2 Maintenance

Maintenance and annual startup

Table 2-1Service and Maintenance Schedules

Service technician

(see the following pages for instructions)

 

General:

 

 

 

 

 

 

• Address reported problems

 

 

• Inspect interior; clean and vacuum if

 

necessary;

 

 

 

 

 

• Clean condensate trap and fill with fresh

 

water

 

 

 

 

 

 

• Check

for

leaks

(water, gas,

flue,

 

condensate)

 

 

 

UP

• Verify flue and air lines in good condition

and sealed tight

 

 

 

-

 

 

 

 

 

 

START

• Check

system water

pressure/system

 

 

piping/expansion tank

 

 

ANNUAL

• Check control settings

 

 

and reposition)

 

 

 

 

• Check ignition and flame sense

 

 

electrodes (sand off any deposits; clean

 

• Check wiring and connections

 

 

• Perform

start-up

checkout

and

 

performance verification per Section 10

 

in the Knight Installation and Operation

 

Manual.

 

 

 

 

 

• Flame inspection (stable, uniform)

 

 

• Flame signal (at least 10 microamps at

 

high fire)

 

 

 

 

 

• Clean

the

heat

exchanger if

flue

 

temperature is more than 54°F above

 

return water temperature.

 

If combustion or performance indicate need:

Clean heat exchanger

Remove and clean burner using compressed air only

Clean the blower wheel

Owner maintenance

(see the Knight User’s Information Manual for

instructions)

• Check boiler area

Daily

Check pressure/temperature gauge

Check vent piping

Check air piping

Monthly

Check air and vent termination screens

Check relief valve

Check condensate drain system

Check air vents

Periodically

• Test low water cutoff (if used)

 

• Reset button (low water cutoff)

 

 

 

• Check boiler piping (gas and

Every

water) for leaks

 

6 months

• Operate relief valve

 

 

 

• Shut boiler down (unless boiler

End

used for domestic hot water)

 

of season

 

months

 

28

Image 28 Contents
Models 81 Contents Handling ceramic fiber materials Please read before proceedingNiosh stated First Aid When servicing boiler What is in this manual? ServiceMaintenance TroubleshootingService Near boiler pipingKnight boiler display Navigation DialControl inputs LOW Voltage Connection BoardSmart Control Module Control outputsAccess modes General OperationHow the boiler operates How the control module operatesOperation Display From previous page Sequence of Operation Display panel menu access Button Screen Operation Display StatusDisplay panel parameter access Button Screen Status Operation DisplayParameter table Description See User Access Installer Access Display ModifyMenu DHW Settings Resetoutdoor See User Access Installer Access Display Modify DescriptionBMS Service Notification Temperature units C / F Viewable and changeable control parametersTime and Date Software VersionData Logging Temperature SettingsFunctions DHW Settings Outdoor Reset Anti-Cycling Ramp Settings Control modesControlling Sensor BMS Thermostat InputCascade Offset Minimum On/Off TimeCirculation pumps Service Notification Service technician Maintenance Maintenance and annual startupInstructions Maintenance Flue vent system and air piping Check water systemCheck expansion tank Check boiler relief valveCheck ignition ground wiring Check all boiler wiringCheck control settings Check flame signalCleaning boiler heat exchanger Review with ownerOiled bearing circulators Kit Part Component Number DescriptionTroubleshooting Before troubleshootingCheck control module fuses Check the followingNo Display No BurnerOperation Unit DoesTemperature Resistance Temperature Resistance Checking temperature sensorsResistance Temperature Noisy No PumpBoiler Pump System Pump DHW PumpTroubleshooting Temp Sw OpenApplies to the 286 Model Only Anti-cyclingCont’d Flame SequenceOutlet Arhl Outlet MrhlFan Low/High Fan Speed LowHigh GV/RelayFault Sensor ShortedLouver Proving Inlet SensorFlue Sensor Fault Fatal ErrorMemory Error Flue Temp DiffDelta T High Flue Temp HighOutlet Temp Rem Ctrl Flt Service BlkParameters Progr Combustion Analysis Procedure Gas valve adjustment procedure Gas Valve AdjustmentOr Obstruction Gas Supply Pressure