Ariston 41-116-07 GAS Adjustments, Methane Gas G20, Liquid Butane Gas Liquid Propane Gas G30 G31

Page 21

5.GAS ADJUSTMENTS

CATEGORY II2H3+

Lower Wobbe Index (15°C;1013mbar)

MJ/m3h

Nominal Delivery Pressure

mbar

Minimum Delivery Pressure

mbar

21 RFFI

 

Main Burner: n. 12 jets (ø )

mm

Consumption (15°C; 1013mbar)

m3/h

Consumption (15°C; 1013mbar)

Kg/h

Gas Burner Pressure:

 

max - min

mbar

28 RFFI

 

Main Burner: n. 14 jets (ø )

 

Consumption (15°C; 1013mbar)

m3/h

Consumption (15°C; 1013mbar)

Kg/h

Gas Burner Pressure:

 

max - min

mbar

Methane Gas

G20

45.67

20

17

1.30

2.4- 1.05

----

8.5- 1.7

1.30

3.15-1.26

----

11.0- 1.6

 

 

TABLE 5.1

Liquid Butane Gas

 

Liquid Propane Gas

 

G30

 

G31

80.58

 

80.58

29

 

37

20

 

25

0.77

 

0.77

----

 

----

1.78 - 0.78

 

1.76 - 0.77

27.5 - 6.2

 

37.4 - 8.0

0.77

 

0.77

----

 

----

1.78 - 0.78

 

1.76 - 0.77

27.7 - 4.6

 

35.5 - 6.0

 

 

 

[1 mbar = 10,197 mmc.a.]

5.1CHANGING THE TYPE OF GAS

The outlet pressure of the gas cock is obtained by completely loosening the screw on the solenoid. The maximum pressure of the gas to the burner will be equal to the nominal delivery pressure minus the head loss within the gas valve.

The boiler can be converted to use either methane (natural) gas (G20) or LPG (G30 - G31) by an Authorised Service Centre.

The operations that must be performed are the following:

1.Replace the jets on the main burner (see table in section 5);

2.Adjust the maximum and minimum thermal capacity values for the boiler (see table in section 5);

3.Replace the gas rating plate;

4.Adjust the maximum thermal power setting;

5.Adjust the soft-light feature (open the cover of the regulation screw on the gas valve (see FIG. 5.1). Rotate clockwise from min. to max. as per installation requirements).

FIG. 5.1

VG002Ab

21

Image 21
Contents Installation Instructions Type C Boilers Table of Contents General Information Flue connector Installation Overall Dimensions Supply must be fused at 3 a Residual Head of the Boiler Tonbridge Morley RoadKent TN9 1RA 60/100 mm80 mm Type Exhaust Restrictor Maximum Risk of Condensation FormingExtension Piping not insulated Piping insulated SystemsRoom Thermostat Connection A11 Overheat Thermostat GAS and Water Circuits H.W. Storage Cylinder Model Domestic HOT Water Priority KIT Commissioning Control Panel Combustion Analysis Turn off the boiler GAS Adjustments Methane Gas G20Liquid Butane Gas Liquid Propane Gas G30 G31 Maintenance Page Technical Service Hot Line 01494 Technical InformationManufacturer Merloni TermoSanitari SpA Italy Servicing Instructions Type C Boilers Fault Finding Removing the front panel Servicing InstructionsRemoving the side panels Removing the sealed chamber front coverRemoving the combustion cover Removing the burner and jetsRemoving the electrodes Removing the main heat exchanger Removing the fan Removing the air pressure switchSetting the minimum and the maximum power of the boiler Setting the gas pressuresGas escaping with an approved soap and water solution Setting pressure for soft ignitionRegulating the heating power for Natural gas G20 Regulating the heating power for Butane gas G30Regulating the heating power for Propane gas G31 Removing the gas valve Removing the spark generatorRemoving the pump pressure switch Removing the safety valveRemoving the automatic air vent 1. Unscrew valve top Z FIG Removing the pump Removing the expansion vessel Removing the pressure gaugeRemoving the overheat thermostat Removing the frost thermostatRemoving the regulation thermostat Checking the fuse Removing the P.C.B.sO1O1 P1 P1 Finding diagrams described in this chapter Fault FindingYES Mbar Electrical DiagramsSF008A MicroSYSTEM 21/28 Rffi Ariston B063 Technical Service Hot Line 01494 23 99 84 1550