9 Maintenance

Inspect ignition and flame sense electrodes

1.Remove the ignition and flame sense electrodes from the boiler heat exchanger access cover.

2.Remove any deposits accumulated on the ignition/flame sense electrode using sandpaper. If the electrodes cannot be cleaned satisfactorily, replace with new ones.

3.Replace ignition/flame sense electrode, making sure gasket is in good condition and correctly positioned.

Check ignition ground wiring

1.

Inspect boiler ground wire from the heat exchanger

 

access cover to ground terminal strip.

2.

Verify all wiring is in good condition and securely

 

attached.

3.

Check ground continuity of wiring using continuity

 

meter.

Check burner flame

1.Inspect flame through observation window.

2.If the flame is unsatisfactory at either high fire or low fire, turn off boiler and allow boiler to cool down. Remove the burner and clean it thoroughly using a vacuum cleaner or compressed air. Do not use compressed air to clean burner if performed inside a building.

3.Remove the burner, reference FIG. 9-2 below.

4.When replacing the burner, ensure gasket is in good condition and positioned correctly (FIG. 9-2).

Figure 9-2Burner Assembly

4. Replace ground wires if ground continuity is not

satisfactory.

Check all boiler wiring

1.Inspect all boiler wiring, making sure wires are in good condition and securely attached.

Check control settings

1. Set the SMART SYSTEM control module display to

Parameter Mode and check all settings. See Section 1 of

Outdoor Knight Boiler Service Manual. Adjust settings

INSULATION

HEAT EXCHANGER ACCESS DOOR

AIR / GAS ARM

BURNER

GASKET

SCREWS (QTY. 5)

IMG00447

if necessary. See Section 1 of the Outdoor Knight Boiler

Service Manual for adjustment procedures.

2. Check settings of external limit controls (if any) and

adjust if necessary.

Perform start-up and checks

1.Start boiler and perform checks and tests specified in Section 7 - Start-up.

2.Verify cold fill pressure is correct and that operating pressure does not go too high.

Check flame signal

1.At high fire the flame signal shown on the display should be at least 10 microamps.

2.A lower flame signal may indicate a fouled or damaged flame sense electrode. If cleaning the flame sense electrode does not improve, ground wiring is in good condition, and ground continuity is satisfactory, replace the flame sense electrode.

3.See Section 3 - Troubleshooting of the Outdoor Knight Boiler Service Manual for other procedures to deal with low flame signal.

52

Image 52
Contents Save this manual for future reference Contents When servicing boiler Please read before proceedingOutdoor Knight Boiler How it works Stainless steel heat exchangerModels 151 Model Ratings Outdoor Knight Boiler Ahri RatingDetermine boiler location Installation must comply withBefore locating the boiler, check Outdoor vent / air intake location Flooring and foundation Provide clearancesPrevent combustion air contamination Remove boiler from wood pallet Prepare boilerGas conversions Leveling the boiler 286Hydronic piping Near boiler piping components System temperature sensor Near boiler piping connectionsCirculator sizing Indirect water heatersFeet PressureModel Minimum Pipe Pump Size GrundfosSmart System / Multi-temperature loop control option Variable speed pump setupVariable speed pump option UP26-96 FC/VS IFC VS Stratos 1.25 3 xZone #1 Number of Units Model Required Pipe Sizes 6Single Boiler Multiple Temperatures 151 211 286 IMG00374 Number of Units 10Multiple Boilers Non-Zoned Primary/Secondary Piping Connecting gas supply piping Gas connectionsNatural gas Propane GasCheck inlet gas supply Single Unit Natural Gas Pipe Capacity ChartLength of Pipe in Straight Feet for 1/2 PSI Gas valve replacement Gas PressureField wiring Installation must comply withLine voltage connections Low voltage connectionsOutdoor temperature sensor High gas pressure switchLow gas pressure switch ThermostatFlow switch Runtime contacts Alarm contactsWiring of the cascade System supply sensor3Low Voltage Field Wiring Connections Condensate disposal Condensate drainFreeze protection when used Start-upCheck/control water chemistry Fill and test water systemCheck for gas leaks Check thermostat circuitsInspect/fill condensate system Inspect/check condensate lines and fittingsFinal checks before starting the boiler Start the boilerIf boiler does not start correctly Check system and boiler2Operating Instructions Set space heating operation Natural Gas PropaneConfiguration of the cascade Verify DHW modeSet domestic hot water DHW operation Operating information GeneralHow the boiler operates How the control module operatesTemperature control Protection featuresBoiler temperature regulation Outdoor reset operation CascadeSequence of operation Operation DisplayStandby, ready to start a new cycle Access modes InstallerOutdoor Knight boiler control module UserCall for Heat Operating information Dial Function Service technician Maintenance Maintenance and annual startupOwner maintenance Maintenance Flue vent system and air piping Check water systemCheck expansion tank Check boiler relief valveCheck ignition ground wiring Check all boiler wiringCheck control settings Check flame signalCleaning boiler heat exchanger Review with ownerOiled bearing circulators Model Kit Part Component Number DescriptionDiagrams PC Interface120 VAC High Voltage

151-286 specifications

Lochinvar 151-286 is a high-efficiency water heater designed for both residential and commercial applications. This model stands out due to its advanced technology, user-friendly controls, and robust construction, making it a reliable choice for those seeking to optimize their hot water supply.

One of the key features of the Lochinvar 151-286 is its impressive heating capacity. With a maximum input of 286,000 BTU/hr, it can efficiently meet hot water demands for a variety of settings, including hotels, restaurants, and other commercial facilities. This substantial output ensures that even during peak usage hours, hot water availability is maximized, reducing wait times and enhancing customer satisfaction.

The water heater utilizes a state-of-the-art condensing technology that maximizes efficiency by capturing and utilizing flue gas heat. This process allows the Lochinvar 151-286 to achieve an impressive thermal efficiency rating of up to 98%. The benefit of such high efficiency translates to significant energy savings and reduced operational costs over time, making it an environmentally friendly option as well.

The Lochinvar 151-286 is equipped with a user-friendly control system featuring advanced microprocessor controls. These controls allow for precise temperature management and monitoring, enabling users to set optimal temperatures according to their specific needs. Additionally, the heater includes built-in diagnostics, allowing for easy troubleshooting and maintenance, which minimizes downtime and extends the life of the unit.

Another standout characteristic of the Lochinvar 151-286 is its durable construction. Built with high-quality materials, including a robust stainless steel heat exchanger, this model is designed to withstand the rigors of daily use. The unit also features a compact design, which facilitates easy installation in various locations, whether it be in a utility closet or alongside existing equipment.

Safety features are paramount in the Lochinvar 151-286, with multiple safeguards in place to protect against overheating and other potential issues. The unit is designed to operate reliably, ensuring peace of mind for users who depend on consistent hot water availability.

In summary, the Lochinvar 151-286 water heater combines high capacity, exceptional efficiency, and user-friendly technology, making it an excellent choice for those seeking reliable hot water solutions. Its advanced features deliver performance and durability that stand out in the competitive market of water heating systems.