2.10Room Thermostat Connection

5

D

In order to perform this procedure, remove boiler cover as indicated in section 3.2. Then proceed as follows:

1Remove the screws “A” located on the bottom part of the boiler;

2Widen the sides so that the control panel can be rotated.

3Open the cover “B” on the left hand side of the compartment.

4Insert the wire for the connection of the room thermostat into the wire holder “C”, as indicated in photo 3.

1

2

 

A

3

4

C

B

5Remove the grommet “D” shown in photo 5, make a hole in it and pass the room thermostat wire through.

6Remove the link located on the terminal and connect the wire.

7Replace the grommet and the terminal to their original positions, close the cover on the grommet compartment and fasten the wire-clamp “C” in place.

8If a remote time clock is to be fitted, disconnect the integral time clock plug from the P.C.B.

9Using a volt-free switching time clock, connect the switching wires from the time clock following points 1-7 above.

10If using a time clock and room thermostat, these must be connected in series as per points 1-9 above.

Note: Only a two-wire type room thermostat can be used.

6

7

C

14

B023

Image 14
Contents Mffi A/27 Mffi Table of Contents General Information General InstructionsTechnical Information MffiMffi A/27 Mffi Overall ViewInstallation Reference Standards Siting the ApplianceOverall Dimensions ClearancesGas Connection Mounting the ApplianceElectrical Connection Pipe Work Safety Valve DischargeWater Connections By-passFilling Flue ConnectionsMains Water Feed Central Heating Terminal Position B023 Coaxial System Room Thermostat Connection Electrical Diagram ColoursB023 Initial Preparation Water Circuit DiagramMffi Commissioning Filling the Heating SystemSelector Knob for Summer/Winter/Flue Analysis Modes Removing the Front PanelControl Panel Initial Start-up Operational Adjustments Checks to be run before initial start-up are as followsOverheating Ignition FailureCirculation Failure Draining the System GAS AdjustmentsSafety Shut-off Limescale Build-upMaintenance Changing the Type of GasWiring Diagram for Two Heating Zones MiscellaneousWiring Diagram for Connection to Ariston Unvented Cylinder BlueB023 B023 B023 Cod 99 84 1260 112 B023 Manufacturer Merloni TermoSanitari SpA Italy