Munchkin Gas-Fired Hot Water Circulating Heater installation manual Fill and Purge Heating System

Page 17

GAS-FIRED HEATER Installation Manual

PART 5: MUNCHKIN CONTENDER PIPING (CONTINUED)

The chart below represents the various system temperatures and their respective flows and friction loss through the Munchkin Contender which will aid circulator selection.

SYSTEM TEMPERATURE RISE CHART

 

20˚ǻt

25˚ǻt

 

30˚ǻt

 

35˚ǻt

 

40˚ǻt

 

45˚ǻt

 

 

Friction

Flow

Friction

 

Flow

Friction

 

Flow

Friction

 

Flow

Friction

 

Flow

Friction

 

Flow

Model

Feet

GPM

Feet

 

GPM

Feet

 

GPM

Feet

 

GPM

Feet

 

GPM

Feet

 

GPM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MC-50

6.5'

5

4.5'

 

4

3'

 

3.3

2'

 

2.5

N/R

 

N/R

N/R

 

N/R

MC-80

7.8'

8

4.7'

 

6.4

2.9'

 

5.3

2'

 

4.6

1.5'

 

4

1'

 

3.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MC-99

9'

10

6'

 

9

5'

 

7.8

4'

 

6.3

3.5'

 

5.6

2'

 

4.8

MC-120

10'

12

7'

 

9.6

5'

 

8

4'

 

6.8

3.5'

 

6

2'

 

5.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N/R = Not recommended

I.FILL AND PURGE HEATING SYSTEM

Attach the hose to balance and purge hose connector or drain valve and run hose to nearest drain

Close the other side of the balance and purge valve or the shut off valve after the drain.

Open first zone balance and purge or drain valve to let water flow out the hose. If zone valves are used, open the valves one at a time manually. (Note: You should check valve manufacturer’s instruction prior to opening valves manually, so as not to damage the valve.)

Manually operate fill valve regulator. When water runs out of the hose, while it’s connected to the balance and purge valve or drain you will see a steady stream of water (without bubbles). Close balance and purge valve or drain to stop the water from flowing. Disconnect the hose and connect it to next zone to be purged.

Repeat this procedure for additional zones (one at time).

CAUTION

For installation that incorporates standing Iron Radiation and systems with manual vents at the high points. Follow above section and starting with the nearest manual air vent, open vent until water flows out, then close vent. Repeat procedure, working your way toward furthest air vent. It may be necessary to install a basket strainer in an older system where larger amounts of sediment may be present. Annual cleaning of the strainer may be necessary.

Upon completion, make sure that the fill valve is in automatic position and each zone balance and purge or shut off is in an open position and zone valves are positioned for automatic opera- tion.

WARNING

Use only inhibited propylene glycol solutions which are specially formulated for hydronic systems. Ethylene glycol is toxic and can attack gaskets and seals used in hydronic systems. Glycol mixtures should not exceed 50%.

1.Glycol in hydronic applications which is specially formulated for this purpose includes inhibitors that prevent the glycol from attacking metallic system components. Make certain that the system fluid is checked for the correct glycol concentration and inhibitor level.

2.The glycol solution should be tested at least once a year and as recommended by the glycol manufacturer.

3.Anti-freeze solutions expand more than water. For example a 50% by volume solution expands 4.8% in volume for a temperature increase from 32° F to 180° F, while water expands 3% with the same temperature rise. Allowances must be made for this expansion in the system design.

4.A 30% mixture of glycol will result in a BTU output loss of 15% with a 5% increase in head against system circulator.

5.A 50% mixture of glycol will result in a BTU output loss of 30% with a 50% increase in head against system circulator.

16

Image 17
Contents Installation Manual What to do if YOU Smell GAS Contents Contents CONT’D Definitions Part 1 Product and Safety InformationHeater Water Munchkin Contender OperationFreeze Protection Fluids Winterizing the Munchkin ContenderModulating Combustion System Gas ValveReturn water temperature sensor Supply water temperature sensorTemperature and pressure gauge Swirl Plate SystemPart 2 HOW the Munchkin Contender Operates CONT’D Installations Must Comply withBefore Locating the Munchkin Contender Clearances for Service AccessPrevent Combustion AIR Contamination Residential Garage InstallationExhaust Vent and Intake AIR Vent Part 4 Prepare Munchkin Contender Heater Munchkin Contender Wall Mounting Instructions Installation StepsPart 5 Munchkin Contender Piping Circulators Part 5 Munchkin Contender PipingCirculator Sizing Fill and Purge Heating System System Temperature Rise ChartZoning with Zone Valves Munchkin Contender PipingZoning with Circulators Multiple HeatersContender Piping Details Piping symbol legendDrawing 1A Standard Munchkin Contender! Heater zoning with valvesDrawing 1B Standard Munchkin Contender Heater zoning with valvesSpace heating zone circuit See note Make-up water Installation Manual GAS-FIRED Heater Installation Manual Space heating zone circuit Vision I System Piping Zoning with Circulators Using VisionHeater Piping Details with the Vision I System Drawing 2ADrawing 2B OFF Drawing 2CDrawing 3A Drawing 3B Drawing 3C Outdoor Temperature sensor Vision 1 system purgeDrawing 3D Drawing 3E Drawing 3F Drawing 3G General Installing Exhaust Vent and Intake AIR VentExhaust Vent and Intake AIR Vent Pipe Location Exhaust Vent and Intake AIR Vent Sizing Part 7 VENTING, Combustion AIR & Condensate RemovalInstallation Manual Reference National Fuel Gas Code Ansi Z223.1/NFPA 54 Exhaust Vent and Intake AIR Pipe InstallationVent Termination Kits Description Stock Code Heater Removal from a Common Vent SystemCanada Condensate Removal SystemMaterial Sidewall Venting with KIT Diagrams for Sidewall Venting12 2 roof vent with tee intake & coupling exhaust GAS Connection Part 8 GAS PipingGAS Piping GAS TableTAP Inlet Dungs GAS ValveField Wiring Installation Must Comply withLine Voltage Wiring ThermostatPart 9 Field Wiring Part 9 Field Wiring Indirect Circulator P2 Program Part 10 Field Wiring Vision 1 OptionPart 11. START-UP Preparation Freeze Protection When UsedCHECK/CONTROL Water Chemistry Fill and Test Water SystemCheck Thermostat Circuits Check for GAS LeaksPurge AIR from Water System Condensate Removal Part 12. START-UP ProcedureAdjusting the Setpoint Part 12. START-UP ProcedureOperating Instructions Status MenuProgramming the Vision I Option Test ModeVision 1 Program Access Vision 1 Program Navigation Central Heating Curve Function Default Function Function Value DescriptionFunction Function Default Setting Programmed Setting Control Program Reference ChartHeater Fault Munchkin Error CodeHeater Error 925 Control Board Fault Codes Description Remedy Part 14 TroubleshootingOutdoor Sensor 7250P-319 Maintenance ProceduresSure Exhaust Vent is no Longer Blocked For GAS LeaksReplacement Parts Part 15 MaintenanceReplacement Parts Replacement Parts Light Off Activities Heater Start UP ReportHeater Inspection and Maintenance Schedule Heater Inspection and Maintenance Schedule Maintenance Notes Maintenance Notes 2007, 2006 Heat Transfer Products, Inc LP-171 REV /20/07

Gas-Fired Hot Water Circulating Heater specifications

The Munchkin Gas-Fired Hot Water Circulating Heater is a cutting-edge heating solution designed to provide efficient and reliable hot water for residential and commercial applications. Renowned for its compact design and innovative technology, the Munchkin heater combines performance with energy efficiency, making it an ideal choice for those seeking comfort and cost savings.

One of the main features of the Munchkin heater is its modulating burner. This technology intelligently adjusts the heating output based on the demand for hot water, ensuring that energy is not wasted. This leads to lower energy bills and a reduction in environmental impact, as the system only uses the necessary resources to maintain desired water temperatures.

Another notable characteristic is its high-efficiency rating. The Munchkin heater operates with an impressive annual fuel utilization efficiency (AFUE) of up to 95%. This means that the majority of the fuel consumed is converted into usable heat. By maximizing energy utilization, homeowners can enjoy a significant reduction in utility costs while minimizing emissions.

The compact size of the Munchkin Gas-Fired Hot Water Circulating Heater is another significant advantage. It is designed to fit into tight spaces, making it suitable for homes where space is at a premium. This compact design does not compromise performance; instead, it enhances installation flexibility, allowing for placement in basements, closets, or utility rooms.

Munchkin heaters are equipped with advanced control systems that offer enhanced convenience. The digital display and programmable settings allow users to set their preferred temperatures and schedules. This feature not only enhances user comfort but also optimizes energy usage, as water is heated only when necessary.

Safety is also a top priority with Munchkin products. The heater includes built-in safety features such as flame monitoring systems, automatic shut-off capabilities, and pressure relief valves, providing peace of mind for users.

In summary, the Munchkin Gas-Fired Hot Water Circulating Heater is a high-efficiency, compact, and innovative solution for hot water needs. With its modulating burner, high-efficiency rating, advanced control systems, and safety features, it stands out as a reliable choice for those looking to invest in heating technology that prioritizes energy conservation and performance. This heater is truly a forward-thinking solution for modern hot water requirements.