GUIDE SPECIFICATIONS (cont)

11. Return-Air Temperature Sensor:

The return-air temperature sensor shall be used with the EconoMi$er device. When used in conjunction with an outdoor-air temperature sensor, the EconoMi$er device will provide differential tempera- ture control.

24. Power Exhaust for Accessory EconoMi$er:

Two two-stage power exhausts shall be used in con- junction with EconoMi$er to provide the system with the capability to exhaust up to 100% of return air. The power exhaust is a field-installed accessory for vertical and horizontal applications.

12. Indoor-Air Quality (CO2) Sensor:

Shall have the ability to provide demand ventilation indoor-air quality (IAQ) control through the EconoMi$er with an IAQ sensor.

The IAQ sensor shall be available in duct mount, wall mount and wall mount with LED display. The set point shall have adjustment capability.

*13. Low Ambient Control Packages:

Each package consists of solid-state control and condenser-coil temperature sensor to maintain con- densing temperature between 90 F and 110 F at out- door ambient temperatures down to –20 F by condenser-fan speed modulation or condenser-fan cycling.

*14. Thermostat and Subbase:

Provides staged cooling and heating automatic (or manual) changeover, fan control, and indicator light.

15. Thru-The-Bottom Service Connection:

Kit shall provide connectors to permit electrical con- nections to be brought to the unit through the basepan.

16. Condenser Coil Hail Guard Assembly:

Hail guard shall protect against damage from hail and flying debris.

17. Condenser Coil Guard Grille:

The grille protects the condenser coil from damage by large objects without increasing unit clearances.

18. Compressor Cycle Delay:

Unit shall be prevented from restarting for a mini- mum of 5 min. after shutdown.

19. Fan/Filter Status Switch:

Provides status of evaporator fan (ON/OFF) or indoor-air filter (CLEAN/DIRTY). Status shall be dis- played over communication bus when used with direct digital controls or with an indicator light at the thermostat.

20. Unit-Mounted, Non-Fused Disconnect Switch:

Shall be factory-installed, internally-mounted, NEC and UL approved non-fused switch shall provide unit power shutoff. Shall be accessible from outside the unit and shall provide power off lockout capability.

21. Convenience Outlet:

Shall be factory-installed and internally-mounted with easily accessible 115-v female receptacle. Shall include 15 amp GFI receptacle with independent fuse protection. Voltage required to operate con- venience outlet shall be provided by a factory- installed step-down transformer. Shall be accessible from outside the unit.

22. High-Static Motor and Drive:

High-static motor and drive shall be factory-installed to provide additional performance range.

23. EconoMi$er and Power Exhaust:

Package shall provide control of internal building pressure. The system shall exhaust up to 100% of return air.

25. Flue Hood Protector Assembly:

Provides protection from the hot sides of the gas flue hood.

26. Liquid Propane Kit:

Package shall contain all the necessary hardware and instructions to convert a standard natural gas unit for use with liquefied propane.

27. NOx Reduction Unit:

Unit shall have reduced nitrous oxide (NOx) emis- sions to meet the California Air Quality Management NOx requirement of 40 nanograms/joule or less on 036-060 sizes.

28. Flue Discharge Deflector:

Package shall contain single-piece deflector and hardware to exhaust the flue discharge up and away from unit. The flue discharge deflector shall allow minimum flue side clearances to combustibles to be reduced to 18 inches.

29. Dehumidification Package:

The dehumidification package is a factory-installed option that provides increased dehumidification by further subcooling the hot liquid refrigerant leaving the condenser coil. The package consists of a sub- cooling coil located on the leaving-air side of the evaporator coil. The location of this coil in the indoor airstream greatly enhances the latent capacity of the units.

The package shall be equipped with crankcase heater(s), low pressure switch(es), and thermostatic expansion valve(s) (TXV). Low pressure switch(es) prevents evaporator coil freeze up and TXV(s) assure a positive superheat condition. If the opera- tion of the subcooling coil is controlled by a field- installed, wall-mounted humidistat or LC Thermidis- tat, the dehumidification circuit will then operate only when needed. Optional field connections for the humidistat are made in the low voltage compartment of the unit control box.

30. Light Commercial Thermidistat:

Field-installed, wall mounted thermidistat is used to control temperature and activation of Perfect Humidity™ package. The thermidistat can be set for humidity settings from 50% to 90% relative humidity.

31. Electronic Programmable Thermostat:

Capable of using deluxe full-featured electronic ther- mostat. Shall use built-in compressor cycle delay control for both heating and cooling duty.

32. Humidistat:

Field-installed, wall-mounted humidistat is used to control activation of the dehumidification package. The humidistat can be set for humidity levels between 20% and 80% relative humidity.

33. Hinged Panel Option:

Hinged panel option provides hinged access panels for the filter, compressor, evaporator fan, and control box areas. Filter hinged panels permit tool-less entry for changing filters. Each hinged panel is perma- nently attached to the rooftop unit.

62

Image 62
Contents Unit 581B036-072 FEATURES/BENEFITSEasy Maintenance and Installation Unit 581B090-150FEATURES/BENEFITS Table of Contents Model Number Nomenclature ServiceabilityCompressors and Safety Switches are Easily Accessible for Indoor AIR Quality IAQARI* Capacities Heating Capacities and EfficienciesTime Guard II Control Options and AccessoriesLOW Ambient Controls Liquid Propane Conversion KITOptions and Accessories Bryant Commercial Programmable Thermostat Hail Guard Accusensor II Enthalpy ControlCoil Guard Grille Bryant Light Commercial ThermidistatPhysical Data Hi-Static090N††† Physical Data060N††† 120N†††090 102 120 150 Nominal Capacity tons LOSS-OF-CHARGE LOW-PRESSURE Base Unit Dimensions 581B036-072Base Unit Dimensions 581B090-150Accessory Dimensions 581B036-072 Control Accessory Dimensions 581B090-150Connector ALT Drain PKG. Accy GAS CRRFCURB003A00Determine NET Cooling Capacity Selection Procedure With 581B048 ExampleII Select Unit Based on Required Cooling Capacity Performance Data Cooling CapacitiesPerformance Data Cooling Capacities581B090 71/2 Tons 581B120 10 Tons Temp F Cooling CAPACITIES, Units with Perfect Humidity Option Cooling CAPACITIES, Units with Perfect Humidity Option 2250/0.10 3000/0.11 3750/0.14 Condenser 134.3 581B036 3 Tons HIGH-STATIC Motor Airflow FAN Performance Vertical Discharge Units581B036 3 Tons Standard Motor Airflow 581B048 4 Tons HIGH-STATIC Motor Airflow FAN Performance Vertical Discharge Units581B048 4 Tons Standard Motor Airflow 581B060 5 Tons HIGH-STATIC Motor 581B060 5 Tons Standard Motor SINGLE-PHASE Units Airflow581B060 5 Tons Standard Motor THREE-PHASE Units Airflow 581B072 6 Tons Standard Motor Airflow 581B072 6 Tons HIGH-STATIC Motor581B090 71/2 Tons Standard Motor 581B090 71/2 Tons HIGH-STATIC Motor Airflow581B102 81/2 Tons HIGH-STATIC Motor Airflow 581B120 10 Tons Standard and HIGH-STATIC Motor Airflow FAN Performance Horizontal Discharge Units FAN Performance Horizontal Discharge Units 581B060 5 Tons Standard Motor 3-PHASE Units Airflow 581B060 5 Tons HIGH-STATIC Motor Airflow2000 1022 1121 1188 1264 Bhp Rpm 1800 885 942 10471900 982 1084 1160 1223 2100 1063 1140 1196 1272581B090 71/2 Tons HIGH-STATIC Motor Airflow 2700 573 648 711 770 798 827 Bhp Rpm 2550 627 692 754 783 8122600 557 634 698 759 787 816 2800 588 662 723 782 809 8373300 537 692 751 828 3100 500 669 731 8083200 519 680 741 818 3400 561 704 761Fiop Perfect Humidity Dehumidification Outdoor Sound Power Total UnitEVAPORATOR-FAN Motor Efficiency EVAPORATOR-FAN Motor Data Standard Motor 581B FAN RPM AT Motor Pulley Setting with Standard Motor581B FAN RPM AT Motor Pulley Setting with HIGH-STATIC Motor EVAPORATOR-FAN Motor Data HIGH-STATIC Motors Operating WattsEconoMi$er Return-Air Pressure Drop EconoMi$er Barometric Relief Damper CharacteristicsEconoMi$er Outdoor-Air Leakage 581B036-150 Altitude CompensationAltitude Derating Factor Supply Electrical DataOFM FAN MotorElectrical Data RLA LRA FLA MCA MOCP†Nominal Voltage Combustion Power Minimum Unit Compressor RLA LRA Applications Maximum Operating OUTDOOR-AIR TemperatureApplication Data Application Data Perfect Humidity Dehumidification Option Pressure Enthalpy Curve Psychrometric Chart 581B072 Shown Horizontal Discharge Typical Piping and WiringVertical Discharge Typical Wiring Schematic Typical Wiring Schematic Tran 581B090-150 Typical Wiring SchematicOFC Operating Sequence for 581B090-150 Units ControlsOperating Sequence for 581B036-072 Units Controls Operating Sequence for 581B036-150 Size UnitsPart 2 Products Guide SpecificationsPart 1 General Guide Specifications Light Commercial Thermidistat Page Specifications Subject to Change Without Notice
Related manuals
Manual 52 pages 16.87 Kb Manual 40 pages 47.12 Kb

581B specifications

The Bryant 581B is an innovative and highly efficient gas furnace that stands out in the HVAC market for its remarkable performance, reliability, and advanced features. Designed to provide optimal heating comfort, the Bryant 581B is perfect for homeowners seeking both quality and energy efficiency.

One of the main features of the Bryant 581B is its impressive Annual Fuel Utilization Efficiency (AFUE) rating. With an AFUE rating of up to 80%, this gas furnace maximizes energy usage, ensuring that a significant portion of the fuel is converted into heat for your home. This efficiency not only translates into lower energy bills but also reduces the carbon footprint, making it an environmentally friendly choice.

The furnace is equipped with a multi-speed blower motor that enhances comfort by providing consistent airflow throughout the home. This technology adjusts to different heating demands, ensuring that every room reaches the desired temperature without the discomfort of hot or cold spots. The quiet operation of the blower motor also adds to the overall comfort, creating a peaceful home environment.

Another notable characteristic of the Bryant 581B is its durable construction. It features a robust heat exchanger built from high-quality materials, designed to withstand the rigors of daily use. The compact design of the furnace allows it to fit seamlessly into various spaces, making it an ideal choice for both new installations and replacement projects.

The Bryant 581B also comes with advanced safety features, including a self-diagnostic control board that monitors the system's performance. This feature allows for easy troubleshooting and maintenance, prolonging the life of the furnace. Additionally, the furnace is equipped with an induced draft blower that enhances venting efficiency and safety by ensuring that combustion gases are safely expelled from the home.

For homeowners looking for enhanced control, the Bryant 581B is compatible with a range of smart thermostats, providing the ability to monitor and adjust heating settings remotely. This integration with smart technology ensures that homeowners can maintain their desired comfort levels while maximizing efficiency.

In conclusion, the Bryant 581B gas furnace is a top-tier option that combines efficiency, durability, and modern technology. With its high AFUE rating, multi-speed blower, and advanced safety features, it promises to deliver unparalleled comfort and peace of mind for years to come. Whether for a new build or an upgrade, the Bryant 581B is an investment that pays off in both comfort and savings.