Burnham V9A manual Typical Arrangement for Stub Vent

Page 12

WARNING

When a V9A gas fired boiler is connected to a venting system that is designed so that it will operate under a positive pressure, manufactured vent systems, designed and approved for positive pressure application per UL1738, must be used (for example, Van-Packer model CS, Protech Model FasNSeal / FasNSeal W2, Heatfab Saf-T-Vent or equivalent).

When a V9A oil fired or combination gas/oil fired boiler is connected to a venting system that is designed so that it will operate un- der a positive pressure, manufactured vent systems, designed and approved for posi- tive pressure application, must be used (for example, Selkirk Metalbestos Model PS / IPS, Van-Packer Model ES or equivalent).

The V9A Series boiler is designed for forced draft firing and may be used with a conventional natural draft stack (15’ minimum height) or a stub vent, sometimes called a diesel stack (see Figure 3a). See Table I for the proper vent outlet size. For low silhouette vent terminations, see Figure 3b. Draft controls are not normally required, although they may be used on installations where a natural draft stack is used or on multiple boiler installations with a common stack. The boiler is provided with a breeching damper, which should be adjusted to maintain a positive pressure of 0.1” W.C. in the vent connector box during burner high fire operation (see breeching pressure sensing port in Figure 1).

Figure 3a: Typical Arrangement for Stub Vent

If the venting system is designed for positive or forced draft venting, the boiler, vent connector and stack will operate under positive pressure. Gas tight vent systems designed for pressure systems must be used to prevent flue by-product leakage. The vent height is usually limited to prevent negative draft, typically three (3) feet above the roof line (see Figure 3a). The damper shall be adjusted to maintain a positive pressure of 0.1” W.C. in the vent connector box during burner high fire operation (see breeching pressure sensing port in Figure 1).

If the venting system is designed for negative pressure (natural draft), the boiler still operates with positive pressure in the chamber and up to the fixed damper on the flue collar. However, if the venting system is larger than what is required, the stack will provide a surplus draft (or negative pressure) that may require the use of a barometric damper to maintain the positive 0.1” W.C. pressure at the flue outlet. Multiple forced draft boiler stacks should always be designed as negative to ensure the products of combustion do not exit a boiler that is not firing.

WARNING

Venting instructions are recommendations only. Consult a venting expert on the design of a specific vent system for your application. The ASHRAE Venting Guide and The National Fuel Gas Code, NFPA 54 should be considered in all venting systems.

Conventional vent material may not be suitable for the application. Flue gases can leak carbon monoxide from the joints on these materials and can result in severe personal injury or death.

Installations having long horizontal runs or an excessive amount of tees or elbows will restrict the flow of combustion gases and can result in condensation, flue gas leakage of carbon monoxide, resulting in severe personal injury or death.

12

Image 12
Contents V9A Series Boiler Page Important Information Read Carefully USA BoilersPage Page Table of Contents Table of Contents Section I General Information Table I Boiler Ratings / Data Recommended Service Clearance Locate the UnitChimney or Vent Typical Arrangement for Stub Vent Right Section II Cast Iron Block Assembly Assembly of Sections Manual DRAW- UPSetting of Nipples V9A Section Arrangement Assembly of Sections Hydraulic DRAW-UP Front and Rear Section Channel Hydraulic Draw-Up Sections Section III Installation Instructions Bare Boiler Assembly Avoid Breathing Fiber Particulates and Dust Left Side Canopy Intermediate Bracket Mount Rear Observation Port Cover Refer to Figure Inspect ALL Boiler SealsV9A Series Jacket Assembly Boiler Models V903A thru V912A Burner Mounting Plate Refer to Figures 16 Mount Burner Adapter Plate to Burner Mounting PlateSteam Boilers Install Steam Trim Water Boilers Install Water TrimBurner Installation Packaged BoilerShipping Information Page V9A Series Minimum Piping Parallel Water Boiler V9A Series Minimum Piping Primary Secondary Water Boiler Page Page Page Page Page Page Page Mounting Elevations of M&M 150 Float Low Water Cut-Offs Schematic Tankless Heater Piping Page DHW Generation with Indirect Water Heater Water Boiler Pressure Relief Valve Hook-Up Always Inspect Installation Before Starting Burner Section IV Operating InstructionsBoiler and System Cleaning Steam Boiler Test ControlsBoiler and System Cleaning Water Boilers Frequent Water Addition Oxygen CorrosionSection V Service Instructions Clean the Boiler FluewaysMaintenance of LOW Water Cutoff Devices Probe Type LOW Water CutoffGeneral Maintenance Considerations Section VI Burner Specifications OIL BurnersCombination GAS / OIL Burners Table VII Webster Burner Specifications Section VII Repair Parts Head Band Low High FireSection VII Repair Parts Jacket Repair Parts Models V903A Thru V912A Bare Boiler Assembly Repair Parts for Bare Boiler Assembly Repair Parts for Bare Boiler Assembly Steam Trim / Water Trim Service Record Service Record

V9A specifications

Burnham V9A is a well-established model in the world of cast iron boilers, renowned for its efficiency and reliability in residential heating applications. As a part of Burnham's esteemed line of heating solutions, the V9A is designed to provide homeowners with consistent warmth while prioritizing fuel economy and ease of use.

One of the defining features of the Burnham V9A is its durable cast iron construction. This robust material enables the boiler to withstand high temperatures and pressures, ensuring a long service life. The V9A is engineered with several sections that are joined together, allowing for easier maintenance and potential adaptability to various heating demands. The boiler's design also promotes excellent heat retention, which not only enhances performance but contributes to overall energy efficiency.

In terms of technology, the Burnham V9A stands out with its advanced combustion design. With an efficiency rating of up to 85%, this model maximizes the heat output while minimizing fuel consumption. The boiler is compatible with both natural gas and propane, providing flexibility for users to choose their preferred fuel source. Additionally, the V9A is designed to operate with a minimum of venting requirements, making installation simpler and more cost-effective.

The Burnham V9A also features a choice of various firing rates, allowing homeowners to select the optimal heating output for their specific needs. This versatility ensures that the boiler can be effectively sized for different home environments, making it a highly adaptable option for a broad range of residential settings.

Moreover, one key characteristic of the Burnham V9A is its user-friendly control systems. It comes equipped with reliable electronic ignition and offers options for outdoor reset controls, which enhance efficiency by adjusting the boiler's operation based on the outdoor temperature. This advanced control capability not only optimizes energy use but also enhances comfort levels in the home.

Overall, the Burnham V9A represents a balance of durability, efficiency, and modern convenience, making it a top choice for homeowners seeking a reliable heating solution. Its combination of cast iron construction, advanced technology, and user-friendly features solidify its reputation in the competitive market of heating systems, ensuring comfort and peace of mind for years to come.