Heat & Glo LifeStyle GEM42 The Gas Supply Line, Gas Pressure Requirements, Natural Gas, Propane

Page 23
Step 7. The Gas Supply Line

Step 7. The Gas Supply Line

NOTE: Have the gas supply line installed in accordance with local building codes by a qualified installer ap- proved and/or licensed as required by the locality. (In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fitter).

NOTE: Before the first firing of the fireplace, the gas supply line should be purged of any trapped air.

NOTE: Consult local building codes to properly size the gas supply line leading to the 1/2 inch (13mm) hook-up at the unit.

This gas fireplace is designed to accept a 1/2 inch

(13 mm) gas supply line. To install the gas supply line:

A listed (and Commonwealth of Massachusetts approved) 1/2 inch (13mm) tee-handle manual shut-off valve and a listed flexible gas connector are connected to the 1/2 inch (13mm) inlet of the control valve. NOTE: If substi- tuting for these components, please consult local codes for compliance.

Locate the gas line access hole in the outer casing of the fireplace.

The gas line may be run from either side of the fireplace provided the hole in the outer wrap does not exceed 2 1/2” in diameter and it does not penetrate the actual firebox.

The gap between the supply piping and gas access hole can be plugged with non-combustible insulation to pre- vent cold air infiltration.

Open the fireplace lower grille, insert the gas supply line through the gas line hole, and connect it to the shut-off valve.

When attaching the pipe, support the control so that the lines are not bent or torn.

After the gas line installation is complete, all connec- tions must be tightened and checked for leaks with a commercially-available, non-corrosive leak check solu- tion. Be sure to rinse off all leak check solution following testing.

!Warning: DO NOT USE AN OPEN FLAME TO CHECK FOR GAS LEAKS.

At the gas line access hole, use insulation to re-pack the space around the gas pipe.

Insert insulation from the outside of the fireplace and pack the insulation tightly to totally seal between the pipe and the outer casing.

Step 8. Gas Pressure Requirements

Pressure requirements for Heat & Glo gas fireplaces are shown in the table below.

Pressure

Natural Gas

Propane

Minimum

5.0 inches

11.0 inches

Inlet Pressure

w.c.

w.c.

Maximum Inlet

14.0 inches

14.0 inches

Gas Pressure

w.c.

w.c.

Manifold

3.5 inches

10.0 inches

Pressure

w.c.

w.c.

 

 

 

A one-eighth (1/8) inch (3 mm) N.P.T. plugged tapping is provided on the inlet and outlet side of the gas control for a test gauge connection to measure the manifold pressure. Use a small flat blade screwdriver to crack open the screw in the center of the tap. Position a rubber hose over the tap to obtain the pressure reading.

The fireplace and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of the system at test pressures in excess of one-half (1/2) psig (3.5 kPa).

The fireplace must be isolated from the gas supply piping system by closing its individual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than one-half (1/2) psig (3.5 kPa).

Heat & Glo • GEM42 • 371-900 Rev. N • 2/05

23

Image 23
Contents Underwriters Laboratories Listed ModelInstallers Guide GEM42DO NOT USE this appliance if any part has been SAFETY AND WARNING INFORMATIONThis gas fireplace and vent assembly MUST be READ and UNDERSTAND all instructions carefullySection 3 Installing the Fireplace TABLE OF CONTENTSSafety and Warning Information Service Parts ListsNG, LP Exploded Parts Diagram Service PartsGEM42 5 Log set assemblyACCESSORIES / ACCESSOIRES Service Parts List / Liste des pièces de rechangeGEM42 Intermittent Pilot Ignition Valve AssemblyAppliance Certification Installation CodesHigh Altitude Installations 1Approvals and CodesANY SUCH ACTION MAY POSSIBLY CAUSE A FIRE HAZARD Pre-install Preparation2Getting Started Introducing the Heat & Glo Gas FireplacesHeat & Glo GEM42 371-900 Rev. N 2/05 Figure 1. Diagram of the GEM42Fireplace Dimensions, Locations 3Installing the FireplaceConstructing the Fireplace Chase Step 1. Locating the Fireplace47-3/4” Step 2. Framing the FireplaceFigure 3. Framing Dimensions 47-1/2”DVP90ST NOTE PIPES OVERLAP 1-1/4 INCHES AT EACH JOINTIdentifying Vent Components Step 3. Installing the Vent SystemA. Vent System Approvals TEMS OR COMPONENTS MAY BE USEDVERTICAL VENTING V FT 40 MAX. 12.4 M Pilot Shield AdjustmentSTRAIGHT UP Flue Restrictor InstructionsVENTING WITH ONE 1 90 ELBOW VENTING WITHTWO 2 90 o ELBOWSH + H 1 FT V FTH FT VENTING WITH THREE 3 90 ELBOWS1. Attach the First Vent Component to the Starting Collars B. Installing Vent Components3. Install Support Brackets Venting Out the Top VentFigure 16. Heat Shield, Interior & Exterior Firestops 4. Install FirestopsCut a 10-inch by 12-inch 254mm X 305mm hole through the wall Figure 15. 10 x 12 Hole and Vent PipePOSITIONED SO THAT THE ARROW IS POINT- ING UP C. Vent TerminationAttic Firestop WARNING THE TERMINATION CAP MUST BEmeter/regulator assembly within = AREA WHERE TERMINAL IS NOT PERMITTEDelectrical service not to be installed above a gasFigure 23. Proper Positioning Step 4. Positioning, Leveling and Securing the FireplaceWARNING MAJOR U.S. BUILDING CODES SPECIFY MINIMUM CHIMNEY AND/OR Figure 22. Minimum Height from Roof to Lowest Discharge OpeningStep 6 The Gas Control System Step 5. Installing the Optional Heat-Out or Heat-Zone KitsHeat-Out Kit Heat-Zone KitNatural Gas Step 7. The Gas Supply LineStep 8. Gas Pressure Requirements PressureOperation with Battery Back-up Step 9. Wiring the FireplaceFigure 26. Intermittent Pilot Ignition IPI Wiring Diagram Intermittent Pilot Ignition IPI Wiring 3 Volt TransformerFINISH WALL MATERIAL Step 10. FinishingFigure 27. Fan Wiring Diagram WARNING WHEN FINISHING THE FIREPLACEFacing Thickness from 3/4” to 1-1/4” IMPORTANT INSTALLATION NOTEFacing Requirements Figure 31. Facing Template DimensionsGlass Specifications GEM42 CERAMIC Step 11. Installing Trim, Logs and Ember MaterialInstalling the Trim Figure 34. Glass AssemblyDouble-check for faulty components After the InstallationStep 12. Before Lighting the Fireplace Step 13. Lighting the FireplaceCleaning Glass Door Fireplace Maintenance4Maintaining and Servicing Your Fireplace Cleaning Flame Sensor Rod IPI Systems Frequency Annually