Bryant 581B manual Application Data

Page 50

APPLICATION DATA (cont)

Standard Unit Refrigerant Cycle

At point no. 1 in the pressure enthalpy curve, vapor leaving the compressor at a high pressure and a high temperature enters the condenser. The condenser removes heat from the refriger- ant, lowers its temperature, and changes it to a liquid. At point no. 2, the liquid leaves the condenser and enters a fixed expan- sion device that lowers the pressure of the refrigerant. At point no. 3, the liquid enters the evaporator coil, where the refrigerant increases in temperature and changes back to a vapor. At point no. 4, the vapor leaves the evaporator and reenters the com- pressor.

Refrigerant Cycle Using Perfect Humidity™ Dehumidification Package

When a subcooler coil is added to the rooftop unit, the refriger- ant is affected in such a way that the unit latent capacity is increased. The refrigerant cycle follows the same path from point no. 1 to point no. 2 as the standard refrigerant cycle with- out a subcooler (see the pressure enthalpy curve). However, at point no. 2, the liquid refrigerant enters the subcooler coil where the temperature is lowered further. At point no. 2A, this sub- cooled liquid enters the TXV, which drops the pressure of the liquid. At point no. 2B, the liquid enters the fixed orifice metering device. The refrigerant leaves this device as a saturated vapor and enters the evaporator at point no. 2C. The improved refrig- eration effect can now be seen between point no. 2C and point no. 3. The increase in the total refrigeration effect is the addi- tional enthalpy gained from point no. 2C to point no. 3. However, the subcooler coil rejects this added refrigeration effect to the air downstream of the evaporator coil, thus maximizing the over- all latent effect. This improved latent effect is a direct result of the addition of the Perfect Humidity subcooler coil to the refrig- erant cycle.

Latent Capacity Effects

Refer to the psychrometric chart to see how the sensible heat factor decreases when the optional Perfect Humidity dehumidifi- cation package is installed. This chart contains data for the 5-ton 581B unit operation, both with and without the Perfect Humidity package, at 1750 cfm. Point no. 1 on the chart repre- sents the return-air dry bulb (80 F) and wet bulb (67 F) condi- tions. Point no. 2 represents the supply-air conditions for a standard 581B rooftop unit without the Perfect Humidity dehu- midification package. Point no. 3 represents the supply-air con- ditions for a 581B rooftop unit with the Perfect Humidity package. By connecting point no. 1 and point no. 2 on the chart and finding the intersection on the sensible heat factor scale, the sensible heat factor is 0.73. Connect point no. 1 and point no. 3, and see that the sensible heat factor is 0.58. This is a 17.5% increase in latent capacity for the given conditions. This increase in latent capacity allows the 581B rooftop units to remove more moisture from the conditioned space; thus lower- ing the humidity levels.

Dehumidification Effects

Further evidence of dehumidification can be seen by analyzing the pounds of water per pound of dry air found in the supply air. At point no. 2 in the psychrometric chart, there are 65 grains (0.0092 lb) of moisture per pound of dry air. At point no. 3, there are 58 grains (0.0083 lb) of moisture per pound of dry air. This is a 12.1% decrease in the amount of water in the supply air.

17.PERFECT HUMIDITY DEHUMIDIFICATION PACKAGE OPERATING PERFORMANCE — Perfect Humidity dehu- midification package operation does not affect the electrical data. The electrical data remains the same either with or without the Perfect Humidity package.

The operating and shipping weights will be slightly increased with the addition of the Perfect Humidity sub- cooler. See the Physical Data table for added base unit weight with this option.

Refer to cooling performance data, both with and without the Perfect Humidity dehumidification package. Note the

greatly improved latent capacity with the Perfect Humidity dehumidification package.

Static pressure is also slightly affected by the addition of the Perfect Humidity dehumidification package. See Static Pressure Drop table on page 40 when using this option.

18.PERFECT HUMIDITY DEHUMIDIFICATION PACKAGE

FEATURES AND BENEFITS

The Perfect Humidity dehumidification package can improve the humidity control of your rooftop equipment by up to 40%. This greatly reduces the risk of sick building syndrome by reducing biological growth in both ductwork and the rest of the building.

The Perfect Humidity dehumidification package improves comfort levels in the building by better controlling the humidity. This improved comfort level allows building tenants to raise the cooling set point on the thermostats for accumulated energy savings.

Better humidity control lowers the risk of humidity-induced property damage.

The Perfect Humidity dehumidification package permits build- ing refrigerators and freezers to operate more efficiently due to lower relative humidity levels. This is the perfect solution for supermarket applications.

The Perfect Humidity subcooling circuit can be operated by a humidity sensor. If the sensor is used, the Perfect Humidity circuit will then only operate when needed. If the humidity lev- els in the occupied space are acceptable (such as in the spring and fall seasons), the Perfect Humidity circuit will not operate. The rooftop unit is then able to operate to its full sen- sible potential, which provides more efficient performance and energy savings.

At lower outdoor temperatures, rooftop units with dehumidifi- cation devices are subject to low suction pressure conditions. The Perfect Humidity dehumidification package contains a low-pressure switch that deactivates the Perfect Humidity dehumidification package under low suction pressure condi- tions without deactivating the compressors.

Improved humidity control allows increased outdoor-air venti- lation in hot and humid geographical areas. Humidity control also helps to improve the indoor-air quality of the building.

The Perfect Humidity dehumidification package is factory installed. There are no additional field installation costs. There is also no need to purchase a roof curb from another manu- facturer, as standard Bryant roof curbs will accommodate the 581B rooftop units which have the Perfect Humidity dehumidi- fication package option installed.

The Perfect Humidity dehumidification package is engineered and manufactured by Bryant for Bryant rooftop units. All appli- cation support, service, and warranty issues can therefore be handled through one company.

The slightly lower sensible capacities obtained when using the Perfect Humidity dehumidification package allow the unit to operate for an extended period of time. The more the unit operates, the more air is exposed to the subcooling coil. This rooftop unit increased latent capacity results in lower relative humidity levels in the occupied space.

It is no longer necessary to oversize equipment and add reheat devices to properly dehumidify your building. In a typi- cal scenario, a building owner may need 39,000 Btuh of sensi- ble capacity and 23,000 Btuh of latent capacity (62,000 total Btuh). To accomplish this without the Perfect Humidity dehu-

midification package, a 71/2-ton unit with a reheat device would be necessary to attain the higher latent capacity required. This results in a large up-front expense to oversize the equipment from a standard 5-ton to a 71/2-ton unit.

The building owner can now purchase a 5-ton unit with the Perfect Humidity dehumidification package for a small addi- tional up-front charge, and no reheat device will be necessary to satisfy the cooling requirements. This reduces both installa- tion costs and operating costs throughout the life of the product.

50

Image 50
Contents Unit 581B036-072 FEATURES/BENEFITSEasy Maintenance and Installation Unit 581B090-150FEATURES/BENEFITS Table of Contents Model Number Nomenclature ServiceabilityCompressors and Safety Switches are Easily Accessible for Indoor AIR Quality IAQARI* Capacities Heating Capacities and EfficienciesTime Guard II Control Options and AccessoriesLOW Ambient Controls Liquid Propane Conversion KITOptions and Accessories Bryant Commercial Programmable Thermostat Hail Guard Accusensor II Enthalpy ControlCoil Guard Grille Bryant Light Commercial ThermidistatPhysical Data Hi-Static090N††† Physical Data060N††† 120N†††090 102 120 150 Nominal Capacity tons LOSS-OF-CHARGE LOW-PRESSURE Base Unit Dimensions 581B036-072Base Unit Dimensions 581B090-150Accessory Dimensions 581B036-072 Control Accessory Dimensions 581B090-150Connector ALT Drain PKG. Accy GAS CRRFCURB003A00Determine NET Cooling Capacity Selection Procedure With 581B048 ExampleII Select Unit Based on Required Cooling Capacity Performance Data Cooling CapacitiesPerformance Data Cooling Capacities581B090 71/2 Tons 581B120 10 Tons Temp F Cooling CAPACITIES, Units with Perfect Humidity Option Cooling CAPACITIES, Units with Perfect Humidity Option 2250/0.10 3000/0.11 3750/0.14 Condenser 134.3 581B036 3 Tons HIGH-STATIC Motor Airflow FAN Performance Vertical Discharge Units581B036 3 Tons Standard Motor Airflow 581B048 4 Tons HIGH-STATIC Motor Airflow FAN Performance Vertical Discharge Units581B048 4 Tons Standard Motor Airflow 581B060 5 Tons HIGH-STATIC Motor 581B060 5 Tons Standard Motor SINGLE-PHASE Units Airflow581B060 5 Tons Standard Motor THREE-PHASE Units Airflow 581B072 6 Tons Standard Motor Airflow 581B072 6 Tons HIGH-STATIC Motor581B090 71/2 Tons Standard Motor 581B090 71/2 Tons HIGH-STATIC Motor Airflow581B102 81/2 Tons HIGH-STATIC Motor Airflow 581B120 10 Tons Standard and HIGH-STATIC Motor Airflow FAN Performance Horizontal Discharge Units FAN Performance Horizontal Discharge Units 581B060 5 Tons Standard Motor 3-PHASE Units Airflow 581B060 5 Tons HIGH-STATIC Motor Airflow2000 1022 1121 1188 1264 Bhp Rpm 1800 885 942 10471900 982 1084 1160 1223 2100 1063 1140 1196 1272581B090 71/2 Tons HIGH-STATIC Motor Airflow 2700 573 648 711 770 798 827 Bhp Rpm 2550 627 692 754 783 8122600 557 634 698 759 787 816 2800 588 662 723 782 809 8373300 537 692 751 828 3100 500 669 731 8083200 519 680 741 818 3400 561 704 761Fiop Perfect Humidity Dehumidification Outdoor Sound Power Total UnitEVAPORATOR-FAN Motor Efficiency EVAPORATOR-FAN Motor Data Standard Motor 581B FAN RPM AT Motor Pulley Setting with Standard Motor581B FAN RPM AT Motor Pulley Setting with HIGH-STATIC Motor EVAPORATOR-FAN Motor Data HIGH-STATIC Motors Operating WattsEconoMi$er Return-Air Pressure Drop EconoMi$er Barometric Relief Damper CharacteristicsEconoMi$er Outdoor-Air Leakage 581B036-150 Altitude CompensationAltitude Derating Factor Supply Electrical DataOFM FAN MotorElectrical Data RLA LRA FLA MCA MOCP†Nominal Voltage Combustion Power Minimum Unit Compressor RLA LRA Applications Maximum Operating OUTDOOR-AIR TemperatureApplication Data Application Data Perfect Humidity Dehumidification Option Pressure Enthalpy Curve Psychrometric Chart 581B072 Shown Horizontal Discharge Typical Piping and WiringVertical Discharge Typical Wiring Schematic Typical Wiring Schematic Tran 581B090-150 Typical Wiring SchematicOFC Operating Sequence for 581B090-150 Units ControlsOperating Sequence for 581B036-072 Units Controls Operating Sequence for 581B036-150 Size UnitsPart 2 Products Guide SpecificationsPart 1 General Guide Specifications Light Commercial Thermidistat Page Specifications Subject to Change Without Notice
Related manuals
Manual 52 pages 16.87 Kb Manual 40 pages 47.12 Kb

581B specifications

The Bryant 581B is an innovative and highly efficient gas furnace that stands out in the HVAC market for its remarkable performance, reliability, and advanced features. Designed to provide optimal heating comfort, the Bryant 581B is perfect for homeowners seeking both quality and energy efficiency.

One of the main features of the Bryant 581B is its impressive Annual Fuel Utilization Efficiency (AFUE) rating. With an AFUE rating of up to 80%, this gas furnace maximizes energy usage, ensuring that a significant portion of the fuel is converted into heat for your home. This efficiency not only translates into lower energy bills but also reduces the carbon footprint, making it an environmentally friendly choice.

The furnace is equipped with a multi-speed blower motor that enhances comfort by providing consistent airflow throughout the home. This technology adjusts to different heating demands, ensuring that every room reaches the desired temperature without the discomfort of hot or cold spots. The quiet operation of the blower motor also adds to the overall comfort, creating a peaceful home environment.

Another notable characteristic of the Bryant 581B is its durable construction. It features a robust heat exchanger built from high-quality materials, designed to withstand the rigors of daily use. The compact design of the furnace allows it to fit seamlessly into various spaces, making it an ideal choice for both new installations and replacement projects.

The Bryant 581B also comes with advanced safety features, including a self-diagnostic control board that monitors the system's performance. This feature allows for easy troubleshooting and maintenance, prolonging the life of the furnace. Additionally, the furnace is equipped with an induced draft blower that enhances venting efficiency and safety by ensuring that combustion gases are safely expelled from the home.

For homeowners looking for enhanced control, the Bryant 581B is compatible with a range of smart thermostats, providing the ability to monitor and adjust heating settings remotely. This integration with smart technology ensures that homeowners can maintain their desired comfort levels while maximizing efficiency.

In conclusion, the Bryant 581B gas furnace is a top-tier option that combines efficiency, durability, and modern technology. With its high AFUE rating, multi-speed blower, and advanced safety features, it promises to deliver unparalleled comfort and peace of mind for years to come. Whether for a new build or an upgrade, the Bryant 581B is an investment that pays off in both comfort and savings.