Figure 18: Electrode / Head Setting

7.Bleed the fuel unit when the burner motor starts rotating. To bleed, loosen the vent fitting (with plastic hose attached) and catch the oil in an empty container. Continue to bleed for 15 seconds after oil is free of air bubbles. Tighten the vent fitting when all the air is purged. NOTE: Bleeding might not be necessary with a two pipe system. When vent fitting is closed, burner flame should start immediately.

8.ADJUST OIL PRESSURE

a.Locate oil pressure adjusting screw and turn screw to obtain 140 PSIG pressure.

b.DO NOT REMOVE PRESSURE GAUGE until later.

9.ADJUST AIR SETTING on burner for a light orange colored flame. Use a smoke tester and adjust air for minimum smoke (not to exceed #1) with a minimum of excess air. Make final check using suitable instrumentation to obtain a

CO2 of 11.5 to 12.5%. These settings will assure a safe and efficient operating condition. If the flame

appears stringy instead of a solid fire, try another nozzle of the same type. Flame should be solid and compact.

10.TURN "OFF" BURNER BY OPENING SERVICE SWITCH. Remove pressure gauge. Install gauge port plug and tighten. Re-start burner.

11.HINTS ON COMBUSTION

a.NOZZLES — Although the nozzle is a relatively inexpensive device, its function is critical to the successful operation of the oil burner. The selection of the nozzle supplied

with the microTEKDV boiler is the result of extensive testing to obtain the best flame shape and efficient combustion. Other brands of the same spray angle and spray pattern may be used but may not perform at the expected level of CO2 and smoke. Nozzles are delicate and should be protected from dirt and abuse. Nozzles are mass-produced and can vary from sample to sample. For all of those reasons a spare nozzle is a desirable item for a serviceman to have.

b.FLAME SHAPE — Looking into the combustion chamber through the flame plug hole, the flame should appear straight with no sparklers rolling up toward the top of the chamber. If the flame drags to the right or left, sends sparklers upward or makes wet spots on the rear door insulation piece, the nozzle should be replaced. If the condition persists look for fuel leaks, air leaks, water or dirt in the fuel as described below.

c.FUEL LEAKS — Any fuel leak between the pump and the nozzle will be detrimental to good combustion results. Look for wet surfaces in the air tube, under the transformer, and around the air inlet. Any such leaks should be repaired as they may cause erratic burning of the fuel and in the extreme case may become a fire hazard.

d.AIR LEAKS — Any such leaks should be repaired, as they may cause erratic burning of the fuel and in extreme cases may become a fire hazard.

There are many possible causes of air leaks in oil lines such as:

23

Image 23 Contents
81433101R3-3/00 Important Information Please Read this page Carefully Page USA Boilers Table of Contents Pre-Installation Removal of Boiler from Skid Install Boiler ControlII. Unpack Boiler Remove CrateProper Hinge Bracket Installation III. Water Piping and Trim Design and install boiler and system piping toRecommended Boiler Piping for Zoning with Valves Recommended Boiler Piping for Zoning with Circulators General Guidelines IV. Venting / Air Intake PipingDirect Oil Vent Pipe Pipe Length Burnham Part No Vent Installation Vent Connector, Assembled Air Intake Installation Direct Vent only See Figure Page Sequence of Operations Electrical and Sequence of OperationsElectrical Schematic Wiring Diagram Single-pipe Oil Lines VI. Oil PipingGeneral Two-Pipe Oil Lines Two-Pipe InstallationRemove Test Plug in Flue Collar Alwaysinspectinstallationbefore Starting BurnerVII. System Start-up BURNERSTART-UPHints on Combustion Adjust OIL PressureTest Controls Simulate ignition failure For Heating Serviceman onlySimulate power failure Simulate flame failureBurner Section Viii Service and CleaningFiretubes and Combustion Chamber Low water cutoff if so equipped Service Notes Urnham Corporation Regional Offices IX. Repair PartsLedv Boiler Trim & Controls Ledv Boiler Jacket & Insulation Ledv Bare Boiler Assembly PartsRepair KitVent 22Figure Beckett Afii Oil Burner Repair Part LEDV1 LEDV2 LEDV3