Ariston 47-116-12, A/23 MFFI Flue Connections, Mains Water Feed Central Heating, Filling

Page 10

2.9Flue Connections

public access. Air Release Points:

These must be fitted at all high points where air naturally collects and must be sited to facilitate complete filling of the system.

The appliance has an integral sealed expansion vessel to accommodate the increase of water value when the system is heated.

It can accept up to 7 l (1.5 gal) of expansion water. If the heating circuit has an unusually high water content, calculate the total expansion and add an additional sealed expansion vessel with adequate capacity.

Mains Water Feed - Central Heating:

There must be no direct connection to the mains water supply even through a non-return valve, without the approval of the Local Water Authority.

Filling:

A temporary method for initially filling the system and replacing lost water during servicing in accordance with Water Supply Byelaw 14 must be provided.

Domestic Water

The domestic water must be in accordance with the relevant recommendation of BS 5546:1990. Copper tubing to BS EN 1057:1996 is recommended for water carrying pipe work and must be used for pipe work carrying drinking water.

Residual Head of the Boiler

Flue System

The provision for satisfactory flue termination must be made as described in BS 5440-1.

The appliance must be installed so that the flue terminal is exposed to outdoor air. The terminal must not discharge into another room or space such as an outhouse or lean-to.

It is important that the position of the terminal allows a free passage of air across it at all times.

The terminal should be located with due regard for the damage or discolouration that might occur on buildings in the vicinity.

In cold or humid weather water vapour may condense on leaving the flue terminal.

The effect of such "steaming" must be considered.

If the terminal is less than 2 metres above a balcony, above ground or above a flat roof to which people have access, then a suitable terminal guard must be fitted. When ordering a terminal guard, quote the appliance model number.

A suitable terminal guard is available from:

TOWER FLUE COMPONENTS

Morley Road

Tonbridge

Kent TN9 1RA

The minimum acceptable spacing from the terminal to obstructions and ventilation openings are specified in Fig. 2.5.

10

B023

Image 10
Contents Mffi A/27 Mffi Table of Contents General Information General InstructionsTechnical Information MffiMffi A/27 Mffi Overall ViewInstallation Reference Standards Siting the ApplianceOverall Dimensions ClearancesElectrical Connection Mounting the ApplianceGas Connection Pipe Work Safety Valve DischargeWater Connections By-passMains Water Feed Central Heating Flue ConnectionsFilling Terminal Position B023 Coaxial System Room Thermostat Connection Electrical Diagram ColoursB023 Initial Preparation Water Circuit DiagramMffi Commissioning Filling the Heating SystemControl Panel Removing the Front PanelSelector Knob for Summer/Winter/Flue Analysis Modes Initial Start-up Operational Adjustments Checks to be run before initial start-up are as followsCirculation Failure Ignition FailureOverheating Draining the System GAS AdjustmentsSafety Shut-off Limescale Build-upMaintenance Changing the Type of GasWiring Diagram for Two Heating Zones MiscellaneousWiring Diagram for Connection to Ariston Unvented Cylinder BlueB023 B023 B023 Cod 99 84 1260 112 B023 Manufacturer Merloni TermoSanitari SpA Italy