4.1Changing the Type of Gas

The boiler can be converted to use either methane (natural) gas (G20) or LPG (G30 - G31) by an Authorised Service Centre.

The operations that must be performed are the following:

1.Replace the jets on the main burner (see table in section 4);

2.Adjust the maximum and minimum thermal capacity values for the boiler (see table in section 4);

3.Replace the gas rating plate;

4.Adjust the maximum thermal power setting;

CATEGORY II2H3+

Methane Gas

Liquid Butane Gas

Liquid Propane Gas

 

G20

G30

G31

 

 

 

 

Recommended Soft-Light Pressure

 

 

 

(mbar)

5-5.5

17 - 18

18 - 19

 

 

 

 

 

 

 

 

5.Adjust the soft-light feature;

6.Adjust the ignition delay feature for the heating system (can be set from 0 to 2 mins.).

5.MAINTENANCE

It is recommended that the following checks be made on the boiler at least once a year:

1 - Check the seals for the water connections; replacement of any faulty seals.

2 - Check the gas seals; replacement of any faulty gas seals.

3 - Visual check of the entire unit.

4 - Visual check of the combustion process and cleaning of the burners if needed.

5 - If called for by check no. 3, dismantling and cleaning of the combustion chamber.

6 - If called for by check no. 4, dismantling and cleaning of the injectors.

7 - Visual check of the primary heat exchanger:

-check for overheating in the blade assembly;

-clean the exhaust fan if needed.

8 - Adjustment of the flow rate of the gas: flow rate for lighting, partial load and full load.

9- Check of the heating safety systems:

-safety device for maximum temperature;

-safety device for maximum pressure.

10- Check of the gas safety systems:

-safety device for lack of gas or flame (detection electrode);

-safety device for gas cock.

11- Check of the electrical connection (make sure it complies with the instructions in the manual).

12- Check of domestic hot water production efficiency (delivery rate and tem- perature)

13- Check of the general performance of the unit.

14- General check of the discharge/ventilation of the combustion by- products.

22

B023

Image 22
Contents Mffi A/27 Mffi Table of Contents General Information General InstructionsTechnical Information MffiMffi A/27 Mffi Overall ViewInstallation Reference Standards Siting the ApplianceOverall Dimensions ClearancesElectrical Connection Mounting the ApplianceGas Connection Pipe Work Safety Valve DischargeWater Connections By-passMains Water Feed Central Heating Flue ConnectionsFilling Terminal Position B023 Coaxial System Room Thermostat Connection Electrical Diagram ColoursB023 Initial Preparation Water Circuit DiagramMffi Commissioning Filling the Heating SystemControl Panel Removing the Front PanelSelector Knob for Summer/Winter/Flue Analysis Modes Initial Start-up Operational Adjustments Checks to be run before initial start-up are as followsCirculation Failure Ignition FailureOverheating Draining the System GAS AdjustmentsSafety Shut-off Limescale Build-upMaintenance Changing the Type of GasWiring Diagram for Two Heating Zones MiscellaneousWiring Diagram for Connection to Ariston Unvented Cylinder BlueB023 B023 B023 Cod 99 84 1260 112 B023 Manufacturer Merloni TermoSanitari SpA Italy