NOTICE

Clearance to venting is for single wall vent pipe. If Type L vent is used, clearance may be reduced to the minimum required by the vent pipe manufacturer.

C.PROVIDE COMBUSTION AND VENTILATION AIR. Local and National Codes may apply and should be referenced.

WARNING

Adequate combustion and ventilation air must be provided to assure proper combustion and to maintain safe ambient air temperatures.

Do not install boiler where gasoline or other flammable vapors or liquids, or sources of hydrocarbons (i.e. bleaches, fabric softeners, etc.) are used or stored.

Do not install boiler in laundry room, or, in vicinity of clothes dryer to prevent inadequate air supply to burner and lint contamination of burner air intake openings.

1.Determine volume of space (boiler room). Rooms communicating directly with the space in which the appliances are installed, through openings not furnished with doors, are considered a part of the space.

Volume(ft3) = Length(ft) x Width(ft) x Height(ft)

2.Determine total input of all appliances in the space.

Add inputs of all appliances in the space and round the result to the nearest 1000 BTU per hour.

3.Determine type of space. Divide Volume by total input of all appliances in space. If the result is greater than or equal to 50 ft3/1000 BTU per hour, then it is considered an unconfined space. If the result is less than 50 ft3/1000 BTU per hour then the space is considered a confined space.

4.For boiler located in an unconfined space of a conventionally constructed building, the fresh air infiltration through cracks around windows and doors normally provides adequate air for combustion and ventilation.

5.For boiler located in a confined space or an unconfined space in a building of unusually tight construction, provide outdoor air.

a.Outdoor air for combustion may be provided with an optional Burnham Inlet Air Accessory

Kit, Part Number 611280031 (only available and suitable for use on Beckett AFG with burner enclosure cover burner). See Section V for installation details.

or

b.Outdoor air may be provided with the use of two permanent openings which communicate directly or by duct with the outdoors or spaces (crawl or attic) freely communicating with the outdoors. Locate one opening within 12 inches of top

of space. Locate remaining opening within 12 inches of bottom of space. Minimum dimension of air opening is 3 inches. Size each opening per following:

i. Direct communication with outdoors. Minimum free area of 1 square inch per

4,000 BTU per hour input of all equipment in space.

ii. Vertical ducts. Minimum free area of 1 square inch per 4,000 BTU per hour input of all equipment in space. Duct cross-sectional area shall be same as opening free area.

iii. Horizontal ducts. Minimum free area of 1 square inch per 2,000 BTU per hour input of all equipment in space. Duct cross-sectional area shall be same as opening free area.

Alternate method for boiler located within confined space. Use indoor air if two permanent openings communicate directly with additional space(s) of sufficient volume such that combined volume of all spaces meet criteria for unconfined space. Size each opening for minimum free area of 1 square inch per 1,000 BTU per hour input of all equipment in spaces, but not less than 100 square inches.

6.Louvers and Grilles of Ventilation Ducts

a.All outside openings should be screened and louvered. Screens used should not be smaller than 1/4 inch mesh. Louvers will prevent the entrance of rain and snow.

b.Free area requirements need to consider the blocking effect of louvers, grilles, or screens protecting the openings. If the free area of the louver or grille is not known, assume wood louvers have 20-25 percent free area and metal louvers and grilles have 60-75 percent free area.

c.Louvers and grilles must be fixed in the open position, or interlocked with the equipment to open automatically during equipment operation.

Image 8
Contents MegaSteam 100618-01R4-5/08 Price $3.00Important Information Read Carefully Page Table of Contents Page =B=R NET Section I PRE-INSTALLATION Boiler is Suitable for InstallationPage Control Carton Insulation WrapperJacket Carton Instruction/Label BagProcedure To Open, Close and Secure Burner Swing Door Jacket Front Panel InstallationBoiler Removal from Skid Page Page Closing / Securing Burner Swing Door Flueway Baffle InstallationBaffle Usage Jacket Rear Panel Installation Flue Cleanout Covers and Smokebox Collar InstallationUNC Less HeaterSide and Top Jacket Panel Installation External Electrical Enclosure MountingTrim and Controls Installation. Pressure Limit Installation Pressure Gauge and Gauge Glass InstallationFloat-Type Lwco and Pressure Limit Installation Safety Valve and Drain Valve Installation Oil Burner InstallationDo not install burner without gasket Aquastat bulb must be fully inserted into the wellOil Burner Installation Section III Steam Boiler Piping & Trim Evaluate the existing steam systemRecommended Boiler Piping for Gravity Return Steam Boiler Section IV Tankless & Indirect Water Heater Piping Schematic Tankless Water Heater Piping Tankless Heater Data Alliance Water Heater Piping with MegaSteam Boiler Chimney Venting Chimney ConnectorSection V Venting & Air intake piping Recommended Vent Pipe Arrangement and Chimney Requirements Stack Temperature DraftMinimum Clearances Do not exceed maximum allowable air intake lengthSeal all external joints with weatherproof caulk Section VI Electrical GeneralWiring Diagram, Steam, Hydrolevel CG450 Probe Lwco Wiring Diagram, Steam, McDonnell & Miller PS-801 Probe Lwco Wiring Diagram, Steam, McDonnell & Miller #67 Float Lwco Boiler Sequence of Operation with Probe Lwco See Figure Boiler Sequence of Operation with Float Lwco See FigureSingle Pipe Oil Lines Single Pipe Oil LineSingle-Stage Units 3450 RPM Two Pipe Systems Two Pipe Oil LinesTwo-Stage Units 3450 RPM Two Pipe Systems Always Inspect Installation Before Starting Burner Section Viii System START-UPAdjusting Fuel Pump Pressure Adjust OIL Burner While OPERATING. flame presentPage R7184 Terminals, LED and Reset Button Cad Cell Resistance When Sensing FlameCad Cell Location Jumper must be removed after this checkAvoid Breathing Fiber Particulates and Dust Section Ix Maintenance and Service Instructions Steam BoilersPage Gallons / Month MST288 MST396 MST513 MST629 Clean the Combustion Chamber Section X Boiler CleaningClean the Flueways See Figure Page Section XI Trouble Shooting Section XII Repair Parts Bare Boiler Assembly Bare Boiler Assembly Bare Boiler Assembly 1FF Jacket Assembly Jacket Assembly MST288 Thru MST629 Steam Boilers Trim and Controls MST Trim and Controls Beckett AFG Burner Beckett OIL Burner Part NOS. for MegaSteam Series Boilers Beckett AFG Burner specifications OUTService Record Limited Warranty

MST513, MST396, MST629, MST288 specifications

The Burnham MST series, comprising models MST396, MST629, MST513, and MST288, is renowned for its robust design and exceptional performance in the boiler industry. Each model is engineered to provide optimal efficiency and reliability for residential and commercial heating applications.

The Burnham MST396 is distinguished by its high thermal efficiency and advanced combustion technology. This model features a cast iron heat exchanger which ensures superior heat retention and distribution. The MST396 is equipped with a powerful burner that allows for variable firing rates, maximizing efficiency and extending the lifespan of the unit. Additionally, it includes a built-in electronic ignition system that enhances reliability while reducing the need for frequent maintenance.

Moving to the MST629, this model is designed for larger applications needing higher output. It boasts a significant BTU input and utilizes a multi-stage burner system. This ensures optimal combustion and adapts to varying demand, providing consistent heat without wasting energy. The MST629 also incorporates enhanced insulation and an advanced flue gas venting system to improve safety and minimize energy loss.

The MST513 caters to mid-sized applications with its adaptable performance and user-friendly features. This model is notable for its compact design, making it suitable for installations with limited space. It uses a two-stage burner for efficient energy use and offers a smart control system that monitors performance in real-time. This allows users to make informed decisions about their energy consumption and maintenance needs, ultimately leading to cost savings.

Lastly, the MST288 is the smaller model in the series, ideal for homes and small businesses. Despite its size, it does not compromise on efficiency. The MST288 features a straightforward design, ensuring ease of installation and maintenance. It utilizes a single-stage burner that provides consistent heat output, making it a reliable choice for low-demand applications. The unit is also equipped with adjustable settings, allowing users to tailor their heating needs effectively.

In summary, the Burnham MST series demonstrates a remarkable blend of innovation and practicality across its models. With features like advanced burner technology, efficient heat exchangers, and smart controls, the MST396, MST629, MST513, and MST288 cater to a wide range of heating needs while prioritizing energy efficiency and user comfort. These models stand out in the market, continually setting a standard for performance and reliability in heating solutions.