STEP 1 – Activate the SIM and Setup the Customer Account

The communicator requires a subscriber account (customer account) to be setup with AlarmNet Direct. This is accomplished by registering the communicator's iGSM communications module with AlarmNet. Registering, enables the fire panel to send reports.

To setup the customer account you will need to contact the central monitoring station to get account information, and have access to the AlarmNet Direct website. To access the AlarmNet Direct website visit – https://services.alarmnet.com/AlarmNetDirect

If you do not wish to use the AlarmNet Direct website, you may call AlarmNet to setup the account, just phone 800-222-6525, then select option 1.

(Monday–Friday 8:00 am to 9:00 pm, Saturday 9:00 am to 5:30 pm EST)

Have the following information ready:

Primary City ID (two digits), obtained from your monitoring station.

Primary Central Station ID (two digits), obtained from your monitoring station.

Primary Subscriber ID (four digits), obtained from your monitoring station.

Communication Module's MAC ID, and MAC CRC number located on outside of box, and inside of the module.

Note: The IPGSM-DP comes with a SIM (Subscriber Identity Module) that needs to be activated.

1.To activate the SIM, log into the AlarmNet Direct website and choose “SIM Activation/Status”, then enter the required information. Click Activate SIM.

2.Setup the customer account by choosing "Program New Device GSM/I", enter the required information. When complete, click DONE.

STEP 2 – Register the Communications Module with AlarmNet

Registering the module activates the account with AlarmNet and enables the fire system's control panel to send reports. There are three methods that can be used to register the communications module.

Register the module by logging into AlarmNet Direct and choosing “Show Programmed Devices GSM/I”. Search for the account using the Account Information or MAC ID. Under the “Actions” column, use the pulldown menu and choose Register. OR

After the IPGSM-DP is installed and programmed, you can register the module by clicking the Tamper Switch 3 times. OR

After the IPGSM-DP is installed and programmed, you can register the module using the 7720P Programming tool. Simply: Press [Shift ] then press []. Please wait for "Registration SUCCESS" message.

2

Image 4 Contents
IPGSM-DP Contents General Information InstallationOperation Activate the SIM and Setup the Customer Account Register the Communications Module with AlarmNetDetermine the Signal Strength and Select a Location Mount and WirePowerBoost1 Transformer N8167 ConduitProgram the Communications Module 7720P ProgrammerConfigure the Fire Panel Test the SystemDialer Capture Module Information IPGSM-DP Trouble Detection InformationLED Display Information PowerBoost1 Module Information ActiveIGSM Communications Module Information OFF Normal Slow Blink Loss of communication withIPGSM-DP Specifications RF SpecificationsPage Wiring Diagram + BatteryÊ800-08074AŠ