Munchkin Gas-Fired Hot Water Circulating Heater Part 8 GAS Piping, GAS Connection, GAS Table

Page 46
Fig. 8-1

GAS-FIRED HEATER Installation Manual

PART 8: GAS PIPING

WARNING

Failure to follow all precautions could result in fire, explosion or death!

A. GAS CONNECTION

The gas sup- ply shall have

am a x i m u m inlet pressure of less than 14" water column

(350 mm), ½ pound pres- sure (3.5 kPa), and a mini - mum of 3.5" water column. The entire pip-

ing system, gas meter and regulator must be sized properly to prevent pressure drop greater than 0.5" as stated in the National Fuel Gas Code. This information is listed on the rating plate. It is very important that you are connect- ed to the type of gas as noted on the rating plate. "LP" for liquefied petroleum, propane gas or, "Nat" natural or city gas. All gas connections must be approved by the local gas supplier, or utility in addition to the governing authority, prior to turning the gas supply on. The nipple provided is ½" with a factory installed. Do not remove this ¾" x ½" bell reducer! It is mandato- ry that this fitting is used for connection to a field fabricated drip leg as shown in the illustration above per the National Fuel Gas Code. You must ensure that the entire gas line to the connection at the Munchkin Contender is no smaller than ¾". Once all the inspections have been per- formed, the piping must be leak tested. If the leak test requirement is a higher test pressure than the maximum inlet pressure, you must iso- late the Munchkin Contender from the gas line. In order to do this, you must shut the gas off using factory and field-installed gas cocks. This will prevent high pressure. Failure to do so may damage the gas valve. In the event the gas valve is exposed to a pressure greater than ½ PSI, 14" water column, the gas valve must be replaced. Never use an open flame (match, lighter, etc.) to check gas connections.

B.GAS PIPING

1.Run the gas supply line in accordance with all applicable codes.

2.Locate and install manual shutoff valves in

a c c o r d a n c e w i t h s t a t e a n d l o c a l requirements.

C. GAS TABLE

Refer to Table 8.2 to size the supply piping to minimize pressure drop between meter or regulator and unit.

Maximum Capacity of Pipe in Cubic Feet of Gas per Hour for Gas Pressures of 0.5 psi or Less and a Pressure Drop of 0.3 Inch water Column

(TABLE 8-2) (Based on a 0.60 Specific Gravity Gas)

 

Nominal

 

 

 

 

 

 

 

 

 

 

 

 

Iron Pipe

Internal

 

 

 

Length of Pipe (Feet)

 

 

 

 

Size

Diameter

 

 

 

 

 

 

 

 

 

 

 

(inches)

(inches)

10

20

30

40

50

60

70

 

 

 

3/4

.824

278

190

152

130

115

105

96

 

BTU'S

 

1

1.049

520

350

285

245

215

195

180

 

PER

 

1 1/4

1.380

1,050

730

590

500

440

400

370

 

HOUR

 

1 1/2

1.610

1,600

1,100

890

760

670

610

560

}x1,000

 

 

 

 

80

90

100

125

150

175

200

 

 

 

3/4

.824

90

84

79

72

64

59

55

 

BTU'S

 

1

1.049

170

160

150

130

120

110

100

 

PER

 

1 1/4

1.380

350

320

305

275

250

225

210

 

HOUR

 

1 1/2

1.610

530

490

460

410

380

350

320

}x1,000

It is recommended that a soapy solution be used to detect leaks. Bubbles will appear on the pipe to indicate a leak is present. The gas piping must be sized for the proper flow and length of pipe, to avoid pressure drop. Both the gas meter and the gas regulator must be properly sized for the total gas load. If you experience a pressure drop greater than 1" WC, the meter, regulator or gas line is undersized or in need of service. You can attach a manometer to the incoming gas drip leg, by removing the cap and installing the manometer. The gas pressure must remain between 3.5" and 14" during stand-by (static) mode and while in operating (dynamic) mode. If an in-line regulator is used, it must be a minimum of 10 feet from the Munchkin

45

Image 46
Contents Installation Manual What to do if YOU Smell GAS Contents Contents CONT’D Part 1 Product and Safety Information DefinitionsMunchkin Contender Operation Heater WaterModulating Combustion System Winterizing the Munchkin ContenderFreeze Protection Fluids Gas ValveTemperature and pressure gauge Supply water temperature sensorReturn water temperature sensor Swirl Plate SystemInstallations Must Comply with Part 2 HOW the Munchkin Contender Operates CONT’DClearances for Service Access Before Locating the Munchkin ContenderExhaust Vent and Intake AIR Vent Residential Garage InstallationPrevent Combustion AIR Contamination Part 4 Prepare Munchkin Contender Heater Installation Steps Munchkin Contender Wall Mounting InstructionsPart 5 Munchkin Contender Piping Part 5 Munchkin Contender Piping CirculatorsCirculator Sizing System Temperature Rise Chart Fill and Purge Heating SystemZoning with Circulators Munchkin Contender PipingZoning with Zone Valves Multiple HeatersPiping symbol legend Contender Piping DetailsStandard Munchkin Contender! Heater zoning with valves Drawing 1AStandard Munchkin Contender Heater zoning with valves Drawing 1BSpace heating zone circuit See note Make-up water Installation Manual GAS-FIRED Heater Installation Manual Space heating zone circuit Zoning with Circulators Using Vision Vision I System PipingDrawing 2A Heater Piping Details with the Vision I SystemDrawing 2B Drawing 2C OFFDrawing 3A Drawing 3B Outdoor Temperature sensor Vision 1 system purge Drawing 3CDrawing 3D Drawing 3E Drawing 3F Drawing 3G Exhaust Vent and Intake AIR Vent Pipe Location Installing Exhaust Vent and Intake AIR VentGeneral Part 7 VENTING, Combustion AIR & Condensate Removal Exhaust Vent and Intake AIR Vent SizingInstallation Manual Reference National Fuel Gas Code Ansi Z223.1/NFPA 54 Installation Exhaust Vent and Intake AIR PipeHeater Removal from a Common Vent System Vent Termination Kits Description Stock CodeMaterial Condensate Removal SystemCanada Diagrams for Sidewall Venting Sidewall Venting with KIT12 2 roof vent with tee intake & coupling exhaust GAS Piping Part 8 GAS PipingGAS Connection GAS TableDungs GAS Valve TAP InletLine Voltage Wiring Installation Must Comply withField Wiring ThermostatPart 9 Field Wiring Part 9 Field Wiring Part 10 Field Wiring Vision 1 Option Indirect Circulator P2 ProgramCHECK/CONTROL Water Chemistry Freeze Protection When UsedPart 11. START-UP Preparation Fill and Test Water SystemPurge AIR from Water System Check for GAS LeaksCheck Thermostat Circuits Part 12. START-UP Procedure Condensate RemovalOperating Instructions Part 12. START-UP ProcedureAdjusting the Setpoint Status MenuVision 1 Program Access Test ModeProgramming the Vision I Option Vision 1 Program Navigation Function Default Function Function Value DescriptionCentral Heating Curve Function Control Program Reference Chart Function Default Setting Programmed SettingHeater Error Munchkin Error CodeHeater Fault Part 14 Troubleshooting 925 Control Board Fault Codes Description RemedyMaintenance Procedures Outdoor Sensor 7250P-319For GAS Leaks Sure Exhaust Vent is no Longer BlockedPart 15 Maintenance Replacement PartsReplacement Parts Replacement Parts Heater Start UP Report Light Off ActivitiesHeater Inspection and Maintenance Schedule Heater Inspection and Maintenance Schedule Maintenance Notes Maintenance Notes 2007, 2006 Heat Transfer Products, Inc LP-171 REV /20/07

Gas-Fired Hot Water Circulating Heater specifications

The Munchkin Gas-Fired Hot Water Circulating Heater is a cutting-edge heating solution designed to provide efficient and reliable hot water for residential and commercial applications. Renowned for its compact design and innovative technology, the Munchkin heater combines performance with energy efficiency, making it an ideal choice for those seeking comfort and cost savings.

One of the main features of the Munchkin heater is its modulating burner. This technology intelligently adjusts the heating output based on the demand for hot water, ensuring that energy is not wasted. This leads to lower energy bills and a reduction in environmental impact, as the system only uses the necessary resources to maintain desired water temperatures.

Another notable characteristic is its high-efficiency rating. The Munchkin heater operates with an impressive annual fuel utilization efficiency (AFUE) of up to 95%. This means that the majority of the fuel consumed is converted into usable heat. By maximizing energy utilization, homeowners can enjoy a significant reduction in utility costs while minimizing emissions.

The compact size of the Munchkin Gas-Fired Hot Water Circulating Heater is another significant advantage. It is designed to fit into tight spaces, making it suitable for homes where space is at a premium. This compact design does not compromise performance; instead, it enhances installation flexibility, allowing for placement in basements, closets, or utility rooms.

Munchkin heaters are equipped with advanced control systems that offer enhanced convenience. The digital display and programmable settings allow users to set their preferred temperatures and schedules. This feature not only enhances user comfort but also optimizes energy usage, as water is heated only when necessary.

Safety is also a top priority with Munchkin products. The heater includes built-in safety features such as flame monitoring systems, automatic shut-off capabilities, and pressure relief valves, providing peace of mind for users.

In summary, the Munchkin Gas-Fired Hot Water Circulating Heater is a high-efficiency, compact, and innovative solution for hot water needs. With its modulating burner, high-efficiency rating, advanced control systems, and safety features, it stands out as a reliable choice for those looking to invest in heating technology that prioritizes energy conservation and performance. This heater is truly a forward-thinking solution for modern hot water requirements.