Service Manual
3 Troubleshooting
Table
FAULT | CAUSE |
| CORRECTIVE ACTION |
| ||||||||
|
|
|
|
| ||||||||
| - No 120 vac supplied to unit. | • | Check external line switch, fuse, or breaker. |
| ||||||||
| • | Check position of ON/OFF switch. Turn switch to the | ||||||||||
|
| |||||||||||
|
|
| ON position. |
|
|
|
|
|
|
| ||
|
| • Check 120 vac through the ON/OFF switch. |
| |||||||||
|
| • Check wiring | harness connection | between | display | |||||||
|
|
| board | and | main | control | board. | Connect | ||||
No Display |
|
| harness at both points. |
|
|
|
|
| ||||
- No voltage through the switch. | • | Replace switch. |
|
|
|
|
|
| ||||
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
| |||
| - Bad display board. | • | Replace board. |
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| |||||
| - Bad main control board. | • | Replace the main control board. |
|
|
|
| |||||
|
|
|
|
|
|
|
|
| ||||
| - Blown fuse. | • | Replace | fuse | F3 on | the main | control | board, see | ||||
|
| page 33 of this manual. |
|
|
|
|
| |||||
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
| ||||
| - Main control board temperature set point | • | Review temperature setting. |
|
|
|
|
| ||||
| satisfied. |
|
|
|
|
|
|
|
|
|
| |
| - Remote thermostat satisfied. | • | Review remote thermostat setting. |
|
|
| ||||||
|
|
|
|
|
|
|
|
| ||||
No Burner | - Outside air temperature above Warm | • | Check | location of | outside | air | sensor. | Check | ||||
Weather Shutdown (WWSD) set point for |
| resistance of outdoor air sensor and compare to Table | ||||||||||
Operation | main control board. |
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
| ||||
|
| • | Consult | display for | specific | fault. | Refer | to fault | ||||
| - Unit locked out on fault. |
| descriptions on page 37 of this manual for corrective | |||||||||
|
|
| actions. |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
| ||||||
| - Unit in Shutdown Mode. | • Take unit out of Shutdown Mode. |
|
|
|
| ||||||
|
|
|
| |||||||||
|
| • | Check ramp delay parameter settings. Optional PC | |||||||||
| - Ramp delay active. |
| software required. |
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
| ||
| • | Turn ramp delay feature off. | See page 23 of this | |||||||||
|
| |||||||||||
Unit Does |
|
| manual for instructions on how to turn this feature off. | |||||||||
|
|
|
|
|
|
|
|
|
|
| ||
| • Check BMS parameter settings. Optional PC | |||||||||||
Not Modulate | - Boiler controlled by BMS. | |||||||||||
| software required. |
|
|
|
|
|
| |||||
Above 50% |
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
| ||
| • | Verify that the flue sensor is located in the flue outlet. | ||||||||||
|
| |||||||||||
|
|
|
|
| ||||||||
| - Flue sensor open. | • | Check wiring connections at the flue sensor. |
| ||||||||
|
|
|
|
|
|
|
|
|
|
| ||
| • | Check the resistance of the flue sensor and compare | ||||||||||
|
| |||||||||||
|
|
| to Table |
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
34