Lochinvar 151-286 Review with owner, Cleaning boiler heat exchanger, Oiled bearing circulators

Page 53

Outdoor Knight Boiler Installation & Operation Manual

9 Maintenance (continued)

Review with owner

1.Review the Outdoor Knight Boiler User’s Information Manual with the owner.

2.Emphasize the need to perform the maintenance schedule specified in the Outdoor Knight Boiler User’s Information Manual (and in this manual as well).

3.Remind the owner of the need to call a licensed contractor should the boiler or system exhibit any unusual behavior.

4.Remind the owner to follow the proper shutdown procedure and to schedule an annual start-up at the beginning of the next heating season.

Cleaning boiler heat exchanger

For recommended materials; including brush, appropriate extension(s), refractory cover, and detailed instructions see Table 9B - Heat Exchanger Cleaning Kits.

1.Shut down boiler:

Follow the “To Turn Off Gas to Appliance” instructions for the boiler in Section 7 - Startup.

Do not drain the boiler unless it will be exposed to freezing temperatures. If using freeze prevention fluid in system, do not drain.

2.Allow time for the boiler to cool to ambient temperature if it has been firing.

3.Remove the nuts securing the heat exchanger access cover to the heat exchanger and set aside.

4.Remove the heat exchanger access cover, burner, and gas/air arm assembly.

￿WARNING The boiler contains ceramic fiber materials. Use care when handling these

materials per instructions in the Service Manual. Failure to comply could result in severe personal injury.

5.Remove the condensate hose from the heat exchanger end. Connect a field supplied 3/4" diameter hose to a drain pan. Using field supplied means, cover the refractory in the back of the combustion chamber of the heat exchanger.

6.Use a vacuum cleaner to remove any accumulation on the boiler heating surfaces. Do not use any solvent.

7.Brush the heat exchanger while dry using a nylon bristle brush. Caution: DO NOT use a metal brush. Re-vacuum the heat exchanger.

8.Finish cleaning using a clean cloth dampened with warm water. Rinse out debris with a low pressure water supply.

9.Allow the heat exchanger to thoroughly dry.

10.Remove the field supplied rear refractory cover from the back of the combustion chamber of the heat exchanger and reassemble.

11.Close isolation valves on piping to isolate boiler from system. Attach a hose to the boiler drain and flush boiler thoroughly with clean water by using purging valves to allow water to flow through the water make-up line to the boiler.

12.Perform start-up and check-out procedures in the Check Flame and Combustion - Section 7 - Startup on pages 35 and 37 of this manual.

13.Replace the access cover and restore boiler to operation.

Table 9B Heat Exchanger Cleaning Kits

Model

 

Kit

Part

Component

Number

Number

Description

 

 

 

 

 

 

151

 

 

CTN20005

Rear Refractory Cover

 

 

MSC20083*

Nylon 4" Wheel Brush*

-

KIT30063

MSC20084

3mm Allen Wrench

286

 

 

 

 

 

MSC20086

1/4" x 24" Drill Extension

 

 

* Do NOT use a metal brush. Only use

￿ CAUTION

the kit provided brush or an equivalent

 

 

 

 

replacement nylon brush.

Figure 9-3Rope Gasket - Heat Exchanger Door

ROPE GASKET

CAUTION: IF GASKET IS DAMAGED

DO NOT REUSE, THE HEAT EXCHANGER DOOR

MUST BE REPLACED.

Rope gasket is intended for sealing combustion NOTICE (FIG. 9-3). If damaged DO NOT reuse, the

heat exchanger door must be replaced. Consult factory for replacement heat exchanger door (kit WTR3080).

Oiled bearing circulators

1.The circulator shipped with the outdoor boiler is water- lubricated. No oiling is required.

2.Check other circulators in the system. Oil any circulators requiring oil, following circulator manufacturer’s instructions. Over-oiling will damage the circulator.

3.Replace the boiler front access cover.

53

Image 53
Contents Save this manual for future reference Contents Please read before proceeding When servicing boilerStainless steel heat exchanger Outdoor Knight Boiler How it worksModels 151 Model Outdoor Knight Boiler Ahri Rating RatingsBefore locating the boiler, check Installation must comply withDetermine boiler location Prevent combustion air contamination Provide clearancesOutdoor vent / air intake location Flooring and foundation Gas conversions Prepare boilerRemove boiler from wood pallet 286 Leveling the boilerHydronic piping Near boiler piping components Near boiler piping connections System temperature sensorCirculator sizing Indirect water heatersPressure FeetModel Minimum Pipe Pump Size GrundfosVariable speed pump setup Smart System / Multi-temperature loop control optionVariable speed pump option UP26-96 FC/VS IFC VS Stratos 1.25 3 xZone #1 Number of Units Model Required Pipe Sizes 6Single Boiler Multiple Temperatures 151 211 286 IMG00374 Number of Units 10Multiple Boilers Non-Zoned Primary/Secondary Piping Gas connections Connecting gas supply pipingPropane Gas Natural gasLength of Pipe in Straight Feet for 1/2 PSI Single Unit Natural Gas Pipe Capacity ChartCheck inlet gas supply Gas Pressure Gas valve replacementInstallation must comply with Field wiringLine voltage connections Low voltage connectionsHigh gas pressure switch Outdoor temperature sensorLow gas pressure switch ThermostatAlarm contacts Flow switch Runtime contactsWiring of the cascade System supply sensor3Low Voltage Field Wiring Connections Condensate drain Condensate disposalStart-up Freeze protection when usedCheck/control water chemistry Fill and test water systemCheck thermostat circuits Check for gas leaksInspect/fill condensate system Inspect/check condensate lines and fittingsStart the boiler Final checks before starting the boilerIf boiler does not start correctly Check system and boiler2Operating Instructions Natural Gas Propane Set space heating operationSet domestic hot water DHW operation Verify DHW modeConfiguration of the cascade General Operating informationHow the boiler operates How the control module operatesProtection features Temperature controlBoiler temperature regulation Cascade Outdoor reset operationOperation Display Sequence of operationStandby, ready to start a new cycle Installer Access modesOutdoor Knight boiler control module UserCall for Heat Operating information Dial Function Owner maintenance Maintenance Maintenance and annual startupService technician Maintenance Check water system Flue vent system and air pipingCheck expansion tank Check boiler relief valveCheck all boiler wiring Check ignition ground wiringCheck control settings Check flame signalReview with owner Cleaning boiler heat exchangerOiled bearing circulators Model Kit Part Component Number DescriptionPC Interface DiagramsHigh Voltage 120 VAC

151-286 specifications

Lochinvar 151-286 is a high-efficiency water heater designed for both residential and commercial applications. This model stands out due to its advanced technology, user-friendly controls, and robust construction, making it a reliable choice for those seeking to optimize their hot water supply.

One of the key features of the Lochinvar 151-286 is its impressive heating capacity. With a maximum input of 286,000 BTU/hr, it can efficiently meet hot water demands for a variety of settings, including hotels, restaurants, and other commercial facilities. This substantial output ensures that even during peak usage hours, hot water availability is maximized, reducing wait times and enhancing customer satisfaction.

The water heater utilizes a state-of-the-art condensing technology that maximizes efficiency by capturing and utilizing flue gas heat. This process allows the Lochinvar 151-286 to achieve an impressive thermal efficiency rating of up to 98%. The benefit of such high efficiency translates to significant energy savings and reduced operational costs over time, making it an environmentally friendly option as well.

The Lochinvar 151-286 is equipped with a user-friendly control system featuring advanced microprocessor controls. These controls allow for precise temperature management and monitoring, enabling users to set optimal temperatures according to their specific needs. Additionally, the heater includes built-in diagnostics, allowing for easy troubleshooting and maintenance, which minimizes downtime and extends the life of the unit.

Another standout characteristic of the Lochinvar 151-286 is its durable construction. Built with high-quality materials, including a robust stainless steel heat exchanger, this model is designed to withstand the rigors of daily use. The unit also features a compact design, which facilitates easy installation in various locations, whether it be in a utility closet or alongside existing equipment.

Safety features are paramount in the Lochinvar 151-286, with multiple safeguards in place to protect against overheating and other potential issues. The unit is designed to operate reliably, ensuring peace of mind for users who depend on consistent hot water availability.

In summary, the Lochinvar 151-286 water heater combines high capacity, exceptional efficiency, and user-friendly technology, making it an excellent choice for those seeking reliable hot water solutions. Its advanced features deliver performance and durability that stand out in the competitive market of water heating systems.