Lochinvar 81-286 service manual Combustion Analysis Procedure

Page 46

Service Manual

3 Troubleshooting

Table 3-4(continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

 

 

 

 

 

• Check 120 vac supply to the transformer.

 

120 vac input to the main control board has

• Check wiring connections at the low voltage

Low 24 vac

terminal strip.

dropped below 80 vac.

 

 

• Check the wire size/length to remote devices.

 

 

 

 

• Replace the transformer.

 

 

 

Watch Dog Error

The main control board has detected an

• Replace the main control board.

 

internal fault.

 

Write EEProm

The main control board has detected an

• Replace the main control board.

internal fault.

 

CRC Parameters

The main control board has detected an

• Replace the main control board.

 

internal fault.

 

No Error Stored

The main control board has detected an

• Replace the main control board.

 

internal fault.

 

Combustion Analysis Procedure

1.Turn the main power off to the boiler by placing the “On/Off” switch in the OFF position.

2.Remove the flue temperature sensor from the flue pipe connection. Note: Combustion measurements will be made at this point.

3.Turn the main power on to the boiler by placing the “On/Off” switch in the ON position.

4.Place the boiler into the active position by pressing the RIGHT SELECT [ON] key (see page 7).

5.Locate the pinhole button below the RESET button on the display board (see page 7). Insert a thin wire (such as a paper clip) into the hole and press the button once and hold for 5 seconds to place the boiler into Service Mode. In Service Mode the boiler will fire at ignition speed and will then modulate up to full fire.

6.Insert the probe from a combustion analyzer into the hole left by the removal of the flue temperature sensor.

7.Once the boiler has modulated up to full fire, measure the combustion. The values should be in the range listed in Table 3-5 above. The CO levels should be less than 150 ppm for a properly installed unit.

If the combustion is not within the specified range, reference the chart below for possible causes and corrective actions.

Table 3-5Flue Products

Natural Gas

Propane

 

 

 

 

CO2

O2

CO2

O2

8.0% - 10%

3.0% - 6.5%

9.0% - 11%

4.1% - 6.9%

 

 

 

 

8.Once the combustion analysis is complete, test the safety shutoff device by turning the manual shutoff switch to the OFF position and ensuring that the boiler shuts down and registers an alarm. Turn the manual shutoff switch to the ON position, reset the control, and return to Service Mode.

9.Turn the main power off to the boiler and replace the flue temperature sensor into the flue pipe connection.

10.Place the boiler back into normal operation.

￿WARNING You must replace the flue gas temperature sensor to prevent flue gas spillage into

the room. Failure to comply could result in severe personal injury, death, or substantial property damage.

46

Image 46 Contents
Models 81 Contents Handling ceramic fiber materials Please read before proceedingNiosh stated First Aid When servicing boiler Maintenance What is in this manual?Service TroubleshootingService Near boiler pipingKnight boiler display Navigation DialControl inputs LOW Voltage Connection BoardSmart Control Module Control outputsHow the boiler operates Access modesGeneral Operation How the control module operatesOperation Display From previous page Sequence of Operation Display panel menu access Button Screen Operation Display StatusDisplay panel parameter access Button Screen Status Operation DisplayParameter table Description See User Access Installer Access Display ModifyMenu DHW Settings Resetoutdoor See User Access Installer Access Display Modify DescriptionBMS Service Notification Time and Date Temperature units C / FViewable and changeable control parameters Software VersionData Logging Temperature SettingsFunctions DHW Settings Outdoor Reset Anti-Cycling Controlling Sensor Ramp SettingsControl modes BMS Thermostat InputCascade Offset Minimum On/Off TimeCirculation pumps Service Notification Service technician Maintenance Maintenance and annual startupInstructions Maintenance Check expansion tank Flue vent system and air pipingCheck water system Check boiler relief valveCheck control settings Check ignition ground wiringCheck all boiler wiring Check flame signalOiled bearing circulators Cleaning boiler heat exchangerReview with owner Kit Part Component Number DescriptionCheck control module fuses TroubleshootingBefore troubleshooting Check the followingOperation No DisplayNo Burner Unit DoesTemperature Resistance Temperature Resistance Checking temperature sensorsResistance Temperature Boiler Pump System Pump NoisyNo Pump DHW PumpTroubleshooting Applies to the 286 Model Only Temp SwOpen Anti-cyclingCont’d Flame SequenceOutlet Arhl Outlet MrhlHigh Fan Low/HighFan Speed Low GV/RelayLouver Proving FaultSensor Shorted Inlet SensorMemory Error Flue Sensor FaultFatal Error Flue Temp DiffDelta T High Flue Temp HighOutlet Temp Rem Ctrl Flt Service BlkParameters Progr Combustion Analysis Procedure Or Obstruction Gas valve adjustment procedureGas Valve Adjustment Gas Supply Pressure