Bryant 581B manual Guide Specifications

Page 61

GUIDE SPECIFICATIONS (cont)

I. Controls and Safeties:

1. Unit Controls:

Unit shall be complete with self-contained low- voltage control circuit protected by a fuse on the 24-v transformer side.

2.Safeties:

a.Unit shall incorporate a solid-state compressor protector which provides anti-cycle reset capabil- ity at the space thermostat, should any of the following standard safety devices trip and shut off compressor.

1)Compressor overtemperature, overcurrent.

2)Loss-of-charge/low-pressure switch.

3)Freeze-protection thermostat, evaporator coil.

4)High-pressure switch.

The lockout protection shall be easily discon- nected at the control board, if necessary.

b.Heating section shall be provided with the follow- ing minimum protections:

1)High-temperature limit switches.

2)Induced draft motor speed sensor.

3)Flame rollout switch.

4)Flame proving controls

J. Operating Characteristics:

f.EconoMi$er shall be equipped with a barometric relief damper with up to 100% of return air (036-

072)or 90% of return air (090-150) relief. The Durablade economizer is equipped with 30% of return-air relief (036-150).

g.Designed to close damper during loss-of-power situations with emergency power supply (Dura- blade economizer) or spring return built into motor (EconoMi$er).

h.Dry bulb outdoor-air thermostat protection shall be provided as standard.

i.Durablade economizer is a guillotine-style damper, and the EconoMi$er is a parallel blade design.

3.50% Manual Outdoor-Air Damper:

Manual damper package shall consist of damper, birdscreen, and rainhood which can be preset to admit up to 50% outdoor air for year-round ventilation.

4. 25% Manual Outdoor-Air Damper:

Manual damper package shall consist of damper, birdscreen, and rainhood which can be preset to admit up to 25% outdoor air for year-round ventilation.

5. 100% Two-Position Damper:

1.Unit shall be capable of starting and running at 125 F ambient outdoor temperature, meeting maximum load criteria of ARI Standard 210/240 or 360 at ±10% voltage.

2.Compressor with standard controls shall be capable of operation down to 25 F ambient outdoor temperature.

K.Electrical Requirements:

All unit power wiring shall enter unit cabinet at a single factory-predrilled location.

L.Motors:

1.Compressor motors shall be cooled by refrigerant passing through motor windings and shall have line break thermal and current overload protection.

2.Indoor blower (evaporator-fan) motor shall have per- manently lubricated bearings and inherent automatic-reset thermal overload protection.

3.Totally enclosed condenser-fan motor shall have permanently lubricated bearings and inherent automatic-reset thermal overload protection.

4.Induced-draft motor shall have permanently lubri- cated, sealed bearings and inherent automatic reset thermal overload protection.

M.Special Features:

Certain features are not applicable when the features designated by * are specified. For assistance in amending the specifications, contact your local sales office.

1.Roof Curbs:

a.Formed galvanized steel with wood nailer strip and capable of supporting entire unit weight.

b.Allows for installing and securing ductwork to curb prior to mounting unit on the curb.

*2. Integrated Economizers:

a. Integrated integral-modulating type capable of simultaneous economizer and compressor operation.

b. Includes all hardware and controls to provide cooling with outdoor air.

c. Equipped with low-leakage dampers not to exceed 3% leakage, at 1 in. wg pressure differen- tial (Durablade economizer).

d.Capable of introducing up to 100% outdoor air in both minimum and fully open positions.

e.Equipped with a gravity relief sliding plate damper (Durablade economizer). Damper shall close upon unit shutoff.

a.Two-position damper package shall include single blade damper and motor. Admits up to 100% out- door air.

b.Damper shall close upon indoor (evaporator) fan shutoff.

c.Designed to close damper during loss of power situations.

d.Equipped with 15% barometric relief damper.

6.25% Two-Position Damper:

a.Two-position damper package shall include single blade damper and motor. Admits up to 25% out- door air.

b.Damper shall close upon indoor (evaporator) fan shutoff.

*7. Solid-State Enthalpy Control:

a.For use with variable sliding economizer package only.

b.Capable of sensing outdoor-air enthalpy content (temperature and humidity) and controlling econ- omizer cut-in point to have minimum heat content air passing over the evaporator coil for most effi- cient system operation.

*8. Differential Enthalpy Sensor:

a.For use with economizer only.

b.Capable of comparing enthalpy content (tempera- ture and humidity) of outdoor and indoor air and controlling economizer cut-in point at the most economical level.

9.Outdoor-Air Enthalpy Sensor:

The outdoor-air enthalpy sensor shall be used with the EconoMi$er device to provide single enthalpy control. When used in conjunction with a return-air enthalpy sensor, the EconoMi$er device will provide differential enthalpy control. The sensor allows the EconoMi$er controller to determine if outside air is suitable for free cooling.

10. Return-Air Enthalpy Sensor:

The return-air enthalpy sensor shall be used with the EconoMi$er device. When used in conjunction with an outdoor-air enthalpy sensor, the EconoMi$er device will provide differential enthalpy control.

61

Image 61
Contents Easy Maintenance and Installation FEATURES/BENEFITSUnit 581B036-072 Unit 581B090-150FEATURES/BENEFITS Table of Contents Compressors and Safety Switches are Easily Accessible for ServiceabilityModel Number Nomenclature Indoor AIR Quality IAQHeating Capacities and Efficiencies ARI* CapacitiesLOW Ambient Controls Options and AccessoriesTime Guard II Control Liquid Propane Conversion KITOptions and Accessories Coil Guard Grille Hail Guard Accusensor II Enthalpy ControlBryant Commercial Programmable Thermostat Bryant Light Commercial ThermidistatHi-Static Physical Data060N††† Physical Data090N††† 120N†††090 102 120 150 Nominal Capacity tons LOSS-OF-CHARGE LOW-PRESSURE 581B036-072 Base Unit Dimensions581B090-150 Base Unit DimensionsAccessory Dimensions 581B036-072 Connector ALT Drain PKG. Accy GAS Accessory Dimensions 581B090-150Control CRRFCURB003A00II Select Unit Based on Required Cooling Capacity Selection Procedure With 581B048 ExampleDetermine NET Cooling Capacity Cooling Capacities Performance DataCooling Capacities Performance Data581B090 71/2 Tons 581B120 10 Tons Temp F Cooling CAPACITIES, Units with Perfect Humidity Option Cooling CAPACITIES, Units with Perfect Humidity Option 2250/0.10 3000/0.11 3750/0.14 Condenser 134.3 581B036 3 Tons Standard Motor Airflow FAN Performance Vertical Discharge Units581B036 3 Tons HIGH-STATIC Motor Airflow 581B048 4 Tons Standard Motor Airflow FAN Performance Vertical Discharge Units581B048 4 Tons HIGH-STATIC Motor Airflow 581B060 5 Tons Standard Motor THREE-PHASE Units Airflow 581B060 5 Tons Standard Motor SINGLE-PHASE Units Airflow581B060 5 Tons HIGH-STATIC Motor 581B072 6 Tons HIGH-STATIC Motor 581B072 6 Tons Standard Motor Airflow581B090 71/2 Tons HIGH-STATIC Motor Airflow 581B090 71/2 Tons Standard Motor581B102 81/2 Tons HIGH-STATIC Motor Airflow 581B120 10 Tons Standard and HIGH-STATIC Motor Airflow FAN Performance Horizontal Discharge Units FAN Performance Horizontal Discharge Units 581B060 5 Tons HIGH-STATIC Motor Airflow 581B060 5 Tons Standard Motor 3-PHASE Units Airflow1900 982 1084 1160 1223 Bhp Rpm 1800 885 942 10472000 1022 1121 1188 1264 2100 1063 1140 1196 1272581B090 71/2 Tons HIGH-STATIC Motor Airflow 2600 557 634 698 759 787 816 Bhp Rpm 2550 627 692 754 783 8122700 573 648 711 770 798 827 2800 588 662 723 782 809 8373200 519 680 741 818 3100 500 669 731 8083300 537 692 751 828 3400 561 704 761EVAPORATOR-FAN Motor Efficiency Outdoor Sound Power Total UnitFiop Perfect Humidity Dehumidification 581B FAN RPM AT Motor Pulley Setting with HIGH-STATIC Motor 581B FAN RPM AT Motor Pulley Setting with Standard MotorEVAPORATOR-FAN Motor Data Standard Motor Operating Watts EVAPORATOR-FAN Motor Data HIGH-STATIC MotorsEconoMi$er Outdoor-Air Leakage EconoMi$er Barometric Relief Damper CharacteristicsEconoMi$er Return-Air Pressure Drop Altitude Derating Factor Altitude Compensation581B036-150 OFM Electrical DataSupply FAN MotorRLA LRA FLA MCA MOCP† Electrical DataNominal Voltage Combustion Power Minimum Unit Compressor RLA LRA Application Data Maximum Operating OUTDOOR-AIR TemperatureApplications Application Data Perfect Humidity Dehumidification Option Pressure Enthalpy Curve Psychrometric Chart 581B072 Shown Vertical Discharge Typical Piping and WiringHorizontal Discharge Typical Wiring Schematic Typical Wiring Schematic OFC 581B090-150 Typical Wiring SchematicTran Operating Sequence for 581B036-072 Units ControlsOperating Sequence for 581B090-150 Units Operating Sequence for 581B036-150 Size Units ControlsPart 1 General Guide SpecificationsPart 2 Products Guide Specifications Light Commercial Thermidistat Page Specifications Subject to Change Without Notice
Related manuals
Manual 52 pages 16.87 Kb Manual 40 pages 47.12 Kb

581B specifications

The Bryant 581B is an innovative and highly efficient gas furnace that stands out in the HVAC market for its remarkable performance, reliability, and advanced features. Designed to provide optimal heating comfort, the Bryant 581B is perfect for homeowners seeking both quality and energy efficiency.

One of the main features of the Bryant 581B is its impressive Annual Fuel Utilization Efficiency (AFUE) rating. With an AFUE rating of up to 80%, this gas furnace maximizes energy usage, ensuring that a significant portion of the fuel is converted into heat for your home. This efficiency not only translates into lower energy bills but also reduces the carbon footprint, making it an environmentally friendly choice.

The furnace is equipped with a multi-speed blower motor that enhances comfort by providing consistent airflow throughout the home. This technology adjusts to different heating demands, ensuring that every room reaches the desired temperature without the discomfort of hot or cold spots. The quiet operation of the blower motor also adds to the overall comfort, creating a peaceful home environment.

Another notable characteristic of the Bryant 581B is its durable construction. It features a robust heat exchanger built from high-quality materials, designed to withstand the rigors of daily use. The compact design of the furnace allows it to fit seamlessly into various spaces, making it an ideal choice for both new installations and replacement projects.

The Bryant 581B also comes with advanced safety features, including a self-diagnostic control board that monitors the system's performance. This feature allows for easy troubleshooting and maintenance, prolonging the life of the furnace. Additionally, the furnace is equipped with an induced draft blower that enhances venting efficiency and safety by ensuring that combustion gases are safely expelled from the home.

For homeowners looking for enhanced control, the Bryant 581B is compatible with a range of smart thermostats, providing the ability to monitor and adjust heating settings remotely. This integration with smart technology ensures that homeowners can maintain their desired comfort levels while maximizing efficiency.

In conclusion, the Bryant 581B gas furnace is a top-tier option that combines efficiency, durability, and modern technology. With its high AFUE rating, multi-speed blower, and advanced safety features, it promises to deliver unparalleled comfort and peace of mind for years to come. Whether for a new build or an upgrade, the Bryant 581B is an investment that pays off in both comfort and savings.