INSTALLATION

Mantel Clearances Floor Clearances

INSTALLATION

Continued

MANTEL CLEARANCES

In addition to meeting noncombustible material clearances, you must also meet required clearances between fireplace opening and mantel shelf. If you do not meet the clearances listed below, you will need a hood.

Determining Minimum Mantel Clearance

If you meet minimum clearance between mantel shelf and top of fireplace opening, a hood is not required (see Figure 6).

Determining Minimum Mantel Clearance When Using a Hood

If minimum clearances in Figure 6 are not met, you must have a hood. When using a hood there are still certain minimum mantel clearances required. Follow minimum clearances shown in Fig- ure 7 when using hood.

Mantel Shelf

10"

8"

6"

2 1/2"

Minimum Non-

 

 

(A)

 

 

 

 

 

 

 

 

 

 

 

 

Combustible

 

 

 

 

 

 

 

Material

12"

18"

20"

22"

 

 

 

 

 

 

 

 

 

 

Minimum Non-

Distances to

Combustible

Underside of

Material Height

Mantel

Underside of

Mantel Shelf

All minimum distances are in inches

Log Set

24" All Models

Top of Fireplace

Opening

NOTICE: Surface temperatures of adjacent walls and mantels become hot during operation. Walls and mantels above the firebox may become hot to the touch. If installed properly, these temperatures meet the requirement of the national product standard. Follow all minimum clearances shown in this manual.

NOTICE: If your installation does not meet the minimum clearances shown, you must do one of the following:

operate the logs only with the flue damper open

raise the mantel to an acceptable height

remove the mantel

FLOOR CLEARANCES

A.If installing appliance on the floor level, you must maintain the minimum distance of 14" to combustibles (see Figure 8).

B.If combustible materials are less than 14" to the fireplace, you must install appliance at least 5" above the combustible floor- ing (see Figure 9).

Figure 6 - Minimum Mantel Clearances Without Using Hood

 

12"

 

Mantel Shelf

 

 

 

 

 

 

 

 

 

 

 

Underside of

 

10"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mantel Shelf

 

 

 

 

 

 

 

 

 

 

8"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 1/2"

 

 

 

 

 

 

All minimum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

distances are

Minimum Non-

 

 

 

 

 

 

 

 

in inches

 

 

 

 

 

 

 

 

 

Combustible

 

 

 

 

 

 

 

 

 

Material

 

 

8"

 

12"

15"

18"

20"

 

 

 

 

 

 

Min.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Top of Fireplace

Opening

Hood

Distances to

(GA6050, GA6052,

Underside of

or GA6053)

Mantel

 

Figure 7 - Minimum Mantel Clearances When Using Hood

 

Combustible

 

 

14"

Material

 

 

 

Hearth

 

Min.

 

Combustible

 

 

 

 

 

 

Material

Noncombustible Material

 

5"

 

 

Figure 8 - Minimum Fireplace

Figure 9 - Minimum Fireplace

Clearances If Installed at Floor

Clearances Above

 

Level

 

Combustible Flooring

For..com

110021-01A

Image 10
Contents OWNER’S Operation and Installation Manual What to do if YOU Smell GASTable of Contents Safety InformationSafety Information Local Codes Optional Remote Control AccessoriesProduct Identification UnpackingProduct Features AIR for Combustion and VentilationDetermining FRESH-AIR Flow for Heater Location Determining if You Have a Confined or Unconfined SpaceVentilation Air From Inside Building Ventilation AIRVentilation Air From Outdoors Installation and Clearances for VENT-FREE Operation InstallationCheck GAS Type Minimum Noncombustible Material Clearances See Between 8Floor Clearances Determining Minimum Mantel Clearance When Using a HoodMantel Clearances Determining Minimum Mantel ClearanceInstallation Items Needed Installing Damper Clamp Accessory for Vented OperationInstalling Heater Base Assembly Remote-Ready Models OnlyConnecting to GAS Supply Attaching Extension Plates to Base Assembly 30 Model OnlyExternal Regulator With Vent Pointing Down Pressure Testing Heater Gas Connections Pressure Testing gas Supply Piping systemChecking GAS Connections Installing Logs Installing Log #1 Ember Bed Model CSG3924NR ShownInstalling Log #2 Right and Log #3 Left Model VRL30NR Shown Adding Lava Rock Attaching Grate to Base AssemblyOperating Heater Lighting InstructionsShutting Off Heater To Turn OFF GAS to ApplianceShutting Off Burners Only pilot stays lit REMOTE-READY Models For Your Safety Read Before Lighting Manual Lighting ProcedureThermostat Control Operation Control Knob Rear Burner Ghrc Series Operation Optional Remote OperationThermostat Control Operation Ghrcta Series OperationPilot Flame Pattern Inspecting BurnersBurner Flame Patterns Cleaning Burner Injector Holders and Pilot AIR Inlet Holes Cleaning MaintenanceLogs Troubleshooting Observed Problem Possible Cause RemedyRefer to Air for Combustion and Venti Gas leak. See Warning statement Optional Positioning of Thermostat Sensing Bulb Important Do not crimp capillaryService Hints SpecificationsWiring Diagram Technical ServiceIllustrated Parts Breakdown For more Visit www ComTHERMOSTAT-CONTROLLED VRL24NT, VRL24PT VRL30NT, VRL30PT Parts List THERMOSTAT-CONTROLLEDREMOTE-READY VRL24NR, VRL24PR VRL30NR, VRL30PR CSG3924NR, CSG3924PR CTB3924NR, CTB3924PRREMOTE-READY Replacement Parts AccessoriesOwners Registration Form Postage Required 110021-01A Not a UPC

VRL30NT, VRL24PT, CSG3924NT, VRL30PT, VRL24NT specifications

Desa VRL24NR, VRL24PR, VRL30NR, VRL30PR, CSG3924NR, CSG3924PR, CTB3924NR, CTB3924PR, VRL24NT, VRL24PT, VRL30NT, VRL30PT, CSG3924NT, CSG3924PT, CTB3924NT, and CTB3924PT are a series of innovative heating solutions that cater to various residential and commercial needs. These models are designed to provide efficient, reliable, and aesthetically pleasing heating options.

One of the key features across these models is their advanced heating technology. They utilize cutting-edge infrared heating systems that ensure consistent and effective warmth. This technology not only heats up spaces quickly but also provides energy savings compared to traditional heating methods. Additionally, many models are equipped with programmable thermostats allowing users to set their desired temperature and schedule, enhancing convenience and energy efficiency.

Another hallmark of these models is their versatility in installation. The options for both vent-free and vented designs provide flexibility for various environments. Users can choose vented models for additional safety and air quality control, or opt for vent-free units that are easier to install in areas without existing ventilation systems. The range of configurations helps accommodate different space sizes and heating requirements.

In terms of design, the Desa heating solutions are crafted with aesthetics in mind. Many models feature sleek exteriors and elegant finishes, making them suitable for integration into modern or traditional interior designs. This commitment to design ensures that users do not have to sacrifice style for functionality.

Durability and reliability are emphasized throughout the line. Constructed with high-quality materials, these models are built to withstand the test of time and can function effectively under varying environmental conditions. Users can have peace of mind with warranties and support from the manufacturer.

Safety is another crucial aspect of these heating solutions. Each model is designed with safety features like automatic shut-off systems, making them safe for family use even in occupied living spaces.

In summary, the Desa VRL and CSG series offers a broad selection of heating solutions characterized by advanced infrared technology, versatile installation options, stylish designs, and robust safety measures. Whether for residential or commercial purposes, these models are engineered to meet diverse heating needs efficiently and reliably.