Burnham MST396, MST288, MST629 manual Section Ix Maintenance and Service Instructions, Steam Boilers

Page 45

SECTION Ix: MAINTENANCE AND SERVICE INSTRUCTIONS

A.MAINTENANCE OF LOW WATER CUT- OFF DEVICES

WARNING

Probe and float type low water cut-off devices require annual inspection and maintenance.

1.PROBE TYPE LOW WATER CUT-OFF Although these devices are solid state in their operation, the probe is exposed to possible contamination in the boiler water and subject to fouling.

It is important to physically remove the probe from the boiler tapping annually and inspect that probe for accumulation of scale or sediment.

Follow these steps to inspect, clean and/or replace the probe:

a.Turn off electric service to the boiler.

b.Drain boiler water to a level below the tapping for the probe.

c.Disconnect wiring connections between the low water cut-off control and the probe.

d.Remove the low water cut-off control from the probe.

DANGER

Assure that the boiler is at zero pressure before removing the LWCO probe. Do not rely on the pressure gauge to indicate that the boiler is at zero pressure. Open the safety valve to relieve all internal pressure prior to proceeding. Safety valve discharge piping must be piped such that the potential for burns is eliminated.

e.Unscrew the probe from the boiler tapping.

f.Inspect that portion of the probe that is exposed to the boiler water for a scale or sediment buildup.

g.Light deposits may be removed by wiping the probe with a damp cloth. Wiping the probe with a cloth soaked in vinegar will remove more tenacious lime deposits. The most stubborn deposits may be removed from the probe by using a diluted amount, 3 parts of water to 1 part of phosphoric acid (H2PO4).

CAUTION

Exercise caution when handling phosphoric acid and follow the instruction label on its container.

h.Clean the pipe threads of the probe to remove old, hardened pipe dope and other foreign matter.

i.Apply a moderate amount of good quality pipe dope to the pipe threads on the probe, leaving the two end threads bare. Do not use PTFE (Teflon) tape.

j.Screw the probe into the boiler tapping.

k.Mount the low water cut-off control on the probe.

l.Reconnect the control to probe wiring.

m.Fill the boiler to its normal waterline.

n.Add boiler water treatment compound as needed

(refer to Paragraph B.).

o.Restore electric service to the boiler.

p.Fire burner to bring the water in the boiler to a boil to drive off free oxygen.

q.WARNING — BEFORE RETURNING

BOILER TO SERVICE: Follow the low water cut-off check out procedure in Section VIII, Paragraph I, No. 4.

2.FLOAT TYPE LOW WATER CUT-OFF During the heating season, if an external low water cut-off is on the boiler, the blow off valve should be opened once a month (use greater frequency where conditions warrant), to flush out the sediment chamber so the device will be free to function properly.

Low water cut-offs and water feeders should be dismantled annually by qualified personnel, to the extent necessary to insure freedom from obstructions and proper functioning of the working parts. Inspect connecting lines to boiler for accumulation of mud, scale, etc., and clean as required. Examine all visible wiring for brittle or worn insulation and make sure electrical contacts are clean and that they function properly. Give special attention to solder joints on bellows and float when this type of control is used. Check float for evidence of collapse and check mercury bulb (where applicable) for mercury separation or discoloration. Do not attempt to repair mechanisms in the field.

Complete replacement mechanisms, including necessary gaskets and installation instructions are available from the manufacturer.

B.BOILER AND SYSTEM CLEANING INSTRUCTIONS FOR TROUBLE FREE OPERATION

1.STEAM BOILERS

a.Oil, greases & sediments which accumulate in a new boiler and piping must be removed in order to prevent an unsteady water line and carry over of the water into the supply main above boiler.

45

Image 45
Contents 100618-01R4-5/08 Price $3.00 MegaSteamImportant Information Read Carefully Page Table of Contents Page =B=R NET Boiler is Suitable for Installation Section I PRE-INSTALLATIONPage Insulation Wrapper Control CartonJacket Carton Instruction/Label BagJacket Front Panel Installation Procedure To Open, Close and Secure Burner Swing DoorBoiler Removal from Skid Page Page Flueway Baffle Installation Baffle UsageClosing / Securing Burner Swing Door Flue Cleanout Covers and Smokebox Collar Installation Jacket Rear Panel InstallationLess Heater UNCExternal Electrical Enclosure Mounting Side and Top Jacket Panel InstallationPressure Gauge and Gauge Glass Installation Trim and Controls Installation. Pressure Limit InstallationFloat-Type Lwco and Pressure Limit Installation Oil Burner Installation Safety Valve and Drain Valve InstallationDo not install burner without gasket Aquastat bulb must be fully inserted into the wellOil Burner Installation Evaluate the existing steam system Section III Steam Boiler Piping & TrimRecommended Boiler Piping for Gravity Return Steam Boiler Section IV Tankless & Indirect Water Heater Piping Schematic Tankless Water Heater Piping Tankless Heater Data Alliance Water Heater Piping with MegaSteam Boiler Chimney Connector Section V Venting & Air intake pipingChimney Venting Recommended Vent Pipe Arrangement and Chimney Requirements Draft Stack TemperatureDo not exceed maximum allowable air intake length Minimum ClearancesSeal all external joints with weatherproof caulk General Section VI ElectricalWiring Diagram, Steam, Hydrolevel CG450 Probe Lwco Wiring Diagram, Steam, McDonnell & Miller PS-801 Probe Lwco Wiring Diagram, Steam, McDonnell & Miller #67 Float Lwco Boiler Sequence of Operation with Float Lwco See Figure Boiler Sequence of Operation with Probe Lwco See FigureSingle Pipe Oil Line Single Pipe Oil LinesTwo Pipe Oil Lines Two-Stage Units 3450 RPM Two Pipe SystemsSingle-Stage Units 3450 RPM Two Pipe Systems Section Viii System START-UP Always Inspect Installation Before Starting BurnerAdjust OIL Burner While OPERATING. flame present Adjusting Fuel Pump PressurePage Cad Cell Resistance When Sensing Flame R7184 Terminals, LED and Reset ButtonJumper must be removed after this check Cad Cell LocationAvoid Breathing Fiber Particulates and Dust Steam Boilers Section Ix Maintenance and Service InstructionsPage Gallons / Month MST288 MST396 MST513 MST629 Section X Boiler Cleaning Clean the Flueways See FigureClean the Combustion Chamber Page Section XI Trouble Shooting Section XII Repair Parts Bare Boiler Assembly Bare Boiler Assembly Bare Boiler Assembly 1FF Jacket Assembly Jacket Assembly MST288 Thru MST629 Steam Boilers Trim and Controls MST Trim and Controls Beckett AFG Burner Beckett OIL Burner Part NOS. for MegaSteam Series Boilers OUT Beckett AFG Burner specificationsService Record Limited Warranty

MST513, MST396, MST629, MST288 specifications

The Burnham MST series, comprising models MST396, MST629, MST513, and MST288, is renowned for its robust design and exceptional performance in the boiler industry. Each model is engineered to provide optimal efficiency and reliability for residential and commercial heating applications.

The Burnham MST396 is distinguished by its high thermal efficiency and advanced combustion technology. This model features a cast iron heat exchanger which ensures superior heat retention and distribution. The MST396 is equipped with a powerful burner that allows for variable firing rates, maximizing efficiency and extending the lifespan of the unit. Additionally, it includes a built-in electronic ignition system that enhances reliability while reducing the need for frequent maintenance.

Moving to the MST629, this model is designed for larger applications needing higher output. It boasts a significant BTU input and utilizes a multi-stage burner system. This ensures optimal combustion and adapts to varying demand, providing consistent heat without wasting energy. The MST629 also incorporates enhanced insulation and an advanced flue gas venting system to improve safety and minimize energy loss.

The MST513 caters to mid-sized applications with its adaptable performance and user-friendly features. This model is notable for its compact design, making it suitable for installations with limited space. It uses a two-stage burner for efficient energy use and offers a smart control system that monitors performance in real-time. This allows users to make informed decisions about their energy consumption and maintenance needs, ultimately leading to cost savings.

Lastly, the MST288 is the smaller model in the series, ideal for homes and small businesses. Despite its size, it does not compromise on efficiency. The MST288 features a straightforward design, ensuring ease of installation and maintenance. It utilizes a single-stage burner that provides consistent heat output, making it a reliable choice for low-demand applications. The unit is also equipped with adjustable settings, allowing users to tailor their heating needs effectively.

In summary, the Burnham MST series demonstrates a remarkable blend of innovation and practicality across its models. With features like advanced burner technology, efficient heat exchangers, and smart controls, the MST396, MST629, MST513, and MST288 cater to a wide range of heating needs while prioritizing energy efficiency and user comfort. These models stand out in the market, continually setting a standard for performance and reliability in heating solutions.