Service Manual
3 Troubleshooting (continued)
Table
FAULT | DESCRIPTION |
| CORRECTIVE ACTION |
| |
|
|
| |||
|
| • Verify that the boiler pump is set to the proper speed | |||
Outlet Temp |
| or that the boiler pump is the proper size. Reference | |||
| Section | 6 - Hydronic Piping of the Knight | Boiler | ||
High | Outlet water temperature has exceeded the | Installation and Operation Manual for boiler pump | |||
(continued) | maximum outlet water temperature. | specifications. |
|
| |
|
| • Replace the main control board. |
|
| |
|
|
|
|
| |
|
| • Check set point of the external control. |
|
| |
|
| • Check the wiring between the external control and the | |||
Rem Ctrl Flt | External control is cycling too often. | unit. |
|
|
|
|
|
|
|
| |
|
| • Replace the control. |
|
| |
|
|
|
|
|
|
Parameters |
|
|
|
|
|
Progr |
|
|
|
|
|
(will require a manual |
|
|
|
|
|
reset once the condition | After downloading parameters from a laptop, | • Press the ENTER/RESET button on the SMART | |||
has been corrected. Press | the main control board must be reset. | SYSTEM display panel. |
|
| |
the RESET button on the |
|
|
|
| |
SMART SYSTEM display |
|
|
|
|
|
to reset.) |
|
|
|
|
|
|
|
| |||
| While the unit is in Service Mode, the outlet | • Establish a heating load to remove the heat from the | |||
| temperature has exceeded 185°F. | boiler loop. |
|
| |
|
| • Verify that the system is full of water and that all air | |||
|
| has been properly purged from the system. |
| ||
|
| • Verify that the boiler is piped properly into the heating | |||
|
| system. Refer to Section 6 - Hydronic Piping of the | |||
|
| Knight | Boiler Installation and | Operation | |
Service Blk |
| Manual for the proper piping methods for the Knight | |||
| boiler. |
|
|
| |
|
| • Check 120 vac to the boiler pump motor on a call for | |||
|
| heat. If voltage is not present, check the wiring back | |||
|
| to the main control board. Replace the main control | |||
|
| board if necessary. |
|
| |
|
| • If 120 vac is present on a call for heat and the boiler | |||
|
| pump is not operating, replace the pump. |
|
| |
|
| • Verify that the boiler pump is set to the proper speed | |||
|
| or that the boiler pump is the proper size. Reference | |||
|
| Section | 6 - Hydronic Piping of | the | Knight |
|
| Boiler Installation and Operation Manual for boiler | |||
|
| pump specifications. |
|
| |
|
|
|
|
|
|
45