainless steel, which not only improves heat transfer but also ensures longevity and resistance to corrosion.

The heater operates quietly, making it suitable for installation in residential settings, including bedrooms and living spaces. Additionally, its compact design allows for flexible installation options, even in constrained spaces. The Munchkin unit is also compatible with multiple venting options, providing further versatility in installation configuration.

Safety features are a priority in the design of the Munchkin Heater. It includes built-in freeze protection, ensuring that the system operates effectively even in low temperatures. The unit also has an array of safety sensors that monitor for conditions such as flue blockage and overheating, triggering automatic shut-off mechanisms to prevent potential hazards.

In conclusion, the Munchkin High Efficiency Heater with the "925" Controller is a cutting-edge solution for efficient heating. With its superior performance, advanced controller system, durable construction, and comprehensive safety features, it remains a top choice for those looking to improve their heating efficiency while reducing energy consumption. Whether it's for residential or commercial use, the Munchkin heater promises reliability and comfort in any environment.