Service Manual
3 Troubleshooting (continued)
Table
FAULT | DESCRIPTION |
| CORRECTIVE ACTION |
| |||
|
|
| |||||
|
| • Adjust the set point of the auto reset limit to a higher | |||||
|
| setting up to a maximum of 200°F. Reference the | |||||
|
| Knight Installation and Operation Manual for adjusting | |||||
|
| procedures. |
|
|
|
| |
|
| • Verify that the system is full of water and that all air | |||||
|
| has been properly purged from the system. |
| ||||
|
| • Verify that the boiler is piped properly into the heating | |||||
|
| system. Refer to Section 6 - Hydronic Piping of the | |||||
|
| Knight | Boiler | Installation | and | Operation | Manual |
|
| for the proper piping methods for the Knight boiler. | |||||
|
| • Check 120 vac to boiler pump motor on a call for | |||||
|
| heat. If voltage is not present, check wiring back to | |||||
| The outlet water temperature has exceeded | the main control board. |
|
|
| ||
Outlet ARHL | • Replace the main control board if necessary. |
| |||||
the setting of the automatic reset high limit. | • If 120 vac is present on a call for heat and the boiler | ||||||
|
| ||||||
|
| pump is not operating, replace the pump. |
| ||||
|
| • If the system pump is a variable speed pump, ensure | |||||
|
| that the system flow is not less than the boiler flow. | |||||
|
| • If operating on something other than an outlet sensor, | |||||
|
| check temperature setting of the main control board. | |||||
|
| • If the optional manual reset high limit has tripped, | |||||
|
| check setting of the device. |
|
|
| ||
|
| • Check resistance of water sensors and compare to | |||||
|
| Table | |||||
|
| sensor if necessary. |
|
|
| ||
|
| • Replace high limit. |
|
|
| ||
|
|
| |||||
|
| • Adjust the set point of the manual reset limit to a higher | |||||
|
| setting up to a maximum of 210°F. Reference the | |||||
Outlet MRHL |
| Knight Boiler Installation and Operation Manual for | |||||
| adjusting procedures. |
|
|
| |||
(will require a manual |
| • Verify that the system is full of water and that all air | |||||
reset once the condition | The outlet water temperature has exceeded | has been properly purged from the system. |
| ||||
has been corrected. | • Verify that the boiler is piped properly into the heating | ||||||
Press the RESET | the setting of the manual reset high limit. | system. | Refer to Section 6 - Hydronic Piping of the | ||||
button on the SMART |
| ||||||
SYSTEM display to |
| Knight | Boiler | Installation | and | Operation | Manual |
| for the proper piping methods for the Knight boiler. | ||||||
reset.) |
| ||||||
|
|
|
|
|
|
| |
|
| • Check 120 vac to boiler pump motor on a call for | |||||
|
| heat. If voltage is not present, check wiring back to | |||||
|
| the main control board. |
|
|
| ||
|
|
|
|
|
|
|
|
40