Ariston 41-116-07 installation instructions Turn off the boiler

Page 20

4.6FUME DISCHARGE MONITORING

In the boiler, it is possible to monitor the correct operation of the flue exhaust/air intake, checking for a loss of general pressure in the system. Through the use of a differential manometer connected to the test points of the combustion chamber, it is possible to detect the P of operation of the air pressure switch.

The value detected should not be less than 0.55 mbar under conditions of maximum thermal power in order for the boiler to function properly and without interruption.

FIG. 4.3

4.7

BOILER SAFETY SYSTEMS

The boiler is fitted with the following devices (see section 4.2 for references).

 

 

1 -

IGNITION FAILURE:

 

 

 

This indicates ignition failure when a flame is not detected within 7

 

 

 

seconds of starting an ignition sequence. The L.E.D. “F” will illuminate

 

 

 

to signal the shutdown status.

 

 

 

The system can be reset by pressing and releasing the button “E” after

 

 

 

checking to make sure that the gas cock is open.

 

 

2 -

INSUFFICIENT SYSTEM PRESSURE:

 

 

 

In the event of insufficient water pressure in the heating system, a

 

 

 

safety device will shutdown the boiler. Check the system pressure on

 

 

 

the pressure gauge “J” and if it is less than 0.4 bar refill the system to

 

 

 

1.5 bar. Once the system pressure is at the correct level the boiler will

 

 

 

ignite automatically.

 

 

3 - OVERHEATING:

 

 

 

This control shuts off the boiler in the case where the primary circuit

 

 

 

reaches a temperature in excess of 105°C.

 

 

 

The red L.E.D. “F” will illuminate to signal this shutdown status.

 

 

 

The system can be reset by waiting a few minutes for the primary

 

 

 

exchanger to cool down and then by pressing and releasing the “E

 

 

 

button.

 

 

4.

ANTI-FROST DEVICE:

 

 

 

The boiler is equipped with a device that, in the event of the water

 

 

 

temperature going below 6°C, the burner ignites at the minimum power

 

 

 

until the boiler water reaches a temperature of 16°C.

 

 

 

This device operates only if the boiler is functioning perfectly and:

 

 

 

- the system pressure is sufficient;

 

 

 

- the boiler is powered electrically - L.E.D. “B” illuminated;

 

 

 

- the gas is turned on.

 

 

5 - EXHAUST DISCHARGE ANOMALY SHUTDOWN:

 

 

 

The boiler is fitted with safety devices, which in the event of defective

 

 

 

discharge of exhaust fumes, automatically interrupts the gas supply,

 

 

 

thereby shutting off the boiler.

The shutdown of the boiler is temporary and when the discharge state of exhaust fumes has returned to normal, the boiler automatically turns back on

4.8

DRAINING THE SYSTEM

The heating system must be emptied as follows:

 

 

- Turn off the boiler;

- Attach a hose pipe and open the drain valve;

- Empty the system at the lowest points (where present). When the heating system is unused for an extended period of time, it is recommended that you add antifreeze with an ethylene glycol base to the water in the heating lines and radiators if the ambient temperature drops below 0°C during the winter.

This makes repeated draining of the entire system unnecessary.

20

Image 20
Contents Installation Instructions Type C Boilers Table of Contents General Information Flue connector Installation Overall Dimensions Supply must be fused at 3 a Residual Head of the Boiler Morley Road TonbridgeKent TN9 1RA 60/100 mm80 mm Exhaust Restrictor Maximum Risk of Condensation Forming TypeExtension Piping not insulated Piping insulated SystemsRoom Thermostat Connection A11 Overheat Thermostat GAS and Water Circuits H.W. Storage Cylinder Model Commissioning Domestic HOT Water Priority KITControl Panel Combustion Analysis Turn off the boiler Liquid Butane Gas Liquid Propane Gas G30 G31 GAS AdjustmentsMethane Gas G20 Maintenance Page Manufacturer Merloni TermoSanitari SpA Italy Technical Service Hot Line 01494Technical Information Servicing Instructions Type C Boilers Fault Finding Servicing Instructions Removing the front panelRemoving the sealed chamber front cover Removing the side panelsRemoving the electrodes Removing the combustion coverRemoving the burner and jets Removing the main heat exchanger Removing the air pressure switch Removing the fanSetting the gas pressures Setting the minimum and the maximum power of the boilerGas escaping with an approved soap and water solution Setting pressure for soft ignitionRegulating the heating power for Propane gas G31 Regulating the heating power for Natural gas G20Regulating the heating power for Butane gas G30 Removing the spark generator Removing the gas valveRemoving the automatic air vent 1. Unscrew valve top Z FIG Removing the pump pressure switchRemoving the safety valve Removing the pump Removing the pressure gauge Removing the expansion vesselRemoving the regulation thermostat Removing the overheat thermostatRemoving the frost thermostat O1O1 P1 P1 Checking the fuseRemoving the P.C.B.s Fault Finding Finding diagrams described in this chapterYES Mbar Diagrams ElectricalSF008A MicroSYSTEM 21/28 Rffi Ariston B063 Technical Service Hot Line 01494 23 99 84 1550

41-116-07 specifications

The Ariston 41-116-07 is a highly efficient and reliable appliance designed to meet the diverse needs of modern households. This model is primarily recognized for its robust build quality and energy-efficient performance, making it a popular choice among consumers looking for sustainability without sacrificing functionality.

One of the standout features of the Ariston 41-116-07 is its advanced heating technology. The appliance utilizes a high-performance heating element that ensures rapid heating and consistent temperature control. This means that users can enjoy hot water and comfort quickly, with minimal wait times. The innovative design also includes insulation that helps to maintain heat, reducing energy consumption and lowering utility bills.

User convenience is another hallmark of the Ariston 41-116-07. The appliance comes equipped with an intuitive control panel that allows for easy operation. The simple interface helps users to set their desired temperature and monitor performance effortlessly. Additionally, the model includes programmable settings, enabling users to schedule heating cycles according to their lifestyles, further enhancing energy savings.

Safety features are paramount in the design of the Ariston 41-116-07. The appliance includes a range of safety mechanisms such as automatic shut-off, preventing overheating and potential hazards. The built-in sensors continuously monitor the system's operation, ensuring optimal performance while safeguarding the user's home and family.

In terms of installation, the Ariston 41-116-07 excels with its compact size and flexible mounting options. It can be conveniently installed in various locations, whether in a utility room, kitchen, or bathroom, without requiring extensive modifications. This flexibility is ideal for homes with limited space or unique layouts.

Maintenance is also simplified with the Ariston 41-116-07. The appliance is designed with easy-access components, making routine maintenance or troubleshooting straightforward for the average user. This ease of care further contributes to its reputation for reliability, ensuring that the unit operates efficiently over its lifespan.

In summary, the Ariston 41-116-07 stands out for its energy efficiency, user-friendly features, safety mechanisms, versatile installation options, and low maintenance requirements. These characteristics make it a valuable addition to any modern home, catering to the needs of consumers seeking both performance and convenience in their appliances. Whether for daily use or occasional needs, the Ariston 41-116-07 guarantees satisfaction through its innovative technologies and thoughtful design.